Toshiba HFC R-410A manual Indoor unit - standard ducted unit

Models: HFC R-410A

1 108
Download 108 pages 43.4 Kb
Page 81
Image 81
Indoor unit - standard ducted unit

Indoor unit - standard ducted unit

MMD-AP0071BH, AP0091BH, AP0121BH, AP0151BH, AP0181BH, AP0241BH, AP0271BH, AP0301BH, AP0361BH, AP0481BH, AP0561BH

Model MMD-

A

B

C

D

E

ØF

ØG

AP0071BH, AP0091BH, AP0121BH

616

550

350

600

470

3/8”

1/4”

AP0151BH, AP0181BH

766

700

500

750

620

1/2”

3/8”

AP0241BH, AP0271BH, AP0301BH

1066

1000

800

1050

920

5/8”

3/8”

AP0361BH, AP0481BH, AP0561BH

1416

1350

1150

1400

1270

5/8”

3/8”

Note: High-efficiency and deodorant filters cannot be used together.

Note: Be sure to provide an inspection hole A in the position indicated in the following figure for maintenance of the equipment.

Drain riser pipe

Legend

11.

Panel CL

1.

Ø125 knockout hole (for air intake)

12.

Ceiling opening

2.

10-Ø4 tapping screw Ø160

13.

Ø26 power supply, remote controller cable conduit

3.

When attaching directly

14.

Refrigerant pipe connection (liquid ØG)

4.

Hanging bolt pitch

15.

Air outlet

5.

Hanging bolt 4-M10 (field-supplied)

16.

Refrigerant pipe connection (gas ØF)

6.

Ceiling opening

17.

Inspection hole A

7.

Drain pipe connection (inner Ø32 vinyl chloride pipe VP25 connection)

18.

For air filter maintenance

8.

Unit dimension

19.

Air filter

9.

Hanging bolt pitch

20.

Inspection hole B

10.Air inlet

All dimensions are given in mm.

81

Page 81
Image 81
Toshiba HFC R-410A manual Indoor unit - standard ducted unit