General

(6 - 10Ton)

Data

Standard Efficiency

 

 

 

 

 

 

 

 

Table GD - 2— General Data

 

6Ton

7½Ton

8½Ton

10Ton

 

Convertible Units

Convertible Units

Convertible Units

Convertible Units

 

 

TSC072A3, A4, AW, AK

TSC090A3,A4,AW, AK

TSC092A3, A4, AW

TSC102A3, A4, AW, AK

TSC120A3, A4, AW, AK

Cooling Performance1

 

 

 

 

 

 

Gross Cooling Capacity

72,000

95,000

92,000

105,000

118,000

 

EER2

10.3

10.3

10.3

10.3

10.46

 

Nominal CFM / ARI Rated CFM

2,400/2,100

3,000/2,625

3,000/2,625

3,400/3,000

4,000/3,200

 

ARI Net Cooling Capacity

69,000

90,000

87,000

100,0007

112,0007

 

Integrated Part LoadValue (IPLV)3

11.18

11.98

11.58

 

System Power (kW)

6.7

8.74

8.45

9.719

10.779

 

Compressor

 

 

 

 

 

 

No./Type

1/Scroll

1/Scroll

2/Scrolls

2/Scrolls

2/Scrolls

Outdoor Sound Rating (dB)4

88

90

87

86

86

 

Outdoor Coil —Type

Lanced

Lanced

Lanced

Lanced

Lanced

 

Tube Size (in.) O.D.

0.3125

0.3125

0.3125

0.3125

0.3125

 

Face Area (sq ft)

13.88

17.00

17.00

19.83

25.92

 

Rows/FPI

2/17

3/17

2/17

2/17

2/17

 

Indoor Coil —Type

Lanced

Lanced

Lanced

Lanced

Lanced

 

Tube Size (in.)

0.3125

0.3125

0.3125

0.3125

0.3125

 

Face Area (sq ft)

9.89

9.89

9.89

12.36

12.36

 

Rows/FPI

2/16

3/16

3/16

3/16

4/16

 

Refrigerant Control

Short Orifice

Short Orifice

Short Orifice

Short Orifice

Short Orifice

Drain Connection No./Size (in.)

1/¾ NPT

1/¾ NPT

1/¾ NPT

1/¾ NPT

1/¾ NPT

Outdoor Fan —Type

Propeller

Propeller

Propeller

Propeller

Propeller

 

No. Used/Diameter (in.)

1/26

1/26

1/26

1/26

1/26

 

DriveType/No. Speeds

Direct/1

Direct/1

Direct/1

Direct/1

Direct/1

CFM

6100

6200

6500

7100

7000

 

No. Motors/HP

1/0.7011

1/0.7011

1/0.70

1/0.75

1/0.75

 

Motor RPM

1115

1115

1115

1115

1115

 

Belt Drive Indoor Fan —Type

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

 

No. Used

1

1

1

1

1

 

Diameter xWidth (in.)

12 x 12

12 x 12

12 x 12

15 x 15

15 x 15

DriveType/No. Speeds

Belt/Variable Speed

Belt/Variable Speed

Belt/Variable Speed

Belt/Variable Speed

Belt/Variable Speed

No. Motors

1

1

1

1

1

 

Motor HP (Standard/Oversized)

1.00/2.0012

2.00/3.00

2.00/3.00

2.00/3.00

3.00/5.00

 

Motor RPM (Standard/Oversized)

1750

1750

1750

1750

1750/3450

 

Motor Frame Size

56

56

56

56

56

 

Filters —Type Furnished 10

Throwaway

Throwaway

Throwaway

Throwaway

Throwaway

 

(No.) Size Recommended (in.)

(4) 16 x 25 x 2

(4) 16 x 25 x 2

(4) 16 x 25 x 2

(4) 20 x 25 x 2

(4) 20 x 25 x 2

Refrigerant Charge (Lbs of R-22)5

7.1

11.9

6.2 Circuit 1

7.9 Circuit 1

8.4Circuit 1

 

 

 

 

3.4 Circuit 2

4.0 Circuit 2

6.6 Circuit 2

 

NOTES:

1.Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240 except AK (380V/60 Hz).

2.SEER is rated at ARI conditions and in accordance with DOE test procedures.

3.Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb ar ARI rated cfm.

4.Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-51.

5.Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

6.EER shown is for downflow airflow. EER for horizontal airflow is 10.3.

7.ARI Net Cooling Capacity shown is for downflow airflow. Cooling Capacity for Horizontal airflow TSC102A is 99,000; TSC120A is 111,000.

8.Integrated Part Load Value (IPLV) shown is for downflow airflow. IPLV for Horizontal airflow TSC092A is 10.8, TSC102A is 11.5; TSC120A is 11.0.

9.System Power (kW) shown is for downflow airflow. System Power (kW) forHorizontal airflow TSC102A is 9.61; for TSC120A is 10.78.

10.Optional 2” Pleated Filters also available.

11.Outdoor motor is 0.75 hp for AK (380V/60 Hz units).

12.Standard indoor motor is 2.00 hp for AK (380V/60 Hz) units.

12

RT-PRC005-EN

Page 12
Image 12
Trane RT-PRC005 manual 10Ton, Table GD 2- General Data, EER2, Outdoor Sound Rating dB4 Outdoor Coil -Type