Electrical (Standard

DataEfficiency)

Table ED-1 — UnitWiring — Standard Efficiency

 

 

 

 

 

 

 

 

 

Optional

 

 

 

Standard Indoor Fan Motor

Oversize Indoor Fan Motor

Belt Drive Indoor Fan Motor2

 

 

Unit

Minimum

Maximum Fuse

 

Minimum

Maximum Fuse

 

Minimum

Maximum Fuse

 

Unit

Operating

Circuit

Size Or Maximum

Circuit

Size Or Maximum

Circuit

Size or Maximum

Tons

Model No.

Voltage Range

Ampacity

Circuit Breaker1

Ampacity

Circuit Breaker1

Ampacity

Circuit Breaker1

 

TSC036A1

187-253

25.3

40

 

27.7

40

 

N/A

N/A

3

TSC036A3

187-253

17.9

25

 

20.3

30

 

20.6

30

 

TSC036A4

414-506

9.2

15

 

10.4

15

 

10.6

15

 

TSC036AW

517-633

7.7

15

 

8.3

15

 

8.3

15

 

TSC048A1

187-253

34.0

50

 

36.1

50

 

N/A

N/A

 

TSC048A3

187-253

23.9

35

 

26.0

40

 

25.3

35

4

TSC048A4

414-506

12.8

20

 

14.4

20

 

13.6

20

 

TSC048AW

517-633

9.8

15

 

10.6

15

 

10.0

15

 

TSC060A1

187-253

47.3

60

 

49.0

60

 

N/A

N/A

 

TSC060A3

187-253

31.5

50

 

33.2

50

 

30.3

45

5

TSC060A4

414-506

16.0

25

 

16.3

25

 

15.6

25

 

TSC060AW

517-633

12.2

15

 

12.8

20

 

11.8

15

 

TSC060AK

342-418

19.6

30

 

 

TSC072A3

187-253

32.7

50

 

34.0

50

 

6

TSC072A4

414-506

17.6

25

 

18.2

25

 

 

TSC072AW

517-633

12.8

20

 

13.6

20

 

 

TSC072AK

342-418

23.2

35

 

 

TSC090A3

187-253

42.7

60

 

45.8

60

 

 

TSC090A4

414-506

22.6

35

 

24.1

35

 

TSC090AW

517-633

17.6

25

 

18.8

25

 

TSC090AK

342-418

28.4

40

 

29.9

45

 

 

 

 

 

TSC092A3

187-253

38.9

50

 

42.0

50

 

 

TSC092A4

414-506

20.5

25

 

22.0

25

 

 

TSC092AW

517-633

15.5

20

 

16.7

20

 

 

TSC102A3

187-253

45.1

60

 

48.2

60

 

TSC102A4

414-506

24.0

30

 

25.5

35

 

 

TSC102AW

517-633

19.5

25

 

20.7

25

 

 

TSC102AK

342-418

32.6

40

 

35.6

45

 

 

TSC120A3

187-253

52.6

60

 

56.6

60

 

10

TSC120A4

414-506

26.9

35

 

28.9

35

 

 

TSC120AW

517-633

21.8

25

 

23.5

30

 

 

TSC120AK

342-418

32.6

40

 

35.6

45

 

NOTES:

1.HACR breaker per NEC.

2.Optional Belt Drive motor applies to 3-5 ton models only. The standard motor for 6-10 ton models is belt drive.

50

RT-PRC005-EN

Page 50
Image 50
Trane RT-PRC005 manual Electrical Standard, DataEfficiency, Table ED-1 UnitWiring Standard Efficiency