Tripp Lite APSX6048VR owner manual Set Battery Charge Conserver Load Sense Control-OPTIONAL

Page 7

Configuration (continued)

12Select Battery Type - REQUIRED

CAUTION: The Battery Type DIP Switch setting must match the type of batteries you connect, or your batteries may be degraded or damaged over an extended period of time. See “Battery Selection,” for more information.

Battery Type

Switch Position

 

 

AGM/Gel Cell (Sealed) Battery

Up

Wet Cell (Vented) Battery

Down (factory setting)

AGM/

Gel Cell

9 10 11 12

Set Battery Charge Conserver (Load Sense) Control—OPTIONAL

In order to save battery power, the unit's inverter automatically shuts off in the absence of any power demand from connected equipment or appliances (the electrical load). When the Inverter/Charger detects a load, it automatically turns its inverter function on. Users may choose the minimum load the Inverter/Charger will detect by adjusting the Battery Charge Conserver Control (see diagram). Using a small tool, turn the control clockwise to lower the minimum load that will be detected, causing the inverter to turn on for smaller loads. When the control is turned fully clockwise, the inverter will operate even when there is no load. Turn the control counterclockwise to increase the minimum load that will be detected, causing the inverter to stay off until the new minimum load is reached.

LOAD

SENSE

MAX OFF

NOTE: The factory setting for the control is fully clockwise. However, based on the threshold load to which you’d like the inverter to respond, you should adjust the control counterclockwise to reduce its sensitivity until the inverter is active only when connected equipment or appliances are actually in use.

Connect Remote Control—Optional

The unit features an 8-conductor telephone style jack on the front panel for use with an optional remote control module (Tripp Lite model APSRM4, sold separately). The remote module allows the Inverter/Charger to be mounted in a compartment or cabinet out of sight, while operated conveniently from a remote location. See instructions packed with the remote control module.

Connect Battery Temperature Sensing Cable—OPTIONAL (Contact Tripp Lite for optional temperature sensing cable accessory.)

The battery temperature sensing function prolongs battery life by adjusting the charge float voltage level based on battery temperature. Connect the sensor cable (the cable has an RJ style connector on one end and a sensor on the other) to the RJ style jack located on the front panel of the Inverter/Charger labeled “RMT BATT TEMP.” With user-supplied electrical or duct tape, affix the sensor to the side of the battery below the electrolyte level. Make sure that nothing, not even tape, comes between the sensor and the side of the battery. To guard against false readings due to ambient temperature, place the sensor between batteries, if possible, and away from sources of extreme heat or cold. If the sensor cable is not used, the Inverter/Charger will charge according to its default value

(25º C).

 

 

 

 

 

1

 

Pin Configuration

Connect Automatic Generator Starter—OPTIONAL

 

 

 

 

2

2

- Common

 

 

 

 

3

- N.C.

Connect the RJ type modular jack on the front panel labeled

“RMT GEN START”

to

separate

3

 

 

 

(Normally Closed)

 

4

 

generator ON/OFF switching mechanism with user-supplied cable (see Pin Configuration Diagram).

 

4

- N.O.

5

 

Once attached,

the interface will

allow the Inverter/Charger to

automatically switch

a

separate

 

 

(Normally Open)

 

 

 

 

6

 

 

generator on

when connected

battery voltage levels are

low and switch it

off when

 

 

 

 

 

 

 

battery voltage levels are high.

