High Efficiency

General

(3 - 5Ton)

Data

High Efficiency

 

 

 

 

Table GD - 3 — General Data

 

3Ton

4Ton

 

5Ton

 

Convertible Units

Convertible Units

Convertible Units

 

THC036A1,A3,A4,AW

THC048A1,A3,A4,AW

THC060A1

THC060A3,A4,AW

Cooling Performance1

 

 

 

 

Gross Cooling Capacity

38,000

49,800

62,100

62,400

SEER / EER2

12.5/—

12.0/—

11.8/—

12.0/ —

Nominal CFM / ARI Rated CFM

1,200/1,200

1,600/1,600

2,000/2,000

2,000/2,000

ARI Net Cooling Capacity

36,600

47,500

59,000

59,500

System Power (kW)

3.33

4.48

5.73

5.56

Compressor

 

 

 

 

No./Type

1/Climatuff Scroll

1/Climatuff Scroll

1/Climatuff Scroll

1/Climatuff Scroll

Outdoor Sound Rating (dB)3

83

85

84

84

Outdoor Coil —Type

Lanced

Lanced

Lanced

Lanced

Tube Size (in.) O.D.

0.3125

0.3125

0.3125

0.3125

Face Area (sq ft)

7.19

9.59

10.96

10.96

Rows/FPI

2/17

3/17

3/17

3/17

Indoor Coil —Type

Lanced

Lanced

Lanced

Lanced

Tube Size (in.)

0.3125

0.3125

0.3125

0.3125

Face Area (sq ft)

6.68

6.68

7.71

7.71

Rows/FPI

3/16

4/16

4/16

4/16

Refrigerant Control

Short Orifice

Short Orifice

Short Orifice

Short Orifice9

Drain Connection No./Size (in.)

1/¾ NPT

1/¾ NPT

1/¾ NPT

1/¾ NPT

Outdoor Fan —Type

Propeller

Propeller

Propeller

Propeller

No. Used/Diameter (in.)

1/22

1/22

1/22

1/22

DriveType/No. Speeds

Direct/1

Direct/1

Direct/1

Direct/110

CFM

2550

3050

3170

3370

No. Motors/HP

1/.20

1/.33

1/.33

1/.33

Motor RPM

1115

1115

1115

1115

Direct Drive Indoor Fan —Type

FC Centrifugal

FC Centrifugal

FC Centrifugal

FC Centrifugal

No. Used

1

1

1

1

Diameter xWidth (in.)

10 x 10

11 x 11

11 x 11

11 x 11

DriveType/No. Speeds

Direct/2

Direct/2

Direct/2

Direct/2

No. Motors

1

1

1

1

Motor HP (Standard/Oversized)

.33/.50

.60/.80

.90/1.00

.90/1.00

Standard Motor RPM (Low/High Speed)

950/1060

930/1000

985/1100

985/1100

Oversized Motor RPM (Low/High Speed)

1100/1145

1000/1100

1080/1135

1080/1135

Motor Frame Size (Standard/Oversized)

48/48

48/48

48/48

48/48

Belt Drive Indoor Fan —Type

FC Centrifugal

FC Centrifugal

FC Centrifugal

No. Used

1

1

1

Diameter xWidth (in.)

11 x 11

11 x 11

11 x 11

DriveType/No. Speeds

Belt/Variable Speed 6

Belt/Variable Speed 6

Belt/Variable Speed

No. Motors

1

1

1

Motor HP

1.00

1.00

1.00

Standard Motor RPM

1750

1750

1750

Motor Frame Size

56

56

56

Filters —Type Furnished 7

Throwaway

Throwaway

Throwaway

Throwaway

(No.) Size Recommended (in.)

(2) 20 x 25 x 1

(2) 20 x 25 x 1

(2) 20 x 30 x 1

(2) 20 x 30 x 111

Optional Hot Gas Reheat Coil -Type

Lanced

Tube Size (in.) OD

0.375

Face Area (sq. ft)

2.22

Rows/FPI

2/18

Refrigerant Charge (Lbs of R-22)4

 

 

 

 

Standard

5.38

7.75

7.9

8.4

Optional Hot Gas Reheat Coil

10.7

NOTES:

1.Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI Standard 210/240.

2.EER and SEER are rated at ARI conditions and in accordance with DOE test procedures.

3.Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For more information refer to Table PD-51

4.Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

5.Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 8.1.

6.Belt Drive Motor is not available for THC036A1, THC048A1.

7.Optional 2” Pleated Filters also available.

8.Refrigerant Charge shown is for 3 phase. 1 phase Refrigerant Charge is 4.5.

9.TXV is supplied from the factory as standard with the Dehumidification (Hot Gas Reheat) option.

10.With Dehumidification (Hot Gas Reheat) option: Direct/2.

11.2" pleated filters is a factory installed option. 2" pleated filters is standard with the Dehumidification (Hot Gas Reheat) option.