E6581738

3.7.Access to VF-MB1/S15 parameter

When access to VF-MB1/S15 parameter, set “1” to the PNU. The communication number of the drive parameter is set to the subindex IND.

Refer to the drive instruction manual about the communication number and unit.

*This procedure changes the value of VF-MB1/S15 EEPROM.

3.7.1.Examples of reading or changing VF-MB1/S15 parameter

3.7.1.1. Example 1. Reading the basic parameter (cmod (command mode selection))

AK = 6 (Request parameter value (array))

SPM = 0

PNU = 1

IND = 0x0003 (cmod communication number)

PKE

0

1

1

0

0

0

0

0

0

0

0

0

0

0

0

1

 

6

 

 

 

 

 

0

 

 

 

0

 

 

 

1

 

Requirement

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKW

 

 

 

 

 

 

 

 

 

 

 

PZD

 

 

 

 

PKE

 

 

IND

 

 

PWE

 

 

 

 

 

 

 

 

 

60

01

 

00

03

 

 

00

00

00

 

00

・・・

・・・

 

 

 

Response (Value: 0x0001 = Operation panel))

40

01

00

03

00

00

00

01

・・・ ・・・

3.7.1.2. Example 2. Reading the extended parameter (f219 (VIC input point 2 frequency))

AK = 6 (Request parameter value (array))

SPM = 0

PNU = 1

IND = 0x0219 (f219 communication number)

PKE

0

1

1

0

0

0

0

0

0

0

0

0

0

0

0

1

 

6

 

 

 

 

 

0

 

 

 

0

 

 

 

1

 

Requirement

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PKW

 

 

 

 

 

 

 

 

 

 

 

PZD

 

 

 

 

PKE

 

 

IND

 

 

PWE

 

 

 

 

 

 

 

 

 

60

01

 

02

19

 

 

00

00

00

 

00

・・・

・・・

 

 

 

Response (Value: 0x1770 (= 6000 -> 60.00Hz *))

40

01

02

19

00

00

17

70

・・・ ・・・

*“0x1770” as reading value of “VIC input point 2 frequency” is 0x1770 = 6000 (decimal number)

Since the unit of “VIC input point 2 frequency” is 0.01Hz, set the following value. 6000×0.01 = 60.00Hz

- 18 -

Page 20
Image 20
Toshiba instruction manual Access to VF-MB1/S15 parameter