Temp. Rise across Elect. Htr =
Temp. Rise across Elect. Htr =

Performance

Data

Table PD-633-5Tons AirTemperature Rise Across Electric Heaters (Degrees F)

 

 

3 Ton

 

4 Ton

1

 

 

5 Ton

 

 

 

 

1200 CFM

 

1600 CFM

 

 

 

2000 CFM

 

 

 

 

Single Phase

Three Phase

Single Phase

Three Phase

Single Phase

Three Phase

kW

Stages

T#C036A1

T#C036A3,A4,AW

T#C048A1

T#C048A3,A4,AW

T#C060A1

T#C060A3,A4,AW

TSC060AK

 

 

 

 

 

 

 

 

 

 

 

 

 

5.00

1

13.2

9.9

 

7.9

6.00

1

15.8

 

 

11.9

 

9.5

7.50

2

 

11.9

 

10.00

2

26.3

19.8

 

15.8

10.90

2

 

17.2

 

12.00

2

31.6

 

 

23.7

 

19.0

13.80

2

36.4

27.3

 

21.8

14.40

2

 

22.8

 

17.40

2

45.8

 

 

34.4

 

27.5

17.60

2

34.8

 

27.8

23.00

2

 

36.4

For minimum design airflow, see airflow performance table for each unit. To calculate temp rise at different air flow, use following formula:

NOTE:

1. Minimum allowable aiflow with a 17.4 or 17.6 KW heater is 1440 cfm.

KW x 3414 1.08 x CFM

Table PD-646-10Tons AirTemperature Rise Across Electric Heaters (Degrees F)

 

 

6Ton

 

 

7½Ton

 

8½Ton

1

 

10 Ton

 

 

2000 CFM

 

3000 CFM

 

3400 CFM

 

 

4000 CFM

 

 

 

 

 

T#C090A3, A4, AW

 

 

 

 

 

 

kW

Stages

T#C072A3, A4, AW

TSC072AK

T#C092A3, A4, AW

TSC090AK

T#C102A3, A4, AW TSC102AK

T#C120A3,A4,AW

TSC120AK

9.00

1

14.2

9.5

8.4

 

11.30

1

14.9

 

11.9

 

 

16.90

2

22.3

 

17.8

 

15.7

 

13.4

18.00

1

28.5

19.0

16.7

14.2

22.60

2

29.8

 

23.8

 

21.0

 

17.9

27.00

2

42.7

28.5

25.1

21.3

33.80

2

 

 

 

26.7

36.00

2

56.9

37.9

33.5

28.5

54.00

2

 

 

42.7

For minimum design airflow, see airflow performance table for each unit. To calculate temp rise at different air flow, use following formula:

NOTE:

1. Minimum allowable aiflow with a 17.4 or 17.6 KW heater is 1440 cfm.

kW x 3414 1.08 x CFM

Table PD-65— Hot Gas ReheatTemperature Rise3

SCFM

 

Leaving Evaporator Dry Bulb [F]

 

 

 

 

 

 

 

 

 

 

5 Tons

35

40

45

50

55

60

65

1000

23.7

23.6

23.4

23.2

23.0

22.8

22.5

1200

22.6

22.4

22.2

22.0

21.8

21.6

21.3

1400

21.4

21.2

21.0

20.9

20.7

20.4

20.2

1600

20.3

20.1

19.9

19.7

19.5

19.3

19.0

1800

19.1

18.9

18.7

18.5

18.4

18.1

17.8

2000

17.9

17.8

17.6

17.4

17.2

16.9

16.6

2200

16.8

16.6

16.4

16.2

16.0

15.7

15.4

2400

15.6

15.4

15.2

15.1

14.9

14.6

14.3

10Tons

35

40

45

50

55

60

65

2000

26.0

26.5

26.9

27.4

27.9

28.3

28.6

2400

23.5

24.1

24.7

25.3

25.9

26.4

26.9

2800

21.1

21.8

22.5

23.3

24.0

24.6

25.1

3200

18.7

19.5

20.3

21.2

22.0

22.7

23.4

3600

16.2

17.2

18.1

19.1

20.1

20.8

21.6

4000

13.8

14.9

15.9

17.0

18.1

19.0

19.8

4400

11.3

12.5

13.7

14.9

16.1

17.1

18.1

4800

8.9

10.2

11.5

12.9

14.2

15.3

16.3

NOTES:

1.Temperature rise does not account for indoor fan heat.

2.70 deg OD Ambient Temperature.

3.For units with the Dehumidification (Hot Gas Reheat) option.

48

RT-PRC005-EN

Page 48
Image 48
Trane RT-PRC005 manual Table PD-65- Hot Gas ReheatTemperature Rise3, Scfm, 10Tons