| Application Example |
|
|
|
|
Add the | Use the following instructions to add a master device (the selected controller board) | ||
Controller Board to your configuration project. |
| ||
|
|
|
|
Step | Action |
| Comment |
|
|
| |
1 | To create a new project, choose New from the | A new project window appears. Default project | |
| File menu. |
| components are already in the project view. |
|
|
| |
2 | In the project window, select | A selection box appears around the Controller Board | |
| Controller Board icon. | icon. | |
|
|
| |
3 | The Select Controller Board dialogue box appears. | ||
| and |
| |
|
|
| |
4 | From the Available Types list, select your | In this case, select the IBS/4K. | |
| controller board. |
| |
|
|
|
|
Adding the |
|
| |
If you have Schneider’s device database (Schneider_Device_DB), you can import it | |||
Island Slave | into CMD. The following instructions are for manually creating a new configuration- | ||
|
| specific device when a configured one is not available: | |
|
|
|
|
Step | Action |
| Comment |
|
|
| |
1 | In your configuration, | The Insert Device Description dialogue box appears. | |
| Board icon, scroll down, and |
| |
|
|
| |
2 | In the ID Code field, enter the ID code for your island. | Use 51 (33h) for the ID code data type of the sample | |
|
|
| island. |
|
|
| |
3 | In the Process Data Channel field, enter your island’s | The sample island assembly’s input data length is 80 | |
| process data length. | bits and the output data length is 64 bits (including the | |
|
|
| control and status words). |
|
|
| |
4 | At Device Type, select Remote Bus Device. | The Advantys island is always configured as a remote | |
|
|
| bus device. |
|
|
| |
5 | In the Station Name field, enter a station name for | Choose your own station name for the Advantys | |
| your island node. | island. | |
|
|
| |
6 | In the Device Name field, enter a name for your | Choose your own device name for the Advantys | |
| island node. |
| island. |
|
|
| |
7 | In the Manufacturer Name field, enter a name for | Enter Schneider for the manufacturer name. | |
| your island node. |
| |
|
|
| |
8 | In the Device Type field, enter a name for your | Enter a device type that you feel describes the nature | |
| island node. |
| of the Advantys island. I/O will suffice. |
|
|
|
|
Saving and |
|
| |
You can save your configuration with the standard Windows commands in the | |||
Downloading the | File menu. The Online menu provides options for downloading and debugging | ||
Configuration | your configuration. |
| |
|
|
|
|
890USE19600 April 2004 | 51 |