E6581738

4.1.How to use

The purposes are adjustment by real time command transmission, and the monitor of an operation state by using cyclic communication of PROFIBUS.

Example 1: Command transmitting

When you want to set "0xC400" to parameter fa06, set “1 (fa06)” to parameter c001.

And Since 0 and 1 byte of the PZD1 supports the parameter c001, if "0xC400" is set up here, "0xC400" will be set as fa06.

VF-MB1

PDP003Z

 

Parameter

Value

c001

1 (FA06)

c002

...

c003

...

...

...

"0xC400" is set as parameter fa06

PROFIBUS Master

PZD1

PZD2

PZD3

C4

00

...

...

...

...

 

Example 2: State monitoring

 

 

 

 

 

When you want to monitor the output current, set “3 (FD03)” to parameter c021.

 

 

The value of the parameter fd03 specified as 0 and1 byte of the PZD1 with the

 

 

parameter c021 is inputted.

 

 

 

 

VF-MB1

PDP003Z

 

 

PROFIBUS Master

 

 

 

 

 

Parameter

Value

 

 

 

 

c021

3 (FD03)

 

 

 

 

c022

...

 

 

 

 

c023

...

PZD1

PZD2

PZD3

...

...

xx

xx

 

 

The value of a parameter fd03 is outputted.

 

 

 

 

- 21 -

Page 23
Image 23
Toshiba VF-MB1/S15 instruction manual How to use, Profibus Master