Table PD-29 — Continued

Performance

(6 Ton)

Data

Standard Efficiency

 

 

 

 

 

 

Table PD-29 — Belt Drive Evaporator Fan Performance — 6-Ton — TSC072,AK — Downflow Airflow

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

.10

 

.20

 

.30

 

.40

 

.50

 

.60

 

.70

 

.80

.90

 

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

2-HP Standard Motor & Field Supplied Low Static Drive (1)

 

 

 

 

 

 

2-HP Standard Motor & Drive

 

1920

-

-

-

-

573

0.34

630

0.41

680

0.48

726

0.55

769

0.62

811

0.70

851

0.78

889

0.87

2160

-

-

548

0.35

602

0.42

656

0.50

706

0.58

751

0.65

792

0.73

832

0.81

871

0.90

908

0.99

2400

-

-

584

0.45

635

0.52

682

0.60

732

0.69

777

0.77

818

0.86

856

0.95

893

1.04

930

1.13

2640

569

0.47

621

0.56

670

0.64

715

0.72

758

0.81

802

0.91

845

1.01

883

1.10

919

1.20

953

1.29

2880

612

0.60

660

0.69

706

0.78

749

0.86

789

0.96

830

1.06

870

1.16

909

1.27

945

1.37

979

1.48

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.

NOTES:

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000

Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table PD-29 — Continued

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

1.10

 

1.20

 

1.30

 

1.40

1.50

1.60

 

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

2- HP Standard Motor & Drive

 

 

 

 

 

2-HP Standard Motor & High Static Drive

 

 

 

 

1920

925

0.95

960

1.03

994

1.11

1026

1.19

1057

1.27

1087

1.36

1116

1.44

1144

1.52

1173

1.61

1200

1.70

2160

944

1.08

978

1.17

1010

1.26

1043

1.36

1073

1.44

1104

1.54

1133

1.63

1162

1.72

1189

1.81

1216

1.91

2400

964

1.22

998

1.32

1030

1.42

1063

1.53

1092

1.63

1123

1.73

1151

1.83

1179

1.93

1206

2.03

1233

2.13

2640

986

1.39

1019

1.49

1051

1.60

1082

1.71

1112

1.81

1141

1.92

1169

2.03

1198

2.15

1225

2.26

-

-

2880

1011

1.58

1043

1.69

1073

1.79

1103

1.90

1133

2.02

1161

2.13

1190

2.26

-

-

-

-

-

-

 

 

 

 

 

2- HP Standard Motor & High Static Drive

 

 

 

 

 

 

 

 

 

 

Table PD-30 — Belt Drive Evaporator Fan Performance — 6-Ton — TSC072,AK — Horizontal

Airflow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

.10

 

.20

 

.30

 

.40

 

.50

 

.60

 

.70

.80

 

.90

 

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

2-HP Standard Motor & Field Supplied Low Static Drive

(1)

 

 

 

 

 

2-HP Standard Motor & Drive

 

1920

-

-

565

0.31

627

0.39

679

0.45

726

0.52

771

0.60

814

0.69

857

0.77

899

0.85

939

0.93

2160

566

0.35

609

0.41

663

0.48

716

0.57

762

0.64

804

0.72

843

0.80

883

0.90

922

0.99

960

1.08

2400

619

0.47

660

0.54

701

0.60

751

0.69

798

0.78

839

0.87

877

0.95

914

1.04

950

1.14

984

1.24

2640

672

0.61

710

0.68

745

0.76

788

0.83

833

0.93

875

1.04

914

1.13

949

1.22

984

1.31

1016

1.42

2880

726

0.77

762

0.86

795

0.94

828

1.02

869

1.11

911

1.21

950

1.33

986

1.44

1019

1.53

1051

1.63

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.

NOTES:

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories 2-HP Fan Motor Heat (MBH) = 3.000 x Fan BHP+.5000

Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range

of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table PD-30 — Continued

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

 

1.10

 

1.20

 

1.30

 

1.40

1.50

1.60

 

1.70

1.80

1.90

2.00

CFM

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

2- HP Standard Motor

& Drive

 

 

 

 

2-HP Standard Motor & High Static Drive

 

 

 

 

 

 

1920

978

1.02

1015

1.11

1051

1.20

1086

1.30

1118

1.39

1150

1.49

1180

1.58

1209

1.68

1236

1.77

1263

1.86

2160

 

996

1.17

1034

1.27

1069

1.36

1103

1.46

1136

1.56

1169

1.67

1199

1.77

1229

1.88

1258

1.98

-

-

2400

1020

1.35

1055

1.45

1089

1.55

1122

1.66

1154

1.76

1186

1.86

1216

1.97

1246

2.08

1276

2.20

-

-

2640

1049

1.53

1081

1.65

1113

1.76

1144

1.87

1176

1.98

1207

2.10

1237

2.21

-

-

-

-

-

-

2880

1081

1.74

1112

1.86

1141

1.97

1170

2.10

1199

2.22

-

-

-

-

-

-

-

-

-

-

2- HP Standard Motor & High Static Drive

RT-PRC005-EN