Trane RT-PRC005 manual 3, 4, 5Ton, Performance, Data, Standard Efficiency

Models: RT-PRC005

1 76
Download 76 pages 18.07 Kb
Page 26
Image 26
(3, 4, 5Ton)

Performance

(3, 4, 5Ton)

Data

Standard Efficiency

 

 

 

 

Table PD-20— Direct Drive Evaporator Fan Performance

3, 4 and 5 Ton TSC036A, TSC048A, TSC060A

 

 

 

 

External Static Pressure (Inches ofWater) & Motor Power (Bhp)1

 

 

 

 

 

Standard Motor

 

 

 

Oversized Motor

 

 

Unit

 

High Speed

 

Low Speed

 

High Speed

 

Low Speed

Tons

Model No. CFM

ESP

BHP

 

ESP

BHP

 

ESP

BHP

 

ESP

BHP

 

 

960

0.81

0.36

0.61

0.28

0.96

0.39

0.89

0.35

 

 

1020

0.77

0.37

0.57

0.28

0.94

0.41

0.86

0.47

 

 

1080

0.73

0.38

0.50

0.29

0.91

0.43

0.82

0.39

 

 

1140

0.69

0.39

0.42

0.29

0.88

0.44

0.77

0.40

3

TSC036A

1200

0.66

0.40

0.34

0.30

0.84

0.45

0.74

0.41

 

Horizontal

1260

0.60

0.41

0.26

0.30

0.80

0.46

0.70

0.42

 

 

1320

0.55

0.42

0.14

0.31

0.75

0.48

0.65

0.44

 

 

1380

0.49

0.42

0.05

0.31

0.70

0.49

0.59

0.45

 

 

1440

0.44

0.43

 

0.64

0.52

0.54

0.48

 

 

1280

0.93

0.53

0.81

0.47

1.20

0.67

0.99

0.56

 

 

1360

0.87

0.54

0.75

0.47

1.15

0.68

0.94

0.58

 

 

1440

0.80

0.54

0.68

0.48

1.10

0.70

0.88

0.60

 

 

1520

0.73

0.55

0.60

0.48

1.05

0.73

0.81

0.63

4

TSC048A

1600

0.66

0.55

0.51

0.49

1.00

0.75

0.74

0.64

 

Horizontal

1680

0.57

0.56

0.38

0.49

0.95

0.78

0.65

0.66

 

 

1760

0.47

0.56

0.23

0.50

0.90

0.82

0.50

0.68

 

 

1840

0.37

0.57

0.13

0.50

0.83

0.83

0.35

0.70

 

 

1920

0.27

0.57

 

0.75

0.85

0.25

0.73

 

 

1600

0.90

0.78

0.82

0.64

1.20

0.90

1.05

0.85

 

 

1700

0.85

0.82

0.68

0.65

1.15

0.94

0.95

0.89

 

 

1800

0.80

0.85

0.56

0.65

1.05

0.98

0.85

0.91

 

 

1900

0.70

0.88

0.46

0.65

0.98

1.02

0.75

0.94

5

TSC060A3

2000

0.60

0.90

0.30

0.66

0.90

1.05

0.65

0.95

 

Horizontal

2100

0.50

0.93

0.14

0.66

0.80

1.10

0.50

0.96

 

 

2200

0.40

0.95

0.05

0.67

0.70

1.12

0.35

0.96

 

 

2300

0.30

0.97

 

0.60

1.17

0.15

0.97

 

 

2400

0.20

1.00

 

0.48

1.20

 

 

960

0.86

0.36

0.61

0.28

1.01

0.39

0.89

0.35

 

 

1020

0.82

0.37

0.62

0.28

0.99

0.41

0.91

0.47

 

 

1080

0.78

0.38

0.55

0.29

0.96

0.43

0.87

0.39

 

 

1140

0.74

0.39

0.47

0.29

0.93

0.44

0.82

0.40

3

TSC036A

1200

0.71

0.40

0.39

0.30

0.89

0.45

0.79

0.41

 

Downflow

1260

0.65

0.41

0.31

0.30

0.85

0.46

0.75

0.42

 

 

1320

0.60

0.42

0.19

0.31

0.80

0.48

0.70

0.44

 

 

1380

0.54

0.42

0.10

0.31

0.75

0.49

0.64

0.45

 

 

1440

0.49

0.43

 

0.69

0.52

0.59

0.48

 

 

1280

0.98

0.53

0.86

0.47

1.25

0.67

1.04

0.56

 

 

1360

0.92

0.54

0.80

0.47

1.20

0.68

0.99

0.58

 

 

1440

0.85

0.54

0.73

0.48

1.15

0.70

0.93

0.60

 

 

1520

0.78

0.55

0.65

0.48

1.10

0.73

0.86

0.63

4

TSC048A

1600

0.71

0.55

0.56

0.49

1.05

0.75

0.79

0.64

 

Downflow

1680

0.62

0.56

0.43

0.49

1.00

0.78

0.70

0.66

 

 

1760

0.52

0.56

0.28

0.50

0.95

0.82

0.55

0.68

 

 

1840

0.42

0.57

0.18

0.50

0.88

0.83

0.40

0.70

 

 

1920

0.32

0.57

 

0.80

0.85

 

 

1600

0.95

0.78

0.87

0.64

1.25

0.90

1.10

0.85

 

 

1700

0.90

0.82

0.73

0.65

1.20

0.94

1.00

0.89

 

 

1800

0.85

0.85

0.61

0.65

1.10

0.98

0.90

0.91

 

 

1900

0.75

0.88

0.51

0.65

1.03

1.02

0.80

0.94

5

TSC060A3

2000

0.65

0.90

0.35

0.66

0.95

1.05

0.70

0.95

 

Downflow

2100

0.55

0.93

0.19

0.66

0.85

1.10

0.55

0.96

 

 

2200

0.45

0.95

0.10

0.67

0.75

1.12

0.40

0.96

 

 

2300

0.35

0.97

 

0.65

1.17

0.20

0.97

 

 

2400

0.25

1.00

 

0.53

1.20

Fan motor heat (MBH) = 3.72 x Fan Bhp + .24.

Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

NOTES:

1.Data includes pressure drop due to wet coil and filters.

2.5 ton oversized motor performance is with 12 x 11 FC blower wheel.

3.YSC060AK uses a 1.0 hp direct drive motor and 12x11 FC centrifugal blower wheel. Refer to oversized motor column for the standard motor performance data.

26

RT-PRC005-EN

Page 26
Image 26
Trane RT-PRC005 manual 3, 4, 5Ton, Performance, Data, Standard Efficiency, 3, 4 and 5 Ton TSC036A, TSC048A, TSC060A