7

Image 7
Contents Apsx Pure Sine Wave DC-to-AC Inverter/Charger ContentsEquipment Connection Warnings Important Safety InstructionsBattery Connection Warnings Location WarningsFeature Identification Indicator Lights Switch Modes Operation 10 11 ConfigurationSet Configuration DIP Switches OFF before changing DIP Switch settingsVoltage Switch Position 270 VAC 260 VAC Down factory setting Select Low VAC Input Voltage Point for Switching to BatteryWet Cell Vented Battery Set Battery Charge Conserver Load Sense Control-OPTIONALConnect Remote Control-Optional Select Battery Type Required Switch PositionExample Battery SelectionSelect Battery Type Match Battery Amp-Hour Capacity to Your ApplicationFeature Identification Warranty. See table below forRecommended cable sizing chart Connect Ground UsingAC Generator Input AC Input/Output ConnectionMaintenance ServiceTroubleshooting Regulatory Compliance Identification Numbers Limited WarrantyMejor Para Sus Baterías ContenidoConfiable Energía de Respaldo de Emergencia Mejor para Su EquipoAdvertencias para la Conexión del Equipo Instrucciones de Seguridad ImportantesAdvertencias para la Ubicación de su Equipo Advertencias para la Conexión de la BateríaVentiladoresdeEnfriamientoControladosTermostáticamente Identificación de CaracterísticasINV Invirtiendo Indicador Amarillo Esta luz se Iluminara OperaciónModos del Interruptor Luces IndicadorasAjuste los Interruptores de Configuración DIP ConfiguraciónOperación a 230V APSX3024SW Configuración continuaciónConecte el Arrancador Automático del Generador-OPCIONAL Conecte el Control Remoto-OPCIONALSeleccione el Tipo de Batería Requerido Paso 1 Determine el Wattaje Total Requerido Selección de la BateríaSeleccione el Tipo de Batería EjemploConexión en Serie Conexión de la BateríaEntrada CA Conexión de Entrada/Salida CAEntrada del Generador de CA TierraServicio Solución de ProblemasMantenimiento Cumplimiento de la Regulación del Número de Identificación Garantía LimitadaMeilleur pour vos batteries Table des matièresAlimentation de secours fiable Meilleur pour votre équipementMises en garde concernant les connexions de léquipement Mises en garde concernant lemplacement de londuleurImportantes consignes de sécurité Mises en garde concernant la connexion de batterieCaractéristiques Niveau approximatif de charge FonctionnementModes Témoins lumineuxCommutateurs DIP situés sur le panneau avant de Laide dun petit outil, établissez la configuration desLunité, voir le diagramme pour optimiser le Configuration des commutateurs DIPConfiguration suite Connecter le starter automatique du générateur Facultatif Connecter la commande à distance FacultatifDéterminez la tension totale nécessaire Choix de batterieChoisir le type de batterie ExempleConnexion en série Connexion de batterieCourant dentrée CA de lalternateur Connexion entrée/sortie CADépannage EntretienNuméros didentification de conformité aux règlements Garantie limitée      ÑîäåðæàíèåÕðàíèòå ÝÒÓ Èíñòðóêöèþ Âàæíûå óêàçàíèÿ ïî òåõíèêå áåçîïàñíîñòè11 Îõëàæäàþùèå âåíòèëÿòîðû, ðåãóëèðóåìûå ñ ïîìîùüþ Îïèñàíèå ôóíêöèéÍåèñïðàâíîñòü Ñâåòÿùàÿñÿ ëàìïà ÝêñïëóàòàöèÿÍàñòðîéêà Íàïðÿæåíèå Ïîëîæåíèå äæàìïåðà Íàñòðîéêà ïðîäîëæåíèåÒèï áàòàðåé îëîæåíèå äæàìïåðà 12 Âûáîð òèïà áàòàðåé  ÍåîáõîäèìûéÏîäêëþ÷åíèå óäàëåííîãî óïðàâëåíèÿ  Îïöèîíàëüíîå ØÀà 3 Îïðåäåëèòå ïîòðåáíóþ åìêîñòü áàòàðåé Âûáîð áàòàðåéØÀà 1 Îïðåäåëèòå ñóììàðíóþ ïîòðåáíóþ ìîùíîñòü ØÀà 2 Îïðåäåëèòå ïîòðåáíóþ ñèëó ïîñòîÿííîãî òîêà áàòàðåéÎïöèîíàëüíîå ïîäêëþ÷åíèå òîëüêî äëÿ òðàíñïîðòíûõ ïðèìåíåíèé Ïîäêëþ÷åíèå áàòàðåéÏîäêëþ÷åíèå Ïðîâîäêó Ïîñòîÿííîãî     Ïîäêëþ÷åíèå âõîäà è íàãðóçêè ïåðåìåííîãî òîêàÏîèñê è óñòðàíåíèå íåèñïðàâíîñòåé ÎáñëóæèâàíèåÇàìå÷àíèå ïî ìàðêèðîâêå Òåõíè÷åñêèå õàðàêòåðèñòèêè è ãàðàíòèÿ