Operation

Important Owner’s Considerations

Engine Oil

This engine is shipped from the factory filled with the recommended oil. Before starting the engine, check oil level and ensure that engine is serviced as described in the engine operator’s manual. See Engine Oil in Maintenance.

notice

Any attempt to crank or start the engine before it has been properly serviced with the recommended oil will result in equipment failure.

Refer to Maintenance and engine manual for oil fill information.

Damage to equipment resulting from failure to follow this instruction will void engine and generator warranty.

Battery

The home generator is supplied with a sealed, lead-acid, rechargeable, 12 Volt DC 55 Amp-Hour, valve regulated battery. It is installed in the unit and the battery cables are connected at the factory.

With the battery installed, all wiring to transfer switch and home generator completed, utility power supplied to the Automatic Transfer Switch, and the unit in AUTO mode, the battery receives a trickle charge while the engine is not running. The trickle charge cannot be used to recharge a battery that is completely discharged.

15 Amp Fuse

The generator’s 15 Amp fuse was removed at the factory to prevent the unit from starting during shipping. Your installer will ensure the fuse is properly installed upon completion of the installation.

Automatic Operation

To select automatic operation, do the following:

1.Set the service disconnect or main distribution panel circuit breaker that sends utility voltage to the transfer switch to ON.

2.Set the generator’s main circuit breaker to its ON position.

3.Set the system switch to AUTO.

caution

With the system switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting normally occurs when utility source voltage drops below a preset level or during the normal exercise cycle.

To prevent possible injury that may be caused by such sudden starts, always set the system switch to OFF.

Remove the 15 Amp fuse before working on or around the generator or transfer switch.

Checking Automatic Operation

To check the system for proper automatic operation, proceed as follows:

1.Turn OFF the service disconnect or main distribution panel circuit breaker sending power to the automatic transfer switch.

The engine will crank and start when the utility voltage drops out and the sensor has timed out. Let the system go through its entire automatic operation sequence.

2.With the generator output supplying its loads, turn ON the service disconnect or main distribution panel circuit breaker that supplies utility power to the Automatic Transfer Switch.

3.The automatic transfer switch will transfer loads back to the utility power after 5 minute minimum run time and utility is restored.

4.The generator will run for an additional one minute for engine cool down, then shut down.

NOTE: If utility is restored and generator does not shut down after 10 minutes, set system switch to OFF and contact your installer or local service center.

This completes the test procedures for automatic operation. The home generator will now start automatically when utility power is lost and will supply power to the transfer switch.

13

Image 13
Contents 20000 Home Generator Date of Purchase Generator Where to Find UsEngine Model Number Model Revision Serial NumberTable of Contents Hazard Symbols and Meanings Safety RulesPage See Essential Circuits For the Installing Dealer/Contractor InstallationFor the Home Owner Owner OrientationEssential Circuits Generator LocationEssential Circuit Selection Delivery InspectionHome generator is supplied with Home Generator Features and ControlsSystem Control Panel Service Tool For use by qualified service personnel onlyTo Open an Access Door Access DoorsTo Close an Access Door Important Owner’s Considerations OperationAutomatic Operation Setting Exercise Timer MaintenanceFault Detection System Servicing the SystemLow Battery Voltage No LED Discharged BatteryLow Oil Pressure Low Voltage GeneratorEngine Oil Generator MaintenanceCharging the Battery BatteryTo fill your engine with oil Servicing the Battery When Calling the FactoryTo Clean the Generator StorageProblem Cause Correction TroubleshootingDown when loads are connected AvailableLimited Warranty Page BRIGGSandSTRATTON.COM Llamada Línea Directa de Generador de Hogar Manual del OperarioFecha de compra Generador Dónde encontrarnosMotor Número de Modelo Revisión Número de SerieInstrucciones importantes de seguridad Instalación Problemas GarantíaControles y características OperaciónSímbolos de Peligro y Significados Conserve estas instruccionesAdvertencia Precaución Para el Propietario Doméstico InstalaciónOrientación para el propietario Factores Relacionados con el CombustibleCircuitos Fundamentales Ubicación del GeneradorDistancias Desde el Generador Selección de los Circuitos Fundamentales Dispositivo Vatiaje deEl Generador Doméstico incluye lo siguiente Inspección al Momento de la EntregaGenerador Doméstico Controles y característicasAjustes. Conserve este manual para referencias futuras Calcomanía de Datos de la Unidad situada en la basePanel de control del sistema Para abrir una puerta de acceso Puertas de AccesoPara cerrar una puerta de acceso Funcionamiento Automático OperaciónVerificación de la Operación Automática Mantenimiento Configuración del Temporizador de PrácticaParo del Sistema Sistema de Detección de FallasBaja Tensión de la Batería No se Enciende el LED Batería DescargadaBaja Presión de Aceite Baja TensiónAceite del Motor Mantenimiento del GeneradorPara llenar el motor de aceite BateríaCargar la Batería Almacenamiento Si Llama a la FábricaServicio la Batería Para Limpiar el GeneradorProblemas Causa Corrección ProblemasGarantía Limitada BRIGGSandSTRATTON.COM Appelez Ligne Directe de Génératrice la Maison Manuel de l’UtilisationDate d’achat Génératrice Où nous trouverMoteur Numéro de modèle Révision Numéro de sérieFonctions et commandes Fonctionnement Directives de sécurité importantes InstallationEntreiten Dépannage GarantieVeuillez conserver ces instructions Symboles de Danger et MoyensDirectives de sécurité importantes SécuritéAvertissement Avis Conseils au propriétaire Au Propriétaire RésidentielFacteurs Relatifs au Combustible Circuits Essentiels Emplacement de la GénératriceDégagement Autour de la Génératrice Sélection des Circuits Essentiels Le Groupe électrogène est livré avec les éléments suivants Vérification de la LivraisonSécurité Instalación Commandes Fonctionnement Fonctions et commandesEntretien Dépannage Garantie Tableau de commande de système Portes d’Accès Sécurité Instalación CommandesPour ouvrir une porte d’accès Pour fermer une porte d’accèsFonctionnement automatique FonctionnementVérification du Fonctionnement Automatique Réglage de la Minuterie du Cycle d’Exercice EntreitenArrêt du Système Système de Détection des PannesFaible Tension de la Batterie Aucun DEL Batterie déchargéeFaible Pression d’Huile Basse Tension’Huile Moteur Entretien du GénérateurPour Nettoyer le Générateur BatteriePour mettre de l’huile dans le moteur Rechargez la BatterieDépannage Problème Cause SolutionCommunications avec le Fabricant RemisageGarantie Limitée