Electrical

 

Data

(High Efficiency)

Table ED-9 — UnitWiringWith Electric Heat (Single Point Connection) — 575Volts — High Efficiency

 

 

 

 

 

Standard Indoor Motor

Oversize Indoor Motor

 

To Use

Heater

Heater

Control

 

Max Fuse Size Or

 

Max Fuse Size Or

Tons

With

Model No.

kW Rating1

Stages

MCA

Max Circuit Breaker2

MCA

Max Circuit Breaker2

 

 

 

 

575 Volts Three Phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BAYHTRRW06A

6.0

1

8.6

15

9.3

15

3

THC036AW

BAYHTRRW12A

12.0

2

15.8

20

16.6

20

 

 

BAYHTRRW18A

17.4

2

22.3

25

23.1

25

 

 

 

 

 

 

 

 

 

 

 

BAYHTRRW06A

6.0

1

9.1

15

10.1

15

4

THC048AW

BAYHTRRW12A

12.0

2

16.3

20

17.3

20

 

 

BAYHTRRW18A

17.4

2

22.8

25

23.8

25

 

 

 

 

 

 

 

 

 

 

 

BAYHTRRW06A

6.0

1

11.8

15

12.4

15

5

THC060AW

BAYHTRRW12A

12.0

2

17.1

20

17.8

20

BAYHTRRW18A

17.4

2

23.6

25

24.3

25

 

 

 

 

BAYHTRRW23A

23.0

2

30.3

35

31.0

35

 

 

 

 

 

 

 

 

 

 

 

BAYHTRSW09A

9.0

1

13.5

20

14.3

20

6

THC072AW

BAYHTRSW18A

18.0

1

23.8

25

24.8

25

 

 

BAYHTRSW27A

27.0

2

34.6

35

35.6

40

 

 

BAYHTRSW36A

36.0

2

45.4

50

46.4

50

 

 

 

 

 

 

 

 

 

 

 

BAYHTRTW18A

18.0

1

24.8

25

26.3

30

THC092AW

BAYHTRTW27A

27.0

2

35.6

40

37.1

40

 

 

BAYHTRTW36A

36.0

2

46.4

50

47.9

50

 

 

 

 

 

 

 

 

 

 

 

BAYHTRTW18A

18.0

1

24.8

25

26.3

30

THC102AW

BAYHTRTW27A

27.0

2

35.6

40

37.1

40

 

 

BAYHTRTW36A

36.0

2

46.4

50

47.9

50

 

 

 

 

 

 

 

 

 

 

 

BAYHTRTW18A

18.0

1

26.3

30

28.4

30

10

THC120AW

BAYHTRTW27A

27.0

2

37.1

40

39.3

40

 

 

BAYHTRTW36A

36.0

2

47.9

50

50.0

50

 

 

BAYHTRTW54A

54.0

2

56.6

60

58.8

60

 

 

 

 

 

 

 

 

 

NOTES:

1.Heater kW ratings are at 208/240 for 208/230V unit

2.HACR type circuit breaker per NEC.