Table GD - 4— General Data

General

(6 - 10Ton)

Data

High Efficiency

 

 

 

 

Table GD - 4— General Data

 

6Ton

7½Ton

8½Ton

10Ton

 

Convertible Units

Convertible Units

Convertible Units

Convertible Units

 

THC072A3, A4, AW

THC092A3, A4, AW

THC102A3, A4. AW

THC120A3, A4, AW

Cooling Performance1

 

 

 

 

Gross Cooling Capacity

73,000

94,000

103,000

117,000

EER2

11.56

11.56

11.56

11.26

Nominal CFM / ARI Rated CFM

2,400/2,100

3,000/2,625

3,400/3,000

4,000/3,200

ARI Net Cooling Capacity

70,000

90,00010

98,00010

109,00010

Integrated Part LoadValue (IPLV)3

11.98

12.18

12.08

System Power (kW)

6.097

7.837

8.527

9.737

Compressor

 

 

 

 

No./Type

1/Climatuff Scroll

2/Climatuff Scrolls

2/Climatuff Scrolls

2/Climatuff Scrolls

Outdoor Sound Rating (dB)4

89

91

89

88

Outdoor Coil —Type

Lanced

Lanced

Lanced

Lanced

Tube Size (in.) O.D.

0.3125

0.3125

0.3125

0.3125

Face Area (sq ft)

17.00

17.50

19.83

27.21

Rows/FPI

3/17

3/17

3/17

3/17

Indoor Coil —Type

Lanced

Lanced

Lanced

Lanced

Tube Size (in.)

0.3125

0.3125

0.3125

0.3125

Face Area (sq ft)

9.89

12.36

12.36

12.36

Rows/FPI

3/16

3/16

4/16

5/16

Refrigerant Control

Short Orifice

Short Orifice

Short Orifice

Short Orifice

Drain Connection No./Size (in.)

1/¾ NPT

1/¾ NPT

1/¾ NPT

1/¾ NPT

Outdoor Fan —Type

Propeller

Propeller

Propeller

Propeller

No. Used/Diameter (in.)

1/26

1/26

1/26

1/26

DriveType/No. Speeds

Direct/1

Direct/1

Direct/1

Direct/1

CFM

6100

6200

6600

7000

No. Motors/HP

1/0.70

1/0.70

1/0.75

1/0.75

Motor RPM

1075

1075

1075

1075

Belt Drive Indoor Fan —Type

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

No. Used

1

1

1

1

Diameter xWidth (in.)

12 x 12

15 x 15

15 x 15

15 x 15

DriveType/No. Speeds

Belt/Variable Speed

Belt/Variable Speed

Belt/Variable Speed

Belt/Variable Speed

No. Motors

1

1

1

1

Motor HP (Standard/Oversized)

1.00/2.00

2.00/3.00

2.00/3.00

3.00/5.00

Motor RPM (Standard/Oversized)

1750

1750

1750

1750/3450

Motor Frame Size

56

56

56

56

Filters —Type Furnished 9

Throwaway

Throwaway

Throwaway

Throwaway

(No.) Size Recommended (in.)

(4) 16 x 25 x 2

(4) 20 x 25 x 2

(4) 20 x 25 x 2

(4) 20 x 25 x 2

Optional Hot Gas Reheat Coil —Type

Lanced

Tube Size (in.) OD

0.375

Face Area (sq. ft.)

5.19

Rows/FPI

2/16

Refrigerant Charge (Lbs of R-22)5

10.7

6.4 Circuit 1

7.4 Circuit 1

11.0 Circuit 1

 

 

6.2 Circuit 2

7.1Circuit 2

7.3Circuit 2

NOTES:

1.Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240.

2.SEER is rated at ARI conditions and in accordance with DOE test procedures.

3.Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 80°F ambient, 80°F entering dry bulb, and 67°F entering wet bulb ar ARI rated cfm.

4.Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-51.

5.Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

6.EER shown is for downflow airflow. EER for horizontal airflow: THC072A - 11.3, THC092A and THC102A - 11.3, THC120A - 10.7.

7.System Power (kW) shown is for downflow airflow. System Power (kW) for horizontal airflow: THC072A - 6.2, THC092A - 7.88, THC102A - 8.58, THC120A - 10.09.

8.Integrated Part Load Value (IPLV) shown is for downflow airflow. IPLV for horizontal airflow: THC092A - 11.5, THC102A - 11.6, THC120A - 11.5.

9.Optional 2” Pleated Filters also available.

10.Net Cooling Capacity shown is for downflow airflow. Net Cooling for horizontal airflow: THC092A - 89,000, THC102A - 97,000, THC120A - 108,000.

14