Trane RT-PRC005 manual 3 - 5Ton, Standard Efficiency, Table GD - 1 - General Data

Models: RT-PRC005

1 76
Download 76 pages 18.07 Kb
Page 11
Image 11
General

General

(3 - 5Ton)

Data

Standard Efficiency

 

 

 

 

Table GD - 1 — General Data

 

3Ton Convertible Units

4Ton Convertible Units

5Ton Convertible Units

 

TSC036A1, A3, A4, AW

TSC048A1

TSC048A3, A4, AW

TSC060A1

TSC060A3, A4, AW

 

TSC060AK

Cooling Performance1

 

 

 

 

 

 

 

Gross Cooling Capacity

37,400

50,300

49,200

63,100

63,100

 

63,100

SEER2

10.75

10.1

10.0

9.9

10.2

 

10.2

Nominal CFM / ARI Rated CFM

1,200/1,200

1,600/1,600

1,600/1,600

2,000/2,000

2,000/2,000

 

2,000/2,000

ARI Net Cooling Capacity

36,000

48,000

47,000

60,000

60,000

 

60,000

System Power (kW)

3.918

5.28

5.40

6.86

6.78

 

6.78

Compressor

 

 

 

 

 

 

 

No./Type

1/Recip.

1/Scroll

1/Scroll

1/Scroll

1/Scroll

 

1/Scroll

Outdoor Sound Rating (dB)3

83

86

82

84

84

 

84

Outdoor Coil —Type

Lanced

Lanced

Lanced

Lanced

Lanced

 

Lanced

Tube Size (in.) O.D.

0.3125

0.3125

0.3125

0.3125

0.3125

 

0.3125

Face Area (sq ft)

7.19

6.17

9.59

8.81

8.81

 

8.81

Rows/FPI

2/17

2/17

1/17

2/17

2/17

 

2/17

Indoor Coil —Type

Lanced

Lanced

Lanced

Lanced

Lanced

 

Lanced

Tube Size (in.)

0.3125

0.3125

0.3125

0.3125

0.3125

 

0.3125

Face Area (sq ft)

5.67

6.68

6.17

5.00

5.00

 

5.00

Rows/FPI

2/16

3/16

3/16

3/16

3/16

 

3/16

Refrigerant Control

Short Orifice

Short Orifice

Short Orifice

Short Orifice

Short Orifice

 

Short Orifice

Drain Connection No./Size (in.)

1/¾ NPT

1/¾ NPT

1/¾ NPT

1/¾ NPT

1/¾ NPT

 

1/¾ NPT

Outdoor Fan —Type

Propeller

Propeller

Propeller

Propeller

Propeller

 

Propeller

No. Used/Diameter (in.)

1/22

1/22

1/22

1/22

1/22

 

1/22

DriveType/No. Speeds

Direct/1

Direct/1

Direct/1

Direct/1

Direct/1

 

Direct/1

CFM

2550

2850

3610

3470

3470

 

3470

No. Motors/HP

1/.20

1/.33

1/.33

1/.33

1/.33

 

1/.40

Motor RPM

1115

1115

1115

1115

1115

 

1115

Direct Drive Indoor Fan —Type

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

No. Used

1

1

1

1

1

 

1

Diameter xWidth (in.)

10 x 10

11 x 11

11 x 11

11 x 11

11 x 11

 

12x11/–

DriveType/No. Speeds

Direct/2

Direct/2

Direct/2

Direct/2

Direct/2

 

Direct/2

No. Motors

1

1

1

1

1

 

1

Motor HP (Standard/Oversized)

.33/.50

.60/.80

.60/.80

.90/1.00

.90/1.00

 

1.0/–

Motor RPM (Low/High Speed)

950/1060

930/1000

930/1000

985/1100

985/1100

 

935/1100

Oversized Motor RPM

 

 

 

 

 

 

 

(Low/High Speed)

1100/1145

1000/1100

1000/1100

1080/1135

1080/1135

 

Motor Frame Size

 

 

 

 

 

 

 

(Standard/Oversized)

48/48

48/48

48/48

48/48

48/48

 

48/—

Belt Drive Indoor Fan —Type

FC Centrifugal

FC Centrifugal

FC Centrifugal

 

No. Used

1

1

1

 

Diameter xWidth (in.)

11 x 11

11 x 11

11 x 11

 

DriveType/No. Speeds

Belt/Variable Speed6

Belt/Variable Speed

Belt/Variable Speed

No. Motors

1

1

1

 

Motor HP

1.00

1.00

1.00

 

Motor RPM

1750

1750

1750

 

Motor Frame Size

56

56

56

 

Filters —Type Furnished 7

Throwaway

Throwaway

Throwaway

Throwaway

Throwaway

 

Throwaway

(No.) Size Recommended (in.)

(2) 20 x 25 x 1

(2) 20 x 25 x 1

(2) 20 x 25 x 1

(2) 20 x 25 x 1

(2) 20 x 25 x 1

(2) 20 x 25 x 1

Refrigerant Charge (Lbs of R-22)4

3.8

4.4

3.8

4.7

4.9

 

4.9

NOTES:

1.Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240 except AK (380V/60 Hz).

2.SEER is rated at ARI conditions and in accordance with DOE test procedures.

3.Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-51

4.Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

5.TSC036A1 SEER is 10.5.

6.Belt Drive Motor is not available for TSC036A1.

7.Optional 2” Pleated Filters also available.

8.TSC036A1 System Power (kW) is 3.79.

RT-PRC005-EN

11

Page 11
Image 11
Trane RT-PRC005 manual 3 - 5Ton, Standard Efficiency, Table GD - 1 - General Data