4.Equipment selection procedure

1. Selection flow chart

1. Determination of indoor air conditioning load

2. Preliminary selection of indoor units

3. Preliminary selection of outdoor unit with indoor units

4. Capacity correction for piping length/height between indoor and outdoor units

5. Capacity correction based on indoor and outdoor temperature

6. Validate preliminary selection of indoor units

No

7. Confirmation of selection for indoor unit and outdoor units

End

2. Indoor unit and outdoor unit combination

For indoor unit, the capacity code is decided for each model size.

Model size

007

009

012

015

018

024

027

030

036

048

056

072

096

Cooling capacity, kW

2.2

2.8

3.6

4.5

5.6

7.1

8.0

9.0

11.2

14.0

16.0

22.4

28.0

Capacity code

0.8

1

1.25

1.7

2

2.5

3

3.2

4

5

6

8

10

Note: Model size: corresponding to Btu/h. Capacity code: corresponding to horsepower.

For outdoor unit, maximum number of connectable indoor units and total capacity code of indoor units are decided.

Outdoor unit

Outdoor unit

Capacity code

Max. No. of

Total indoor unit

(cooling only)

(heat pump)

of outdoor unit

indoor units

capacity code

MMY-MAP0501T8

MMY-MAP0501HT8

5

8

2.5 to 6.75

MMY-MAP0601T8

MMY-MAP0601HT8

6

10

3 to 8.1

MMY-MAP0801T8

MMY-MAP0801HT8

8

13

4 to 10.8

MMY-MAP1001T8

MMY-MAP1001HT8

10

16

5 to 13.5

MMY-MAP1201T8

MMY-MAP1201HT8

12

20

6 to 16.2

MMY-AP1401T8

MMY-AP1401HT8

14

23

7 to 18.9

MMY-AP1601T8

MMY-AP1601HT8

16

27

8 to 21.6

MMY-AP1801T8

MMY-AP1801HT8

18

30

9 to 24.3

MMY-AP2001T8

MMY-AP2001HT8

20

33

10 to 27.0

MMY-AP2201T8

MMY-AP2201HT8

22

37

11 to 29.7

MMY-AP2211T8

MMY-AP2211HT8

22

37

11 to 29.7

MMY-AP2401T8

MMY-AP2401HT8

24

40

12 to 32.4

MMY-AP2411T8

MMY-AP2411HT8

24

40

12 to 32.4

MMY-AP2601T8

MMY-AP2601HT8

26

43

13 to 35.1

MMY-AP2801T8

MMY-AP2801HT8

28

47

14 to 37.8

MMY-AP3001T8

MMY-AP3001HT8

30

48

15 to 40.5

MMY-AP3201T8

MMY-AP3201HT8

32

48

16 to 43.2

MMY-AP3211T8

MMY-AP3211HT8

32

48

16 to 43.2

MMY-AP3401T8

MMY-AP3401HT8

34

48

17 to 45.9

MMY-AP3411T8

MMY-AP3411HT8

34

48

17 to 45.9

MMY-AP3601T8

MMY-AP3601HT8

36

48

18 to 48.6

MMY-AP3611T8

MMY-AP3611HT8

36

48

18 to 48.6

MMY-AP3801T8

MMY-AP3801HT8

38

48

19 to 51.3

MMY-AP4001T8

MMY-AP4001HT8

40

48

20 to 54.0

MMY-AP4201T8

MMY-AP4201HT8

42

48

21 to 56.7

MMY-AP4401T8

MMY-AP4401HT8

44

48

22 to 59.4

MMY-AP4601T8

MMY-AP4601HT8

46

48

23 to 62.1

MMY-AP4801T8

MMY-AP4801HT8

48

48

24 to 64.8

50 to 135% of outdoor unit capacity

19

Page 19
Image 19
Toshiba HFC R-410A manual Equipment selection procedure, Selection flow chart, Indoor unit and outdoor unit combination