Performance
Data
Table
|
| 3 Ton |
| 4 Ton | 1 |
|
| 5 Ton |
|
| ||
|
| 1200 CFM |
| 1600 CFM |
|
|
| 2000 CFM |
|
| ||
|
| Single Phase | Three Phase | Single Phase | Three Phase | Single Phase | Three Phase | |||||
kW | Stages | T#C036A1 | T#C036A3,A4,AW | T#C048A1 | T#C048A3,A4,AW | T#C060A1 | T#C060A3,A4,AW | TSC060AK | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
5.00 | 1 | 13.2 | — | 9.9 |
| — | 7.9 | — | — | |||
6.00 | 1 | — | 15.8 |
| — |
| 11.9 |
| — | 9.5 | — | |
7.50 | 2 | — | — | — |
| — | — | — | 11.9 |
| ||
10.00 | 2 | 26.3 | — | 19.8 |
| — | 15.8 | — | — | |||
10.90 | 2 | — | — | — |
| — | — | — | 17.2 |
| ||
12.00 | 2 | — | 31.6 |
| — |
| 23.7 |
| — | 19.0 | — | |
13.80 | 2 | 36.4 | — | 27.3 |
| — | 21.8 | — | — | |||
14.40 | 2 | — | — | — |
| — | — | — | 22.8 |
| ||
17.40 | 2 | — | 45.8 |
| — |
| 34.4 |
| — | 27.5 | — | |
17.60 | 2 | — | — | 34.8 |
| — | 27.8 | — | — | |||
23.00 | 2 | — | — | — |
| — | — | 36.4 | — |
For minimum design airflow, see airflow performance table for each unit. To calculate temp rise at different air flow, use following formula:
NOTE:
1. Minimum allowable aiflow with a 17.4 or 17.6 KW heater is 1440 cfm.
KW x 3414 1.08 x CFM
Table
|
| 6Ton |
|
| 7½Ton |
| 8½Ton | 1 |
| 10 Ton | ||
|
| 2000 CFM |
| 3000 CFM |
| 3400 CFM |
|
| 4000 CFM | |||
|
|
|
|
| T#C090A3, A4, AW |
|
|
|
|
|
| |
kW | Stages | T#C072A3, A4, AW | TSC072AK | T#C092A3, A4, AW | TSC090AK | T#C102A3, A4, AW TSC102AK | T#C120A3,A4,AW | TSC120AK | ||||
9.00 | 1 | 14.2 | — | 9.5 | — | 8.4 | — |
| — | — | ||
11.30 | 1 | — | 14.9 |
| — | 11.9 |
| — | — |
| — | — |
16.90 | 2 | — | 22.3 |
| — | 17.8 |
| — | 15.7 |
| — | 13.4 |
18.00 | 1 | 28.5 | — | 19.0 | — | 16.7 | — | 14.2 | — | |||
22.60 | 2 | — | 29.8 |
| — | 23.8 |
| — | 21.0 |
| — | 17.9 |
27.00 | 2 | 42.7 | — | 28.5 | — | 25.1 | — | 21.3 | — | |||
33.80 | 2 | — | — |
| — | — |
| — | — |
| — | 26.7 |
36.00 | 2 | 56.9 | — | 37.9 | — | 33.5 | — | 28.5 | — | |||
54.00 | 2 | — | — |
| — | — |
| — | — | 42.7 | — |
For minimum design airflow, see airflow performance table for each unit. To calculate temp rise at different air flow, use following formula:
NOTE:
1. Minimum allowable aiflow with a 17.4 or 17.6 KW heater is 1440 cfm.
kW x 3414 1.08 x CFM
Table PD-65— Hot Gas ReheatTemperature Rise3
SCFM |
| Leaving Evaporator Dry Bulb [F] |
|
| |||
|
|
|
|
|
|
|
|
5 Tons | 35 | 40 | 45 | 50 | 55 | 60 | 65 |
1000 | 23.7 | 23.6 | 23.4 | 23.2 | 23.0 | 22.8 | 22.5 |
1200 | 22.6 | 22.4 | 22.2 | 22.0 | 21.8 | 21.6 | 21.3 |
1400 | 21.4 | 21.2 | 21.0 | 20.9 | 20.7 | 20.4 | 20.2 |
1600 | 20.3 | 20.1 | 19.9 | 19.7 | 19.5 | 19.3 | 19.0 |
1800 | 19.1 | 18.9 | 18.7 | 18.5 | 18.4 | 18.1 | 17.8 |
2000 | 17.9 | 17.8 | 17.6 | 17.4 | 17.2 | 16.9 | 16.6 |
2200 | 16.8 | 16.6 | 16.4 | 16.2 | 16.0 | 15.7 | 15.4 |
2400 | 15.6 | 15.4 | 15.2 | 15.1 | 14.9 | 14.6 | 14.3 |
10Tons | 35 | 40 | 45 | 50 | 55 | 60 | 65 |
2000 | 26.0 | 26.5 | 26.9 | 27.4 | 27.9 | 28.3 | 28.6 |
2400 | 23.5 | 24.1 | 24.7 | 25.3 | 25.9 | 26.4 | 26.9 |
2800 | 21.1 | 21.8 | 22.5 | 23.3 | 24.0 | 24.6 | 25.1 |
3200 | 18.7 | 19.5 | 20.3 | 21.2 | 22.0 | 22.7 | 23.4 |
3600 | 16.2 | 17.2 | 18.1 | 19.1 | 20.1 | 20.8 | 21.6 |
4000 | 13.8 | 14.9 | 15.9 | 17.0 | 18.1 | 19.0 | 19.8 |
4400 | 11.3 | 12.5 | 13.7 | 14.9 | 16.1 | 17.1 | 18.1 |
4800 | 8.9 | 10.2 | 11.5 | 12.9 | 14.2 | 15.3 | 16.3 |
NOTES:
1.Temperature rise does not account for indoor fan heat.
2.70 deg OD Ambient Temperature.
3.For units with the Dehumidification (Hot Gas Reheat) option.
48 |