SDSFE31xx-100 Industrial Device Server

Transition Networks

Connecting power to the Device Server, continued

CAUTION

When connecting DC power wires to the terminal-block plug, pay close attention to the polarity markings shown near the terminal block of the Device Server. Failure to observe this caution could result in damage to the device.

Terminal-blockTo wire the six-contact-terminal-block plug for redundant power, do the following: plug wiring

Note: The six-contact-terminal-block plug is constructed (keyed) to mate with the Device Server terminal block. When wiring the plug for power, use the polarity markings next to the terminal block on top of the Device Server to ensure proper connection.

Step

Action

1.

Turn the external power source OFF.

2.

Strip the power wires as required.

3.

Insert one stripped power wire into the terminal-block plug, Observe

 

polarity. See Figure 7.

4.

Secure the wire using a flathead screwdriver by tightening the contact

 

screw. See Figure 7.

5.

Repeat Steps 3 and 4 until all wires are installed and secured.

Figure 7: Six-Contact-Terminal-Block Plug (Primary/Redundant Power Wiring)

Continued on next page

24-Hour Technical Support: 1-800-260-1312 International: 00-1-952-941-7600

13

Page 25
Image 25
Transition Networks SDSFE31XX-100 manual Connecting power to the Device Server, Turn the external power source OFF