E6581738
3.5.Access to the PROFIBUS parameter
In the cyclic
| PKW |
|
|
|
| PZD | ||
| (Parameter ID/value) |
| Process data (cyclically) | |||||
|
|
|
|
| PZD1 |
| PZD2 | |
PKE | IND |
| PWE |
| STW |
| HSW | |
|
|
|
|
| ZSW |
| HIW | |
Octet 1 Octet 2 | Octet 3 Octet 4 Octet 5 | Octet 6 Octet 7 | Octet 8 |
|
|
|
PKE (Parameter ID)
15 14 13 12
11
10 | 9 | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 |
AK | SPM | PNU |
(Task ID/Response ID) |
| (Parameter number) |
AK (Request from Master to PDP003Z)
Request ID | Function | Note |
0 | No task |
|
1 | Request parameter value | for PNU access |
2 | Change parameter value (word) | for PNU access |
6 | Request parameter value (array) | for PNU access, |
|
| access |
7 | Change parameter value (array) | for PNU access, |
|
| access |
AK (Response from PDP003Z to Master)
Response ID | Function |
0No response
1Transfer parameter value (word)
4 | Transfer parameter value (array) |
7Task can not be executed, followed by error number 0 = Illegal parameter number
1 = Parameter value cannot be changed
2 = Lower or upper limit violated
3 = Erroneous sub index
11 = No parameter change rights
17 = Task cannot be executed due to operating status (e.g. parameter is currently
18 = Other error
102 = Request not supported
SPM: always 0.
- 15 -