Performance | (6 Ton) |
Data | High Efficiency |
|
|
|
|
Table
|
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
| ||||
| .10 |
|
| .20 |
| .30 | .40 | .50 |
| .60 |
| .70 |
| .80 |
| .90 |
| 1.00 | ||
CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP |
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
| Low Static Drive (1) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
1920 | — | — | — | — | 588 | 0.35 | 643 | 0.43 | 693 | 0.50 | 738 | 0.57 | 782 | 0.65 | 823 | 0.73 | 862 | 0.81 | 900 | 0.89 |
2160 | — | — | 564 | 0.37 | 618 | 0.44 | 672 | 0.52 | 721 | 0.60 | 765 | 0.68 | 806 | 0.76 | 847 | 0.85 | 885 | 0.93 | 922 | 1.02 |
2400 | — | — | 602 | 0.47 | 652 | 0.54 | 701 | 0.63 | 750 | 0.72 | 794 | 0.81 | 834 | 0.90 | 873 | 0.98 | 909 | 1.08 | 945 | 1.17 |
2640 | 589 | 0.50 | 642 | 0.59 | 690 | 0.67 | 734 | 0.76 | 779 | 0.85 | 822 | 0.95 | 864 | 1.05 | 901 | 1.15 | 936 | 1.24 | 971 | 1.34 |
2880 | 634 | 0.63 | 682 | 0.74 | 728 | 0.82 | 770 | 0.91 | 810 | 1.01 | 851 | 1.11 | 892 | 1.22 | 930 | 1.33 | 965 | 1.44 | 999 | 1.54 |
For Standard Evaporator Fan Speed (RPM), reference Table
NOTES:
Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data. Refer to Table
1. Field Supplied Fan Sheave AK84 and Belt AX34 required.
Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.
Table PD-46 — Continued
|
|
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
| |||||
|
|
| 1.10 |
|
| 1.20 |
| 1.30 |
| 1.40 | 1.50 | 1.60 |
| 1.70 | 1.80 | 1.90 | 2.00 | |||||
CFM | RPM | BHP |
| RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
| Motor & Drive |
| (or 2 HP Oversized Motor & Drive) |
|
|
|
|
|
|
|
|
|
|
| |||||||
1920 | 937 | 0.98 | 971 | 1.06 | 1004 | 1.14 | 1037 | 1.22 | 1068 | 1.30 | 1097 | 1.38 | 1127 | 1.47 | 1154 | 1.55 | 1182 | 1.64 | 1210 | 1.74 | ||
2160 | 957 | 1.12 | 991 | 1.21 | 1024 | 1.30 | 1057 | 1.40 | 1087 | 1.49 | 1117 | 1.58 | 1146 | 1.67 | 1174 | 1.76 | 1201 | 1.85 | 1227 | 1.95 | ||
2400 | 980 | 1.27 | 1013 | 1.37 | 1046 | 1.47 | 1076 | 1.57 | 1106 | 1.68 | 1137 | 1.78 | 1166 | 1.89 | 1194 | 1.99 | 1220 | 2.08 | 1248 | 2.19 | ||
2640 |
| 1004 | 1.44 |
| 1036 | 1.55 | 1067 | 1.65 | 1098 | 1.77 | 1129 | 1.88 | 1158 | 1.99 | 1185 | 2.10 | 1214 | 2.22 | — | — | — | — |
2880 | 1030 | 1.64 |
| 1061 | 1.75 | 1092 | 1.86 | 1123 | 1.98 | 1151 | 2.09 | 1181 | 2.22 | — | — | — | — | — | — | — | — |
2-HP Oversized Motor & Drive
Table
|
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
| ||||
| .10 |
|
| .20 |
| .30 | .40 | .50 |
| .60 |
| .70 |
| .80 |
| .90 |
| 1.00 | ||
CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP |
|
|
|
|
|
|
|
|
|
| |||||||||||
|
|
