Xantrex Technology RS232-XPD manual To install the ferrite block

Models: RS232-XPD

1 60
Download 60 pages 29.02 Kb
Page 33
Image 33
To install the ferrite block:

Installation and Configuration

User Signals

Figure 2.6 J21 User Signal Connector Circuit Block Diagram

J21 Cable Use a standard 8-position telephone jack and data cable to connect to J21. Add a Connection ferrite block to reduce radiated emission. The one inch square ferrite block with built-in housing clip is packaged and shipped with the power supply interface card.

To install the ferrite block:

1.Position the block no more than 5 cm (2") from the power supply end of the J21 user cable.

2.Open the ferrite block housing.

3.Loop the cable through the ferrite block. See Figure 2.7, “J21 User Cable with Ferrite Block” on page 32.

4.Close the housing clip.

The ferrite block ensures that the power supply system meets radiated emission requirement 89/336/EEC for CE mark approval. See the power supply's operating manual for noise specifications.