Toshiba HFC R-410A manual Indoor units Ceiling-suspendedunits

Models: HFC R-410A

1 108
Download 108 pages 43.4 Kb
Page 52
Image 52
Indoor units

Indoor units

Ceiling-suspended units

Model MMC-AP

 

0151H

0181H

0241H

0271H

0361H

0481H

Cooling capacity*

kW

4.5

5.6

7.1

8.0

11.2

14.0

Heating capacity

kW

5.0

6.3

8.0

9.0

12.5

16.0

Electrical data

 

 

 

 

 

 

 

Power supply

V-ph-Hz

230-1-50 (voltage range 220-240 V) - power supply to indoor unit only

 

 

Operating current

A

0.29

0.32

0.42

0.42

0.78

0.84

Power input

kW

0.033

0.038

0.050

0.050

0.091

0.110

Starting current

A

0.43

0.48

0.62

0.62

1.17

1.25

Unit appearance

 

White (Munsell 10Y 9.3/0.4)

 

 

 

 

Unit dimensions

 

 

 

 

 

 

 

Height

mm

210

210

210

210

210

210

Width

mm

910

910

1180

1180

1595

1595

Depth

mm

680

680

680

680

680

680

Unit weight

kg

22

22

26

26

34

34

Heat exchanger

 

Finned tube

 

 

 

 

 

Sound proofing/heat insulating material

 

Non-flammable insulation

 

 

 

 

Fan type

 

Centrifugal fan

 

 

 

 

 

Fan motor power input

W

30

30

40

40

80

80

Air flow

 

 

 

 

 

 

 

High

l/s

200

217

308

308

458

500

Medium

l/s

167

183

250

250

383

433

Low

l/s

150

150

233

233

333

367

Air flow

 

 

 

 

 

 

 

High

m3/h

720

780

1110

1110

1650

1800

Medium

m3/h

600

660

900

900

1380

1560

Low

m3/h

540

540

840

840

1200

1320

Sound power level (high/medium/low)

dB(A)

48/45/43

49/46/43

51/49/46

51/49/46

54/51/48

56/53/50

Sound pressure level (high/medium/low)**

dB(A)

35/32/30

36/33/30

38/36/33

38/36/33

41/38/35

43/40/37

Air filter

 

Standard long-life filter supplied

 

 

 

 

Controller

 

Remote controller

 

 

 

 

 

Room thermostat

 

Supplied

 

 

 

 

 

Connection pipes

 

 

 

 

 

 

 

Gas connection diameter

in

1/2

1/2

5/8

5/8

5/8

5/8

Liquid connection diameter

in

1/4

1/4

3/8

3/8

3/8

3/8

Drain connection, nom. dia (polyvinyl tube)

in

3/4

3/4

3/4

3/4

3/4

3/4

Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

*Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main piping and 2.5 m of branch piping connected with 0 metre height.

**The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

52

Page 52
Image 52
Toshiba HFC R-410A manual Indoor units Ceiling-suspendedunits