Troubleshooting
Load Control Troubleshooting
The following table lists possible problems that may arise when using the
Table 4-3 Load Control Problems
Problem | Possible Cause | Solution |
|
|
|
Load disconnects at | A. Load Control decal | A. Install the decal or |
different point than set | is not in place. | follow procedure in |
for. | B. BTS has been | manual. See “Setting |
| installed. | Voltage Parameters for |
|
| Load Control Mode” on |
|
| page 24. |
|
| B. Battery Temperature |
|
| Sensors should not be used |
|
| in load control |
|
| applications. |
|
|
|
Status LED Blinks | Startup or Inrush | Use larger controller or |
Orange after switching | current exceeds | “buffer” the controller by |
on the load breaker. | controller rating. | using a relay/contactor |
|
| where the controller |
|
| operates only the coil of |
|
| the relay/contactor and not |
|
| directly to the DC load. |
|
|
|