E6581738

- 20 -

4. Vendor Spec. Profile

Cyclic command transmission (the value of the parameter c001 - c006) and

monitoring (the value of the parameter c021 - c026) are possible for PDP003Z by

the original profile

Select the ”Telegram 100”, ”Telegram 101” or ”Telegram 102” as the profile on the

configuration. Refer to the PLC configurator documents.

c001 - c006 setup value c021 - c026 setup value
0: No action
1: fa06 (Communication command 1)
2: fa23 (Communication command 2)
3: fa07 (Fequency command, 0.01Hz)
5: fa50 (Terminal output data)
6: fa51 (FM analog output)
8: f601 (Stall prevention level, %)
13: acc (Acceleration time 1, 0.1s)*
14: dec (Deceleration time 1, 0.1s) *
15: ul (Upper limit,0.01Hz)
16: vb (Torque boost value 1,0.1%)
17: vlv (Base frequency voltage 1, 0.1V)
0: No action
1: fd01 (Status information 1)
2: fd00 (Output frequency, 0.01Hz)
3: fd03 (Output current, 0.01%)
4: fd05 (Output voltage, 0.01%)
5: fc91 (Alarm information)
6: fd22 (PID feedback value, 0.01Hz)
7: fd06 (Input terminal board status)
8: fd07 (Output terminal status)
9: fe36 (VIB input, 0.01%)
10: fe35 (VIA input, 0.01%)
11: fe37 (VIC input, 0.01%)
12: fd04 (Input voltage (DC detection), 0.01%)
13: fd16 (Estimated speed (real-time value), 0.01Hz)
14: fd18 (Torque, 0.01%)
19: f880 (Free notes)
20: fd29 (Input power, 0.01kW)
21: fd30 (Output power, 0.01kW)
22: fe14 (Cumulative operation time, hour)
23: fe40 (FM terminal output monitor, 0.01%)
25: fd20 (Torque current, 0.01%)
26: fd23 (Motor overload factor, 0.01%)
27: fd24 (Drive overload factor, 0.01%)
28: fd25 (PBR overload factor, %)
29: fd26 (Motor load factor, %)
30: fd27 (Drive load factor, %)
31: fe56 (Pulse train input, pps)
32: fe70 (Drive rated current, 0.1A)
33: fe76 (Input Watt-hour, 0.1kWh 10f749) **
34: fe77 (Output Watt-hour, 0.1kWh 10f749) **
35: fd83 (IGBT temperature, degree C)

* The unit of acc, dec is according to the parameter f519.

** The unit of fe76, fe77 is according to the parameter f749.