Trane RT-PRC005 manual Performance, 5 Ton, Data, High Efficiency, Table PD-44- Continued

Models: RT-PRC005

1 76
Download 76 pages 18.07 Kb
Page 39
Image 39
Table PD-44 — Continued

Performance

(5 Ton)

Data

High Efficiency

 

 

 

 

Table PD-44 — Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Horizontal Airflow

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

.10

 

 

.20

 

.30

 

.40

 

.50

 

.60

 

.70

 

.80

.90

 

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

1-HP Standard Motor & Field Supplied

 

 

 

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

Low Static Drive (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1600

707

0.35

774

0.42

837

0.50

898

0.57

953

0.65

1001

0.72

1045

0.80

1087

0.87

1129

0.95

1168

1.03

1800

778

0.48

840

0.56

897

0.64

953

0.72

1008

0.81

1058

0.89

1102

0.98

1143

1.06

1181

1.15

1219

1.23

2000

850

0.65

908

0.73

961

0.81

1012

0.90

1062

1.00

1111

1.09

1157

1.19

1198

1.28

1237

1.37

1274

1.47

2200

923

0.84

978

0.93

1028

1.02

1075

1.12

1120

1.22

1166

1.32

1211

1.43

2400

997

1.07

1049

1.17

1096

1.27

1140

1.37

1183

1.48

For Standard Evaporator Fan Speed (RPM), reference Table PD-50.

NOTES:

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.

1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.

Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table PD-44 — Continued

 

 

 

External Static Pressure (Inches of Water)

 

 

 

1.10

 

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

1-HP Standard Motor

 

 

 

 

 

1600

1206

1.12

1241

1.20

1275

1.28

1306

1.37

1338

1.46

1800

1256

1.32

1291

1.41

1326

1.50

2000

2200

2400

Table PD-45— Belt Drive Evaporator Fan Performance — 5 Ton — THC060A3,A4,AW — Horizontal Airflow — Dehumidification (Hot Gas Reheat)

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

.10

 

.20

 

.30

.40

 

 

.50

 

.60

 

.70

.80

 

.90

 

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

1-HP Standard Motor & Low

 

 

1-HP Standard Motor & Low

 

 

 

1-HP Standard Motor & Drive

 

 

 

Static DriveAccessory Kit (2)

 

 

 

Static Drive Accessory Kit (1)

 

 

 

 

 

 

 

 

 

 

1000

507

0.11

599

0.16

671

0.21

735

0.26

792

0.31

843

0.37

889

0.42

931

0.48

971

0.54

1007

0.59

1200

570

0.17

654

0.23

727

0.28

787

0.34

843

0.40

895

0.46

942

0.52

986

0.59

1026

0.66

1064

0.73

1400

638

0.25

711

0.31

782

0.38

844

0.44

896

0.51

946

0.58

993

0.65

1037

0.72

1078

0.79

1117

0.86

1600

707

0.35

774

0.42

837

0.50

898

0.57

953

0.65

1001

0.72

1045

0.80

1087

0.87

1129

0.95

1168

1.03

***MINIMUM AIR VOLUME REQUIRED FOR USE WITH OPTIONAL ELECTRIC HEAT IS 1600 CFM.

NOTES:

Data includes pressure drop due to standard filters and wet coils. Data does not include pressure drop due to reheat coil.

1 HP Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.

1.BAYLSDR008ARequired.

2.BAYLSDR008ARequired.

Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table PD-45 — Continued

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

1.10

 

1.20

1.30

1.40

1.50

 

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

1-HP Standard Motor & Drive

 

 

 

 

1000

1042

0.65

1078

0.70

1110

0.76

1142

0.82

1175

0.89

1200

1099

0.80

1133

0.86

1166

0.93

1197

0.99

1227

1.06

1400

1153

0.94

1188

1.02

1221

1.10

1253

1.18

1284

1.27

 

1600

1206

1.12

1241

1.20

1275

1.28

1306

1.37

1338

1.46

RT-PRC005-EN

 

 

 

 

 

 

 

 

 