Indoor units

Slim duct units

Model MMD-AP

 

0071SPH

0091SPH

0121SPH

0151SPH

0181SPH

Cooling capacity*

kW

2.2

2.8

3.6

4.5

5.6

Heating capacity

kW

2.5

3.2

4.0

5.0

6.3

Electrical data

 

 

 

 

 

 

Power supply

V-ph-Hz

230-1-50 (voltage range 220-240 V) - power supply to indoor unit only

 

Operating current

A

0.29

0.29

0.31

0.32

0.39

Power input

kW

0.039

0.039

0.043

0.045

0.054

Starting current

A

0.51

0.51

0.54

0.56

0.68

Unit appearance

 

Zinc hot dipping steel plate

 

 

 

Unit dimensions

 

 

 

 

 

 

Height

mm

210

210

210

210

210

Width

mm

845

845

845

845

845

Depth

mm

645

645

645

645

645

Unit weight

kg

22

22

22

23

23

Heat exchanger

 

Finned tube

 

 

 

 

Sound proofing/heat insulating material

 

Polyethylene foam and polyurethane foam

 

 

 

Fan type

 

Centrifugal fan

 

 

 

 

Fan motor power input

W

60

60

60

60

60

Air flow

 

 

 

 

 

 

High

l/s

150

150

167

192

217

Medium

l/s

131

131

145

167

189

Low

l/s

111

111

125

145

161

Air flow

 

 

 

 

 

 

High

m3/h

540

540

600

690

780

Medium

m3/h

470

470

520

600

680

Low

m3/h

400

400

450

520

580

Static pressure (factory setting)

Pa

6

6

5

5

4

Static pressure (max.)

Pa

-16/-31/-46

-16/-31/-46

-15/-30/-45

-15/-30/-45

-14/-29/-44

Air filter pressure loss

Pa

4

4

5

5

6

Lower air inlet

 

 

 

 

 

 

Sound power level (high/medium/low)

dB(A)

49/46/43

49/46/43

51/48/45

52/49/46

53/51/49

Sound pressure level (high/medium/low)**

dB(A)

36/33/30

36/33/30

38/35/32

39/36/33

40/38/36

Rear air inlet

 

 

 

 

 

 

Sound power level (high/medium/low)

dB(A)

41/39/37

41/39/37

42/40/38

45/43/41

46/44/42

Sound pressure level (high/medium/low)**

dB(A)

28/26/24

28/26/24

29/27/25

32/30/28

33/31/29

Air filter

 

Standard long-life filter supplied

 

 

 

Controller

 

Remote controller

 

 

 

 

Connection pipes

 

 

 

 

 

 

Gas connection diameter

in

3/8

3/8

3/8

1/2

1/2

Liquid connection diameter

in

1/4

1/4

1/4

1/4

1/4

Drain connection, nom. dia (polyvinyl tube)

in

1

1

1

1

1

Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

*Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main

piping and 2.5 m of branch piping connected with 0 metre height.

**The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

51

Page 51
Image 51
Toshiba HFC R-410A manual Indoor units Slim duct units, Lower air inlet Sound power level high/medium/low