General | (6 - 10Ton) | ||
Data | Standard Efficiency | ||
|
|
|
|
|
|
|
|
Table GD - 2— General Data
| 6Ton | 7½Ton | 8½Ton | 10Ton | ||
| Convertible Units | Convertible Units | Convertible Units | Convertible Units |
| |
| TSC072A3, A4, AW, AK | TSC090A3,A4,AW, AK | TSC092A3, A4, AW | TSC102A3, A4, AW, AK | TSC120A3, A4, AW, AK | |
Cooling Performance1 |
|
|
|
|
|
|
Gross Cooling Capacity | 72,000 | 95,000 | 92,000 | 105,000 | 118,000 |
|
EER2 | 10.3 | 10.3 | 10.3 | 10.3 | 10.46 |
|
Nominal CFM / ARI Rated CFM | 2,400/2,100 | 3,000/2,625 | 3,000/2,625 | 3,400/3,000 | 4,000/3,200 |
|
ARI Net Cooling Capacity | 69,000 | 90,000 | 87,000 | 100,0007 | 112,0007 |
|
Integrated Part LoadValue (IPLV)3 | — | — | 11.18 | 11.98 | 11.58 |
|
System Power (kW) | 6.7 | 8.74 | 8.45 | 9.719 | 10.779 |
|
Compressor |
|
|
|
|
|
|
No./Type | 1/Scroll | 1/Scroll | 2/Scrolls | 2/Scrolls | 2/Scrolls | |
Outdoor Sound Rating (dB)4 | 88 | 90 | 87 | 86 | 86 |
|
Outdoor Coil | Lanced | Lanced | Lanced | Lanced | Lanced |
|
Tube Size (in.) O.D. | 0.3125 | 0.3125 | 0.3125 | 0.3125 | 0.3125 |
|
Face Area (sq ft) | 13.88 | 17.00 | 17.00 | 19.83 | 25.92 |
|
Rows/FPI | 2/17 | 3/17 | 2/17 | 2/17 | 2/17 |
|
Indoor Coil | Lanced | Lanced | Lanced | Lanced | Lanced |
|
Tube Size (in.) | 0.3125 | 0.3125 | 0.3125 | 0.3125 | 0.3125 |
|
Face Area (sq ft) | 9.89 | 9.89 | 9.89 | 12.36 | 12.36 |
|
Rows/FPI | 2/16 | 3/16 | 3/16 | 3/16 | 4/16 |
|
Refrigerant Control | Short Orifice | Short Orifice | Short Orifice | Short Orifice | Short Orifice | |
Drain Connection No./Size (in.) | 1/¾ NPT | 1/¾ NPT | 1/¾ NPT | 1/¾ NPT | 1/¾ NPT | |
Outdoor Fan | Propeller | Propeller | Propeller | Propeller | Propeller |
|
No. Used/Diameter (in.) | 1/26 | 1/26 | 1/26 | 1/26 | 1/26 |
|
DriveType/No. Speeds | Direct/1 | Direct/1 | Direct/1 | Direct/1 | Direct/1 | |
CFM | 6100 | 6200 | 6500 | 7100 | 7000 |
|
No. Motors/HP | 1/0.7011 | 1/0.7011 | 1/0.70 | 1/0.75 | 1/0.75 |
|
Motor RPM | 1115 | 1115 | 1115 | 1115 | 1115 |
|
Belt Drive Indoor Fan | FC Centrifugal | FC Centrifugal | FC Centrifugal | FC Centrifugal | FC Centrifugal |
|
No. Used | 1 | 1 | 1 | 1 | 1 |
|
Diameter xWidth (in.) | 12 x 12 | 12 x 12 | 12 x 12 | 15 x 15 | 15 x 15 | |
DriveType/No. Speeds | Belt/Variable Speed | Belt/Variable Speed | Belt/Variable Speed | Belt/Variable Speed | Belt/Variable Speed | |
No. Motors | 1 | 1 | 1 | 1 | 1 |
|
Motor HP (Standard/Oversized) | 1.00/2.0012 | 2.00/3.00 | 2.00/3.00 | 2.00/3.00 | 3.00/5.00 |
|
Motor RPM (Standard/Oversized) | 1750 | 1750 | 1750 | 1750 | 1750/3450 |
|
Motor Frame Size | 56 | 56 | 56 | 56 | 56 |
|
Filters | Throwaway | Throwaway | Throwaway | Throwaway | Throwaway |
|
(No.) Size Recommended (in.) | (4) 16 x 25 x 2 | (4) 16 x 25 x 2 | (4) 16 x 25 x 2 | (4) 20 x 25 x 2 | (4) 20 x 25 x 2 | |
Refrigerant Charge (Lbs of | 7.1 | 11.9 | 6.2 Circuit 1 | 7.9 Circuit 1 | 8.4Circuit 1 |
|
|
|
| 3.4 Circuit 2 | 4.0 Circuit 2 | 6.6 Circuit 2 |
|
NOTES:
1.Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary
2.SEER is rated at ARI conditions and in accordance with DOE test procedures.
3.Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb ar ARI rated cfm.
4.Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table
5.Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6.EER shown is for downflow airflow. EER for horizontal airflow is 10.3.
7.ARI Net Cooling Capacity shown is for downflow airflow. Cooling Capacity for Horizontal airflow TSC102A is 99,000; TSC120A is 111,000.
8.Integrated Part Load Value (IPLV) shown is for downflow airflow. IPLV for Horizontal airflow TSC092A is 10.8, TSC102A is 11.5; TSC120A is 11.0.
9.System Power (kW) shown is for downflow airflow. System Power (kW) forHorizontal airflow TSC102A is 9.61; for TSC120A is 10.78.
10.Optional 2” Pleated Filters also available.
11.Outdoor motor is 0.75 hp for AK (380V/60 Hz units).
12.Standard indoor motor is 2.00 hp for AK (380V/60 Hz) units.
12 |