4. Vendor Spec. Profile
Cyclic command transmission (the value of the parameter c001 - c006) and monitoring (the value of the parameter c021 - c026) are possible for PDP003Z by the original profile
Select the ”Telegram 100”, ”Telegram 101” or ”Telegram 102” as the profile on the configuration. Refer to the PLC configurator documents.
c001 - c006 setup value | c021 - c026 setup value |
0: No action | 0: No action |
1: fa06 (Communication command 1) | 1: fd01 (Status information 1) |
2: fa23 (Communication command 2) | 2: fd00 (Output frequency, 0.01Hz) |
3: fa07 (Fequency command, 0.01Hz) | 3: fd03 (Output current, 0.01%) |
5: fa50 (Terminal output data) | 4: fd05 (Output voltage, 0.01%) |
6: fa51 (FM analog output) | 5: fc91 (Alarm information) |
8: f601 (Stall prevention level, %) | 6: fd22 (PID feedback value, 0.01Hz) |
13: acc (Acceleration time 1, 0.1s)* | 7: fd06 (Input terminal board status) |
14: dec (Deceleration time 1, 0.1s) * | 8: fd07 (Output terminal status) |
15: ul (Upper limit,0.01Hz) | 9: fe36 (VIB input, 0.01%) |
16: vb (Torque boost value 1,0.1%) | 10: fe35 (VIA input, 0.01%) |
17: vlv (Base frequency voltage 1, 0.1V) | 11: fe37 (VIC input, 0.01%) |
| 12: fd04 (Input voltage (DC detection), 0.01%) |
| 13: fd16 (Estimated speed |
| 14: fd18 (Torque, 0.01%) |
| 19: f880 (Free notes) |
| 20: fd29 (Input power, 0.01kW) |
| 21: fd30 (Output power, 0.01kW) |
| 22: fe14 (Cumulative operation time, hour) |
| 23: fe40 (FM terminal output monitor, 0.01%) |
| 25: fd20 (Torque current, 0.01%) |
| 26: fd23 (Motor overload factor, 0.01%) |
| 27: fd24 (Drive overload factor, 0.01%) |
| 28: fd25 (PBR overload factor, %) |
| 29: fd26 (Motor load factor, %) |
| 30: fd27 (Drive load factor, %) |
| 31: fe56 (Pulse train input, pps) |
| 32: fe70 (Drive rated current, 0.1A) |
| 33: fe76 (Input |
| 34: fe77 (Output |
| 35: fd83 (IGBT temperature, degree C) |
*The unit of acc, dec is according to the parameter f519.
**The unit of fe76, fe77 is according to the parameter f749.