Toshiba HFC R-410A manual Indoor units High-pressureducted units

Models: HFC R-410A

1 108
Download 108 pages 43.4 Kb
Page 50
Image 50
Indoor units

Indoor units

High-pressure ducted units

Model MMD-AP

 

0181H

0241H

0271H

0361H

0481H

0721H

0961H

Cooling capacity*

kW

5.6

7.1

8.0

11.2

14.0

22.4

28.0

Heating capacity

kW

6.3

8.0

9.0

12.5

16.0

25.0

31.5

Electrical data

 

 

 

 

 

 

 

 

Power supply

V-ph-Hz

230-1-50 (voltage range 220-240 V) - power supply to indoor unit only

 

 

Operating current

A

0.81

1.35

1.35

1.63

1.84

5.25

5.52

Power input

kW

0.184

0.299

0.299

0.368

0.414

1.200

1.260

Power factor

%

99

96

96

98

98

99

99

Starting current

A

1.3

3.5

3.5

4.1

4.8

13.6

14.8

Unit appearance

 

Zinc hot dipping steel plate

 

 

 

 

 

Unit dimensions

 

 

 

 

 

 

 

 

Height

mm

380

380

380

380

380

470

470

Width

mm

850

850

850

850

1200

1380

1380

Depth

mm

660

660

660

660

660

1250

1250

Unit weight

kg

50

52

52

56

67

150

150

Heat exchanger

 

Finned tube

 

 

 

 

 

 

Sound proofing/heat insulating material

 

Non-flammable insulation

 

 

 

 

 

Fan type

 

Centrifugal fan

 

 

 

 

 

 

Fan motor power input

W

160

160

160

260

260

370 x 3

370 x 3

Air flow

 

 

 

 

 

 

 

 

High

l/s

300

439

439

533

700

1200

1400

Medium

l/s

250

367

367

445

583

1000

1167

Low

l/s

200

295

295

356

467

800

933

Air flow

 

 

 

 

 

 

 

 

High

m3/h

1080

1580

1580

1920

2520

4320

5040

Medium

m3/h

900

1320

1320

1600

2100

3600

4200

Low

m3/h

720

1060

1060

1280

1680

2880

3360

Static pressure (factory setting)

Pa

137

137

137

137

137

137

137

Static pressure (low/medium/high)

Pa

68.6/137/196

68.6/137/196

68.6/137/196

68.6/137/196

68.6/137/196

68.6/137/196

68.6/137/196

Sound power level (high)

dB(A)

50

53

53

53

53

62

63

Sound pressure level (high/medium/low)**

dB(A)

37/35/33

40/38/36

40/38/36

40/38/36

40/38/36

49/47/45

50/48/46

Air filter

 

Optional or field-supplied

 

 

 

 

 

Controller

 

Remote controller

 

 

 

 

 

Connection pipes

 

 

 

 

 

 

 

 

Gas connection diameter

in

1/2

5/8

5/8

5/8

5/8

7/8

7/8

Liquid connection diameter

in

1/4

3/8

3/8

3/8

3/8

1/2

1/2

Drain connection, nom. dia***

in

1

1

1

1

1

1

1

Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

*Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main

piping and 2.5 m of branch piping connected with 0 metre height.

**The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

***Male screw connection one side