2.3.VF-MB1/S15 Communication parameters

In a network, VF-MB1/S15 (PDP003Z) serves as a PROFIBUS slave device. PDP003Z configuration is set by the following parameters.

Parameter

Function

Adjustment range

Default setting

c150

PDP003Z

2 to

126

126

 

Station address

The station address "126" cannot exchange data.

 

c151

PDP003Z

0:

12 Mbit/s

-

 

Baud rate Monitor

1:

6

Mbit/s

 

2:3 Mbit/s

3:1.5 Mbit/s

4:500 kbit/s

5:187.5 kbit/s

6:93.75 kbit/s

7:19.2 kbit/s

8:9.6 kbit/s

c152

PDP003Z

0Telegram 1 (PROFIdrive)

-

 

Profile Monitor

1Telegram 100 (Vender Spec. 1)

 

 

 

2Telegram 101 (Vender Spec. 2)

 

 

 

3Telegram 102 (Vender Spec. 3)

 

c154

JOG1 Frequency

0.0 to 20.0Hz

5.0Hz

 

(STW.8)

 

 

c155

JOG2 Frequency

0.0 to 20.0Hz

5.0Hz

 

(STW.9)

 

 

c156

Tmax

0.1 to 60.0s

10.0s

 

(ZSW.8)

 

 

c157

Tolerance

0.1 to 99.0%

50.0%

 

(ZSW.8)

 

 

c100

Communication error

0.0 to 100.0 sec

0.0

 

detection delay time

 

 

c101

Drive operation at the

0: Stop and Communication release *

4

 

communications

(follows cmod and fmod setting)

 

 

loss action

1: None

 

 

(Network wire breaks)

2: Deceleration stop

 

 

 

3: Coast stop

 

 

 

4: Emergency stop

 

 

 

5: Preset speed operation command

 

 

 

(Operating at the preset speed operation frequency

 

 

 

set with c102)

 

c102

Preset speed

0: None

0

 

operation selection

1 to 15: Preset speed (sr1 - sr7, f287 - f295)

 

c103 **

Communication

0: Disconnection detection

1

 

time-out condition

1: When communication mode enable (Both cmod

 

 

selection

and fmod are set CANopen or COM option)

 

 

 

2: 1+Driving operation

 

f899

Network option

0: None

0

 

reset setting

1: Resetting the PDP003Z and the drive

 

fd67

PDP003Z versioon

PDP003Z firmware version

-

 

 

(ex. 0x1101 means "V1.01")

 

*Do not set at VF-MB1 V1.00.

**It is necessary to enable "Watchdog" function with the configurator.

***When the parameters are changed or to reset err8, the power must be cycled (or set f899 to 1). After reset, the parameter changes become effective.

Set 1 to f899 by the PROFIBUS communication might not be able to be set.

****When fmod or cmod is set to “Communication option”, VF-MB1/S15 drives without Net Reference (STW Bit 13) or Net Control (STW Bit 12) at PROFIdrive.

Please note that drive keeps driving when the communication is lost if 1 (None) is set to Caution the parameter c101 (Drive operation at the communications loss action).