Indoor units

Concealed chassis units

Model MML-AP

 

0071BH

0091BH

0121BH

0151BH

0181BH

0241BH

Cooling capacity*

kW

2.2

2.8

3.6

4.5

5.6

7.1

Heating capacity

kW

2.5

3.2

4.0

5.0

6.3

8.0

Electrical data

 

 

 

 

 

 

 

Power supply

V-ph-Hz

230-1-50 (voltage range 220-240 V) - power supply to indoor unit only

 

 

Operating current

A

0.25

0.25

0.25

0.45

0.45

0.46

Power input

kW

0.056

0.056

0.056

0.090

0.090

0.095

Power factor

%

97

97

97

87

87

90

Starting current

A

0.60

0.60

0.60

0.80

0.80

1.00

Unit appearance

 

Zinc hot dipping steel plate

 

 

 

 

Unit dimensions

 

 

 

 

 

 

 

Height

mm

600

600

600

600

600

600

Width

mm

745

745

745

1045

1045

1045

Depth

mm

220

220

220

220

220

220

Unit weight

kg

21

21

21

29

29

29

Heat exchanger

 

Finned tube

 

 

 

 

 

Sound proofing/heat insulating material

 

Non-flammable insulation

 

 

 

 

Fan type

 

Centrifugal fan

 

 

 

 

 

Fan motor power input

W

19

19

19

70

70

70

Air flow

 

 

 

 

 

 

 

High

l/s

128

128

128

206

206

264

Medium

l/s

111

111

111

167

167

220

Low

l/s

83

83

83

136

136

178

Air flow

 

 

 

 

 

 

 

High

m3/h

460

460

460

740

740

950

Medium

m3/h

400

400

400

600

600

790

Low

m3/h

300

300

300

490

490

640

Static pressure

kPa

0

0

0

0

0

0

Sound power level (high/medium/low)

dB(A)

49/47/45

49/47/45

49/47/45

49/47/45

49/47/45

55/50/46

Sound pressure level (high/medium/low)**

dB(A)

36/34/32

36/34/32

36/34/32

36/34/32

36/34/32

42/37/33

Air filter

 

Standard single filter supplied

 

 

 

 

Controller

 

Remote controller

 

 

 

 

 

Connection pipes

 

 

 

 

 

 

 

Gas connection diameter

in

3/8

3/8

3/8

1/2

1/2

5/8

Liquid connection diameter

in

1/4

1/4

1/4

1/4

1/4

3/8

Drain connection, nom. dia.***

in

3/4

3/4

3/4

3/4

3/4

3/4

Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

*Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main piping and 2.5 m of branch piping connected with 0 metre height.

**The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

***Male screw connection one side.

56