Service
If you are returning your Inverter/Charger to Tripp Lite, please pack it carefully, using the ORIGINAL PACKING MATERIAL that came with the unit. Enclose a letter describing the symptoms of the problem. If the Inverter/Charger is within the warranty period, enclose a copy of your sales receipt. To obtain service you must obtain a Returned Material Authorization (RMA) number from Tripp Lite or an authorized Tripp Lite service center.
Maintenance
Your Inverter/Charger requires no maintenance and contains no
Troubleshooting
Try these remedies for common Inverter/Charger problems before calling for assistance. Call Tripp Lite Customer Service before returning your unit for service.
SYMPTOM | PROBLEMS | CORRECTIONS | |
|
|
| |
No AC Output | Unit is not properly connected to utility power. | Connect unit to utility power. | |
(All Indicator Lights Are OFF) |
|
| |
Operating Mode Switch is set to “OFF” and | Set Operating Mode Switch to “AUTO/REMOTE” or “CHARGE ONLY.” | ||
| |||
| AC input is present. |
| |
|
|
| |
| This is normal when the Operating Mode Switch | No correction is required. AC output will return when AC input | |
| is set to “CHARGE ONLY” and AC input is absent. | returns. Set Operating Mode Switch to “AUTO/REMOTE” if you require | |
| AC output. | ||
|
| ||
|
|
| |
| Unit has shut down due to battery overcharge (preventing | Disconnect any auxiliary chargers. Reset by moving Operating | |
| battery damage). The problem may be with connected | Mode Switch to “OFF.” Wait 1 minute and switch to “AUTO/REMOTE” | |
| or “CHARGE ONLY.” If unit remains in shutdown mode after several | ||
| auxiliary chargers, if any, or with the unit’s charger. | ||
| attempts to reset, contact Tripp Lite Customer Service for | ||
|
| ||
|
| assistance. | |
|
|
| |
| Unit has shut down due to excessive battery discharge. | Use an auxiliary charger* to raise battery voltage. Check external | |
|
| battery connections and fuse. Unit automatically resets when | |
|
| condition is cleared. | |
|
|
| |
| Unit has shut down due to overload. | Reduce load. Reset by moving Operating Mode Switch to “OFF.” | |
|
| Wait 1 minute. Switch to “AUTO/REMOTE” or “CHARGE ONLY.” | |
|
|
| |
Battery Not Recharging | Connected batteries are dead. | Check and replace old batteries. | |
(AC Input Present) |
|
| |
Battery fuse* is blown. | Check and replace fuse.* | ||
| |||
|
|
| |
| Battery cabling* is loose. | Check and tighten or replace cabling.* | |
|
|
| |
| Unit has shut down due to battery overcharge (preventing | Disconnect any auxiliary chargers. Reset by moving Operating | |
| battery damage). The problem may be with connected | Mode Switch to “OFF.” Wait 1 minute and switch to “AUTO/REMOTE” | |
| or “CHARGE ONLY.” If unit remains in shutdown mode after several | ||
| auxiliary chargers, if any, or with the unit’s charger. | ||
| attempts to reset, contact Tripp Lite Customer Service for | ||
|
| ||
|
| assistance. | |
|
|
| |
All Three Battery Indicator Lights | Battery is excessively discharged. | Use an auxiliary charger* to raise battery voltage. Check external | |
Are Slowly Flashing |
| battery connections and fuse. Unit automatically resets when | |
(½ Second Flashes) |
| condition is cleared. | |
|
|
| |
All Three Battery Indicator Lights | Battery is overcharged. Unit will shut down to prevent battery | Disconnect any auxiliary chargers. Reset by moving Operating | |
Are Rapidly Flashing | damage. The problem may be with connected auxiliary | Mode Switch to “OFF.” Wait 1 minute and switch to “AUTO/REMOTE” | |
(¼ Second Flashes) | chargers, if any, or with the unit’s charger. | or “CHARGE ONLY.” If unit remains in shutdown mode after several | |
|
| attempts to reset, contact Tripp Lite Customer Service for | |
|
| assistance. | |
|
|
| |
Red “LOW” Battery | Battery voltage is low. Unit will automatically shut down after | Make sure that AC power is present in order to recharge batteries. | |
Indicator Light is Flashing | 10 seconds to protect battery from damage. | Reset by moving Operating Mode Switch to “OFF” then to “AUTO/ | |
|
| REMOTE” or “CHARGE ONLY.” | |
|
|
| |
| False reading due to undersized or insufficiently connected | Use sufficient size DC cable sufficiently connected to the | |
| DC cabling. | Inverter/Charger. | |
|
|
| |
Red “LOAD” Operation | Inverter is overloaded. Unit will automatically shut down after | Reduce load. Reset by moving Operating Mode Switch to “OFF.” | |
Indicator Light Flashing | 5 seconds. | Wait 1minute. Switch to “AUTO/REMOTE” or “CHARGE ONLY.” | |
|
|
| |
|
|
11