Trane RT-PRC005 manual Performance, 5Ton, Data, Standard Efficiency, Table PD-25- Continued

Models: RT-PRC005

1 76
Download 76 pages 18.07 Kb
Page 29
Image 29
Table PD-25 — Continued

Performance

(5Ton)

Data

Standard Efficiency

 

 

 

 

 

 

 

 

Table PD-25— Belt Drive Evaporator Fan Performance — 5 Ton — TSC060A3,A4,AW — Downflow Airflow

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM

BHP RPM

BHP RPM BHP

RPM BHP

 

 

 

1-HP Standard Motor & Field Supplied

 

 

 

 

Low Static Drive (1)

 

 

1600

674

0.33

735

0.39

786

0.45

835

0.50

1800

743

0.46

801

0.52

849

0.59

894

0.65

2000

813

0.61

866

0.68

914

0.76

956

0.83

2200

886

0.80

933

0.87

980

0.96

1019

1.03

2400

959

1.03

1000

1.10

1045

1.19

1085

1.28

 

 

 

 

 

1-HP Standard Motor & Drive

 

 

883

0.56

928

0.63

972

0.70

1011

0.77

1048

0.84

1084

0.90

937

0.70

979

0.77

1021

0.85

1060

0.93

1098

1.01

1134

1.09

995

0.89

1035

0.96

1073

1.02

1111

1.10

1147

1.19

1183

1.28

1057

1.11

1093

1.18

1129

1.25

1164

1.33

1198

1.40

1233

1.50

1121

1.36

1154

1.45

1188

1.53

1221

1.60

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.

NOTES:

Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.

Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.

1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.

Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table PD-25 — Continued

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

 

 

 

1.10

1.20

 

1.30

 

 

1.40

 

1.50

 

 

 

 

 

 

 

 

 

 

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

 

 

 

 

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1600

1117

0.97

1150

1.04

1183

1.11

1215

1.18

1244

1.25

 

 

 

 

 

 

 

 

 

1800

1167

1.16

1199

1.24

1230

1.31

1259

1.39

1289

1.47

 

 

 

 

 

 

 

 

 

2000

1216 1.37

1249

1.47

 

 

 

 

 

 

 

 

 

 

 

2200

 

 

 

 

 

 

 

 

 

 

 

 

2400

 

 

Table PD-26 — Belt Drive Evaporator Fan Performance — 5 Ton — TSC060A3,A4,AW — Horizontal Airflow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

.10

 

.20

 

 

.30

 

.40

.50

 

.60

 

.70

 

 

 

.80

.90

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

1-HP Standard Motor & Field Supplied

 

 

 

 

 

 

1-HP Standard Motor & Drive

 

 

 

 

Low Static Drive (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1600

746

0.39

812

0.47

876

0.54

934

0.62

985

0.70

1032

0.77

1074

0.85

1117

0.93

1157

1.01

1196

1.09

1800

824

0.54

883

0.62

940

0.70

996

0.79

1048

0.88

1094

0.96

1137

1.05

1176

1.14

1214

1.22

1252

1.31

2000

902

0.72

957

0.80

1008

0.90

1059

0.99

1110

1.09

1157

1.19

1200

1.28

1239

1.38

1276

1.47

1311

1.50

2200

981

0.93

1032

1.03

1080

1.13

1126

1.23

1173

1.34

1219

1.44

 

2400

1061

1.19

1109

1.29

1153

1.40

1196

1.50

 

For Standard Evaporator Fan Speed (RPM), reference Table PD-48.

NOTES:

Data includes pressure drop due to standard filters and wet coils No accessories or options are included in pressure drop data.

Refer to Table PD-54 to determine additional static pressure drop due to other options/accessories. Fan Motor Heat (MBH) = 2.829 x Fan BHP+.4024.

1. Field Supplied Fan Sheave AK56 required. Field Supplied Belt may be necessary.

Trane’s factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product’s warranty will not be affected.

Table PD-26 — Continued

 

 

 

External Static Pressure (Inches of Water)

 

 

 

1.10

1.20

 

1.30

 

1.40

 

1.50

 

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

1-HP Standard Motor & Drive

 

 

 

 

 

1600

1232

1.18

1267

1.26

1299

1.35

1332

1.45

1800

1289

1.41

1323

1.50

2000

2200

2400

RT-PRC005-EN

29

Page 29
Image 29
Trane RT-PRC005 manual Performance, 5Ton, Data, Standard Efficiency, Table PD-25- Continued, Table PD-26- Continued