Trane RT-PRC005 manual Performance Data, Table PD-62-Auxiliary Electric Heat Capacity

Models: RT-PRC005

1 76
Download 76 pages 18.07 Kb
Page 47
Image 47
Table PD-62— Auxiliary Electric Heat Capacity

Performance

Data

Table PD-62— Auxiliary Electric Heat Capacity

 

 

 

 

Total2

 

 

Stage1

 

 

 

Stage 2

 

 

Unit

kW

MBH

No. of

 

kW

MBH

kW

MBH

Tons

 

Model No.

Input1

Output1

Stages

Input1

Output1

Input1

Output1

 

 

 

5.00

17.07

1

5.00

17.07

 

 

 

T#C036A1

10.00

34.14

2

5.00

17.07

 

5.00

17.07

 

 

 

13.80

47.11

2

8.80

30.04

 

5.00

17.07

3

 

 

 

 

 

 

 

 

 

 

 

 

 

6.00

20.48

1

6.00

20.48

 

 

 

 

 

 

 

T#C036A3, A4, AW

12.00

40.97

2

6.00

20.48

 

6.00

20.48

 

 

 

17.40

59.40

2

8.70

29.70

 

8.70

29.69

 

 

 

5.00

17.07

1

5.00

17.07

 

 

 

 

10.00

34.14

2

5.00

17.07

 

5.00

17.07

 

 

T#C048A1

13.80

47.11

2

8.80

30.04

 

5.00

17.07

4

 

 

17.60

60.09

2

8.80

30.04

 

8.80

30.04

 

 

6.00

20.48

1

6.00

20.48

 

 

 

 

 

 

 

T#C048A3, A4, AW

12.00

40.97

2

6.00

20.48

 

6.00

20.48

 

 

 

17.40

59.40

2

8.70

29.70

 

8.70

29.70

 

 

 

5.00

17.07

1

5.00

17.07

 

 

 

 

10.00

34.14

2

5.00

17.07

 

5.00

17.07

 

 

T#C060A1

13.80

47.11

2

8.80

30.04

 

5.00

17.07

5

 

 

17.60

60.09

2

8.80

30.04

 

8.80

30.04

 

 

6.00

20.48

1

6.00

20.48

 

 

 

 

 

 

 

T#C060A3, A4, AW

12.00

40.97

2

6.00

20.48

 

6.00

20.48

 

 

 

17.40

59.40

2

8.70

29.70

 

8.70

29.70

 

 

 

23.00

78.52

2

14.30

48.82

 

8.70

29.70

 

 

 

7.50

25.61

2

3.25

11.10

 

3.25

11.10

 

 

TSC060AK

10.90

37.23

2

5.45

18.61

 

5.45

18.61

 

 

 

14.4

49.18

2

7.20

24.59

 

7.20

24.59

 

 

 

9.00

30.73

1

9.00

30.73

 

—-

—-

 

 

T#C072A3, A4, AW

18.00

61.45

1

18.00

61.45

 

—-

—-

6

 

 

27.00

92.18

2

18.00

61.45

 

9.00

30.73

 

 

 

36.00

122.90

2

18.00

61.45

 

18.00

61.45

 

 

 

11.30

38.60

1

11.30

38.60

 

 

 

TSC072AK

16.90

57.72

2

11.30

38.60

 

5.60

19.13

 

 

 

22.60

77.18

2

11.30

38.60

 

11.30

38.60

 

 

 

9.00

30.73

1

9.00

30.73

 

—-

—-

 

 

T#SC090A3, A4, AW

18.00

61.45

1

18.00

61.45

 

—-

—-

 

 

 

27.00

92.18

2

18.00

61.45

 

9.00

30.73

7 1/2

 

 

36.00

122.90

2

18.00

61.45

 

18.00

61.45

 

 

 

11.30

38.60

1

11.30

38.60

 

 

 

TSC090AK

16.90

57.72

2

11.30

38.60

 

5.60

19.13

 

 

 

22.60

77.18

2

11.30

38.60

 

11.30

38.60

 

 

 

9.00

30.73

1

9.00

30.73

 

—-

—-

 

 

T#C092A3, A4, AW

18.00

61.45

1

18.00

61.45

 

—-

—-

 

 

 

27.00

92.18

2

18.00

61.45

 

9.00

30.73

 

 

 

36.00

122.90

2

18.00

61.45

 

18.00

61.45

 

 

 

9.00

30.73

1

9.00

30.73

 

—-

—-

8 1/2

 

T#C102A3, A4, AW

18.00

61.45

1

18.00

61.45

 

—-

—-

 

 

 

27.00

92.18

2

18.00

61.45

 

9.00

30.73

 

 

 

36.00

122.90

2

18.00

61.45

 

18.00

61.45

 

 

TSC102AK

16.90

57.72

2

11.30

38.60

 

5.60

19.13

 

 

 

22.60

77.18

2

11.30

38.60

 

11.30

38.60

 

 

 

18.00

61.45

1

18.00

61.45

 

—-

—-

10

 

T#C120A3, A4, AW

27.00

92.18

2

18.00

61.45

 

9.00

30.73

 

 

 

36.00

122.90

2

18.00

61.45

 

18.00

61.45

 

 

 

54.00

184.36

2

36.00

122.90

 

18.00

61.45

 

 

 

16.90

57.72

2

11.30

38.60

 

11.30

38.60

 

 

TSC120AK

22.60

77.18

2

11.30

38.60

 

11.30

38.60

 

 

 

33.80

115.43

2

22.50

76.84

 

11.30

38.60

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

 

 

1.

Does not include indoor fan power or heat.

Voltage

2

2.

Heaters are rated at 240v, 380v, 480v. and 600v. For other than rated voltage, CAP =(

)x rated cap.

Rated Voltage

RT-PRC005-EN

47

Page 47