Model

Number

Description

 

T

S

C

036

A

3

R

B

A ** C

0

0 0

A

1

0 0

0

1

A

1

 

1

2

3

4,5,6

7

8

9

10

11 12,13 14

15

16 17

18

19

20 21

22

23

24

25

DIGIT 1 - Unit Function

 

 

DIGIT 11 - Minor Design Sequence

 

DIGIT 20 - Convenience Outlet

 

 

 

T

= DX Cooling

 

 

A = First Sequence

 

 

 

0 = No Convenience Outlet

 

 

 

DIGIT 2 - Efficiency

 

 

 

 

 

 

 

 

 

A = Unpowered Convenience Outlet

 

 

 

DIGITS 12, 13 - Service Sequence

 

B = Powered Convenience Outlet

 

 

S

= Standard Efficiency

 

 

**=

Factory Assigned

 

 

 

(3 phase only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

= High Efficiency

 

 

 

 

 

 

 

 

 

DIGIT 21 - Communications Options

 

 

 

 

 

 

DIGIT 14 - Fresh Air Selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIGIT 3 - Airflow

C = Convertible

DIGITS 4,5,6 - Nominal Gross Cooling Capacity (MBh)

036

=

3Ton

048

=

4Ton

060

=

5Ton

072

=

6Ton

090

=

7½Ton, Single Compressor

092

=

7½Ton, Dual Compressor

102

=

8½Ton

120

=

10Ton

DIGIT 7 - Major Design Sequence

A = First

DIGIT 8 - UnitVoltage

1 = 208-230/60/1

3 = 208-230/60/3

4 = 460/60/3 W= 575/60/3 K = 380/60/3

DIGIT 9 - Unit Controls

E = Electromechanical

R = ReliaTel™Microprocessor

DIGIT 10 - Heating Capacity

0= No Electric Heat A = 5 kW (1 phase) B = 6 kW (3 phase) C = 9 kW (3 phase) D = 10 kW (1 phase) E = 12 kW (3 phase) F = 14 kW (1 phase)

G = 18 kW (1 and 3 phase) J = 23 kW (3 phase)

K = 27 kW (3 phase) N = 36 kW (3 phase) P = 54 kW (3 phase)

0 = No Fresh Air

A= Manual Outside Air Damper 0-50%

B= Motorized Outside Air Damper 0-50%

C= Economizer, Dry Bulb 0-100% without Barometric Relief

D= Economizer, Dry Bulb 0-100%

with Barometric Relief

E= Economizer, Reference Enthalpy 0-100% without Barometric Relief

F= Economizer, Reference Enthalpy 0-100% with Barometric Relief

G= Economizer, Comparative Enthalpy 0-100% without Barometric Relief

H= Economizer, Comparative Enthalpy 0-100% with Barometric Relief

DIGIT 15 - Supply Fan/DriveType/Motor

0= Standard Drive

1= Oversized Motor

2= Optional Belt Drive Motor

DIGIT 16 - Hinged Service Access/Filters

0 = Standard Panels/Standard Filters

A= Hinged Access Panels/Standard Filters

B= Standard Panels/2” Pleated Filters

C= Hinged Access Panels/2” Pleated Filters

DIGIT 17 - Condenser Coil Protection

0 = Standard Coil

1= Standard Coil with Hail Guard

2= Epoxy Coated Condenser Coil

3= Epoxy Coated Condenser Coil with Hail Guard

DIGIT 18 -Through the Base Provisions

0= NoThrough the Base Provisions A = Through the Base Electric

DIGIT 19 - Disconnect/Circuit Breaker (3 phase only)

0= No Disconnect or Circuit Breaker

1= Non-Fused Disconnect

2= Circuit Breaker

0= No Communications Interface

1= Trane Communications Interface

2= LonTalk® Communications Interface

3= Novar 2024 Controls

4= Novar 3051 Controls

DIGIT 22 - Refrigeration System Option

0= Standard Refrigeration System A = Thermal Expansion Valve (TXV)

B = Dehumidification (Hot Gas Reheat Coil)

DIGIT 23 - Refrigeration Controls

0 = No Refrigeration Control

1= High Pressure Control

2= Frostat

3= Crankcase Heater

4= High Pressure Control and Frostat

5= High Pressure Control and Crankcase Heater

6= Frostat and Crankcase Heater

7= High Pressure Control, Frostat and Crankcase Heater

DIGIT 24 - Smoke Detector

0 = No Smoke Detector

A= Return Air Smoke Detector

B= Supply Air Smoke Detector

C= Supply and Return Air Smoke Detectors

DIGIT 25 - Monitoring Controls

0= No Monitoring Control

1= Clogged Filter Switch

2= Fan Failure Switch

3= Discharge Air SensingTube

4= Clogged Filter Switch and Fan Fail Switch

5= Clogged Filter Switch and Discharge Air SensingTube

6= Fan Fail Switch and Discharge Air SensingTube

7= Clogged Filter and Fan Fail Switches and Discharge Air SensingTube

8= Novar Return Air Sensor

Example:

Model number TSC036A3RBA**C000A10001A1 describes a unit with the following characteristics: DX Cooling, 3 ton nominal cooling capacity, 208-230/60/3 power supply, ReliaTel™ controls, 6 kW electric heater model. 0-100% dry bulb economizer without barometric relief, standard direct drive motor, standard access panels/ filters, standard condenser coil with no coil protection, through the base electric, non-fused disconnect, no convenience outlet or communications interface, standard refrigeration coil, high pressure control, return air smoke detector, and clogged filter switch.

10

RT-PRC005-EN

Page 10
Image 10
Trane RT-PRC005 manual Model Number Description, 036 11 12,13