When the communication loss occurs, PDP003Z returns the diagnosis telegram including the following information.

Byte

1: Station Status 1

Byte

2: Station Status 2

Byte

3: Station Status 3

Byte

4: Master station address

Byte

5: PDP003Z Ident Number high byte (0x0C)

Byte

6: PDP003Z Ident Number low byte (0x24)

Byte

7: Diagnostic data lengh

Byte

8: Status Type (Status message = 0x81)

Byte

9: Slot Number (Slot number = 0x00)

Byte 10: Specifier (0=No further diff, 1=Status comes, 2=Status goes)

Byte 11: External diagnostic data length

Byte 12: PDP003Z Station Address

Byte 13: PDP003Z Profile

Byte 14: Drive CPU1 Major version

Byte 15: Drive CPU1 Minor version

Byte 16: PDP003Z software version

Byte 17: PDP003Z communication network Fault

Byte 18: PDP003Z internal link Fault

*It is necessary to set the parameter c101 to "4".

*It is necessary to set it by the configuration to include Byte 7 or more in the response. (The figure below is a setting for SIMATEC Step7.)