Vermont Castings, Majestic Products DVRT36/39/43
Troubleshooting the Gas Control System
SIT NOVA 820 MILLIVOLT VALVE
Note: Before trouble shooting the gas control system, be sure external gas shut off is in the “ON” position.
WARNING: BEFORE DOING ANY GAS CONTROL SERVICE WORK, REMOVE GLASS FRONT.
SYMPTOM | POSSIBLE CAUSES | CORRECTIVE ACTION | |
|
|
|
|
1. Spark ignitor will not light. | A. Defective or misaligned | Using a match, light pilot. If pilot lights, turn off | |
|
| electrode at pilot | pilot and push the red button again. If pilot will not |
|
|
| light, check gap at electrode and pilot; it should be |
|
|
| 1/8 in. to have a strong spark. |
|
|
|
|
|
| B. Defective ignitor | Push Piezo Ignitor Button. Check for spark at |
|
| (Push Button) | electrode and pilot. If no spark to pilot, and elec- |
|
|
| trode wire is properly connected, replace ignitor. |
|
|
|
|
2. Pilot will not stay lit after | A. Defective pilot generator | Check pilot flame. Must impinge on thermocouple/ | |
carefully following lighting | (thermocouple); remote | thermopile. NOTE: This pilot burner assembly | |
instructions. | wall switch | utilizes | |
|
|
| The thermocouple operates the main valve |
|
|
| operation (On and Off). Clean and/or adjust pilot |
|
|
| for maximum flame impingement on thermopile |
|
|
| and thermocouple. |
|
|
|
|
|
| B. Defective automatic valve | Turn valve knob to “Pilot.” Maintain flow to pilot; |
|
|
| millivolt meter should read greater than 10 mV. If |
|
|
| the reading is okay and the pilot does not stay On, |
|
|
| replace the gas valve. NOTE: An interrupter block |
|
|
| (not supplied) must be used to conduct this test. |
|
|
|
|
3. Pilot burning; no gas to | A. Wall switch or wires defective | Check wall switch and wires for proper connec- | |
main burner |
| tions. Jumper wire across terminals at wall | |
|
|
| switch; if burner comes on, replace defective wall |
|
|
| switch. If okay, jumper wires across wall switch |
|
|
| wires at valve. If burner comes on, wires are faulty |
|
|
| or connections are bad. |
|
|
|
|
|
| B. Thermopile may not be | 1. Be sure wire connections from thermopile at |
|
| generating sufficient | gas valve terminals are tight and thermopile is |
|
| millivoltage | fully inserted into pilot bracket. |
|
|
| 2. One of the wall switch wires may be grounded. |
|
|
| Remove wall switch wires from valve terminals; |
|
|
| if pilot now stays lit, trace wall switch wiring for |
|
|
| ground. May be grounded to fireplace or gas |
|
|
| supply. |
|
|
| 3. Check thermopile with millivolt meter. Take |
|
|
| reading at thermopile terminals of gas valve. |
|
|
| Should read |
|
|
| while holding valve knob depressed in pilot |
|
|
| position and wall switch “Off.” Replace faulty |
|
|
| thermopile if reading is below specified minimum. |
|
|
|
|
|
| C. Plugged burner orifice | Check burner orifices for debris and remove. |
|
|
|
|
|
| D. Defective automatic valve | Turn valve knob to “On;” place wall switch to “On.” |
|
| operator | Millivolt meter should read greater than 100 mV. If |
|
|
| the reading is okay and the burner does not come |
|
|
| On, replace the gas valve. |
|
|
|
|
4. Frequent pilot outage | A. Pilot flame may be too low | Clean and/or adjust pilot flame for maximum flame | |
problem | or blowing (high), causing the | impingement on thermopile and thermocouple. | |
|
| pilot safety to drop out. |
|
|
|
|
|
|
| B. Possible blockage of the vent | Check the vent terminal for blockage (recycling the |
|
| terminal | flue gases). |
|
|
|
|
36 | 10002428 |