Trane RT-PRC005 manual 4Ton, Performance, Data, Standard Efficiency, Table PD-23- Continued

Models: RT-PRC005

1 76
Download 76 pages 18.07 Kb
Page 28
Image 28
(4Ton)

Performance

(4Ton)

Data

Standard Efficiency

 

 

 

 

 

 

Table PD-23 — Belt Drive Evaporator Fan Performance — 4 Ton — TSC048A3,A4,AW — Downflow Airflow

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

.10

 

 

.20

 

.30

.40

.50

 

.60

 

.70

 

.80

 

.90

 

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

1-HP Standard Motor & Field Supplied

 

 

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

 

Low Static Drive (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1280

616

0.22

677

0.26

734

0.31

787

0.37

834

0.42

878

0.48

919

0.53

959

0.59

997

0.64

1440

596

0.23

663

0.29

719

0.33

772

0.38

823

0.44

871

0.51

914

0.57

954

0.63

993

0.69

1029

0.75

1600

647

0.31

711

0.37

764

0.42

813

0.47

860

0.53

906

0.59

951

0.66

992

0.74

1029

0.80

1065

0.87

1760

701

0.41

758

0.46

811

0.52

856

0.58

901

0.64

944

0.70

986

0.77

1027

0.85

1066

0.93

1102

1.00

1920

755

0.52

807

0.57

859

0.64

903

0.71

945

0.77

985

0.83

1024

0.89

1063

0.97

1101

1.05

1137

1.14

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.

NOTES:

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.

1. Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.

Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table PD-23 — Continued

 

 

 

External Static Pressure (Inches of Water)

 

 

 

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

1280

1033

0.70

1069

0.77

1103

0.83

1136

0.89

1170

0.96

1440

1066

0.81

1099

0.87

1133

0.94

1165

1.01

1196

1.08

1600

1099

0.93

1132

1.00

1166

1.07

1196

1.14

1228

1.21

1760

1136

1.08

1168

1.15

1200

1.22

1229

1.29

1920

1172

1.23

1205

1.31

1236

1.39

Table PD-24 — Belt Drive Evaporator Fan Performance — 4 Ton — TSC048A3,A4,AW — Horizontal Airflow

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

.10

 

 

 

.20

 

 

.30

.40

.50

 

.60

 

.70

 

.80

 

.90

 

1.00

CFM

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

1-HP Standard Motor & Field Supplied

 

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

 

 

 

 

Low Static Drive (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1280

604

0.20

683

0.26

 

756

0.32

816

0.39

869

0.45

920

0.51

967

0.57

1011

0.64

1052

0.71

1090

0.79

1440

660

0.28

731

0.34

 

800

0.41

862

0.48

914

0.54

963

0.61

1009

0.68

1053

0.76

1094

0.83

1133

0.91

1600

717

0.36

783

0.43

 

846

0.51

907

0.58

961

0.66

1008

0.73

1053

0.81

1095

0.89

1135

0.97

1174

1.05

1760

774

0.47

 

837

0.54

 

894

0.62

952

0.70

1006

0.79

1054

0.87

1098

0.95

1139

1.04

1178

1.12

1216

1.21

1920

833

0.59

 

892

0.67

 

946

0.76

998

0.85

1050

0.94

1100

1.03

1144

1.12

1185

1.21

1224

1.30

1259

1.39

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data includes pressure drop due to standard filters and wet coils

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No accessories or options are included in pressure drop data.

 

 

 

 

 

 

 

 

 

1-HP Standard Motor &

 

 

Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories.

 

 

 

 

 

 

Field Supplied High Static Drive

Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Field Supplied Fan Sheave AK61 required. Field Supplied Belt may be necessary.

2.Field Supplied Fan Sheave AK41 required. Field Supplied Belt may be necessary.

Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged

conditions. Using the full horsepower range of our fan motors as shown in our tabular Table PD-24 — Continued data will not result in nuisance tripping or premature motor failure. Our product’s

warranty will not be affected.

 

 

External Static Pressure (Inches ofWater)

 

 

 

 

1.10

1.20

1.30

 

1.40

 

1.50

 

 

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

1280

1125

0.86

1160

0.94

1192

1.01

1223

1.08

1254

1.15

1440

1169

0.98

1204

1.07

1237

1.15

1269

1.23

1300

1.32

1600

1211

1.13

1247

1.21

1280

1.30

1312

1.39

1343

1.48

1760

1253

1.30

1289

1.39

1322

1.47

1920

1295

1.48

 

 

 

 

1-HP Standard Motor &

 

 

 

 

 

 

 

 

Field Supplied High Static Drive

 

 

 

28

 

 

 

 

 

 

 

 

 

RT-PRC005-EN

Page 28
Image 28
Trane RT-PRC005 manual 4Ton, Performance, Data, Standard Efficiency, Table PD-23- Continued