Diversion Control Troubleshooting
Table 4-2 Diversion Control Problems
Problem | Possible Cause | Solution |
|
|
|
Diversion load operates | Bulk Voltage setting on | A. Bulk voltage on |
while a generator (fuel | diversion controller is | controller needs to be set |
powered) is running. | set too close to other | higher than other charging |
| charger settings. | sources or use a |
|
| switch/relay to disable the |
|
| diversion load while using |
|
| a generator. |
|
|
|
Diversion load operates | Mode jumper is set for | Change jumper setting. |
immediately at full | “Load Control” instead |
|
power when load | of “Charge Control”. |
|
breaker is turned on. |
|
|
|
|
|
67 |