E6581738
4.2.12.fc91 (Alarm code)
bit
Function
0
1
Remarks
(Code displayed on
the panel)
0 | Normal | Alarming | c flicking | ||
1 | Inverter over load alarm | Normal | Alarming | l flicking | |
2 | Motor over load alarm | Normal | Alarming | l flicking | |
3 | Over heat alarm | Normal | Alarming | h flicking | |
4 | Over voltage alarm | Normal | Alarming | p flicking | |
5 | Main circuit undervoltage alarm | Normal | Alarming | - | |
6 | main device overheat alarm | Normal | Alarming | l flicking | |
7 | Under current alarm | Normal | Alarming | - | |
8 | Normal | Alarming | - | ||
9 | Braking resistor overload alarm | Normal | Alarming | - | |
10 | Cumulative operation hours alarm | Normal | Alarming | - | |
11 | Option communication alarm | Normal | Alarming | - | |
12 | Serial communication alarm | Normal | Alarming | - | |
13 | MOFFMS (MSrelay off or MOFF) | Normal | Alarming | - | |
14 | Stop after instantaneous power off | - | Dec., Under | Refer to f302 | |
stop | value | ||||
|
|
| |||
15 | Stop after LL continuance time | - | Dec., Under | Refer to f256 | |
stop | value | ||||
|
|
|
4.2.13.fd06 (Input TB Status)
bit | TB Name | Function (Parameter) | 0 | 1 |
0F Input terminal function selection 1 (f111)
1R Input terminal function selection 2 (f112)
2 | RES | Input terminal function selection 3 (f113) |
|
| |
3 | S1 | Input terminal function selection 4 (f114) | OFF | ON | |
4 | S2 | Input terminal function selection 5 (f115) | |||
|
| ||||
5 | S3 | Input terminal function selection 6 (f116) |
|
| |
6 | VIB*1 | Input terminal function selection 7 (f117) |
|
| |
7 | VIA*1 | Input terminal function selection 8 (f118) |
|
| |
5 to 15 | (Undefined) | - | - | - |
Note: The bit described "Undefined" is unstable. Do not use the bit for the judgment.
*1: VIA/ VIB are input terminal function when f109 is logic input. *The input terminal function is selected by each parameter.
- 27 -