| Low Static Drive (1) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
1920 | — | — | 580 | 0.33 | 641 | 0.41 | 692 | 0.47 | 738 | 0.54 | 783 | 0.63 | 827 | 0.71 | 870 | 0.79 | 912 | 0.88 | 951 | 0.96 |
2160 | 578 | 0.37 | 623 | 0.43 | 679 | 0.51 | 731 | 0.59 | 775 | 0.67 | 817 | 0.74 | 857 | 0.83 | 896 | 0.93 | 935 | 1.02 | 974 | 1.12 |
2400 | 633 | 0.49 | 673 | 0.56 | 718 | 0.63 | 769 | 0.72 | 814 | 0.82 | 855 | 0.90 | 893 | 0.98 | 929 | 1.08 | 965 | 1.18 | 999 | 1.29 |
2640 | 688 | 0.64 | 725 | 0.71 | 762 | 0.79 | 808 | 0.87 | 853 | 0.98 | 894 | 1.09 | 931 | 1.17 | 966 | 1.26 | 1000 | 1.36 | 1032 | 1.47 |
2880 | 743 | 0.81 | 778 | 0.90 | 811 | 0.98 | 848 | 1.06 | 891 | 1.16 | 932 | 1.28 | 970 | 1.40 | 1004 | 1.49 | 1037 | 1.59 | 1068 | 1.69 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Motor & Drive |
|
For Standard Evaporator Fan Speed (RPM), reference Table | Trane’s factory supplied motors, in commercial equipment, are definite purpose |
NOTES: | motors, specifically designed and tested to operate reliably and continuously at |
Data includes pressure drop due to standard filters and wet coils. | all cataloged conditions. Using the full horsepower range of our fan motors as |
No accessories or options are included in pressure drop data. | shown in our tabular data will not result in nuisance tripping or premature motor |
Refer to Table | failure. Our product’s warranty will not be affected. |
due to other options/accessories |
|
| |
| |
1. Field Supplied Fan Sheave AK84 and Belt AX34 required. |
|
2. Field Supplied Fan Sheave AK54 and Belt AX30. |
|
Table PD-47 — Continued
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
| ||
| 1.10 | 1.20 | 1.30 | 1.40 | 1.50 | 1.60 | 1.70 | 1.80 | 1.90 | 2.00 |
CFM | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM | BHP RPM BHP | RPM BHP |
|
|
|
|
|
|
| |||||||||||
Motor & Drive |
| (or 2 HP Oversized Motor & Drive) |
|
|
|
|
|
|
|
| |||||||
1920 | 990 | 1.05 | 1026 | 1.14 | 1062 | 1.24 | 1096 | 1.33 | 1130 | 1.43 | 1160 | 1.52 | 1190 | 1.61 | 1218 | 1.71 | |
2160 |
| 1010 | 1.21 | 1047 | 1.31 | 1082 | 1.40 | 1116 | 1.50 | 1150 | 1.61 | 1182 | 1.71 | 1211 | 1.81 | 1242 | 1.92 |
2400 | 1035 | 1.39 | 1070 | 1.50 | 1104 | 1.60 | 1137 | 1.70 | 1168 | 1.81 | 1201 | 1.92 | 1232 | 2.03 | 1261 | 2.14 | |
2640 |
| 1065 | 1.59 | 1097 | 1.71 | 1129 | 1.82 | 1161 | 1.93 | 1192 | 2.05 | 1223 | 2.16 | 1252 | 2.27 | — | — |
2880 | 1099 | 1.80 | 1130 | 1.93 | 1159 | 2.05 | 1188 | 2.18 | 1217 | 2.30 | — | — | — | — | — | — |
2-HP Oversized Motor & Drive
1247 1.80 1273 1.90
1271 2.03 1298 2.14
1291 2.26 — —
2-HP Oversized Motor & Field Supplied Drive (2)
40 |