The STB NIB 1010 Basic NIM Module

Selecting a Source Power Supply for the Island’s Logic Power Bus

Logic Power

 

An external 24 VDC power supply is needed as the source for logic power to the

Requirements

 

island bus. The external power supply connects to the island’s NIM. This external

 

 

supply provides the 24 V input to the built-in 5 V power supply in the NIM.

Characteristics

 

 

 

The external power supply needs to deliver 24 VDC source power to the island. The

of the External

 

supply that you select can have a low range limit of 19.2 VDC and a high range limit

Power Supply

 

of 30 VDC. The external supply must be rated safety extra low voltage (SELV-rated).

 

 

The SELV-rating means that SELV isolation is provided between the power supply’s

 

 

inputs and outputs, the power bus, and the devices connected to the island bus.

 

 

Under normal or single-fault conditions the voltage between any two accessible

 

 

parts, or between an accessible part and the protective earth (PE) terminal for Class

 

 

1 equipment, will not exceed a safe value (60 VDC max.).

 

 

 

CAUTION

 

 

 

IMPROPER GALVANIC ISOLATION

 

The power components are not galvanically isolated. They are intended for use only

 

in systems designed to provide SELV isolation between the supply inputs or outputs

 

and the load devices or system power bus. You must use SELV-rated supplies to

 

provide 24 VDC source power to the island.

 

Failure to follow this precaution can result in injury or equipment damage.

 

 

 

Calculating the

 

 

 

 

Wattage

 

The external supply needs to provide 13 W of power to the NIM.

Requirement

 

 

Suggested

 

 

 

The external power supply is generally enclosed in the same cabinet as the island.

Devices

 

Usually the external power supply is a DIN rail-mountable unit.

 

 

For installations that require 72 W or less from a 24 VDC source power supply, we

 

 

recommend a device such as the ABL7 RE2403 Phaseo power supply from

 

 

Telemecanique, distributed in the United States by Square D. This supply is DIN rail-

 

 

mountable and has a form factor similar to that of the island modules.

 

 

If you have room in your cabinet and your 24 VDC power requirements are greater

 

 

than 72 W, summable power supply options such as Schneider’s Premium

 

 

TSX SUP 1011 (26 W), TSX SUP 1021 (53 W), TSX SUP 1051 (120 W), or

 

 

TSX SUP 1101 (240 W) can be considered. These modules are also available from

 

 

Telemecanique and, in the United States, from Square D.

 

 

 

890USE19600 April 2004

27

Image 27
Contents 890USE19600 Version Advantys STBPage Table of Contents Application Example Safety Information ProcedureImportant Information Safety Information Construed as a commitment by Schneider Electric About the BookAt a Glance Validity NoteAbout the Book Introduction Summary What’s in this Chapter?Topic Basic What Is Advantys STB?Introduction Island Bus I/OWhat Is a Network Interface Module? Structural About Interbus Outputs in 4 msComponents of a simplified Interbus network are shown below Topology Physical LayerOn the shift register ring on which data is circulated NodeAddressing Input and output data in the masters bufferIntroduction Chapter? Product specifications of the basic Interbus NIMSTB NIB Basic NIM Module What’s in thisHardware External Features of the STB NIB 1010 NIMFeatures Called out in the illustration below Feature FunctionSpace reserved for the network connectors NIM housing Connections STB NIB 1010 Fieldbus InterfaceSummary Fieldbus PortCable ConnectorsInterbus NetworkingIndications LED Physical DescriptionOverview GeneralLEDs NIM ActivityDescription Power Supply InterfaceIsland is the two-receptacle connector illustrated below PhysicalRight Use eitherImproper Galvanic Isolation Logic PowerExternal CharacteristicsPower Supply RequirementsTechnical Specifications STB NIB 1010 Module SpecificationsConfiguring the Island Bus Bus Address Basic island configurationAuto-Addressing About the IslandModule Physical Location Island Bus Address An ExampleAuto-Configuration ConfigurationAbout Auto Stage Been successfully configured at least onceRST Button Hinged coverHeartbeat Island Fallback ScenariosFallback ScenariosIntroduction What’s in this Chapter? Fieldbus Communications SupportData Type Interbus ID CodeLow High BytesData Length Objects Data ExchangeData and Status ObjectsBoundaries InternalProcess Image WordContains the NIM status Output DataInput Data ExchangeWith an Advantys STB NIB 1010 basic NIM Application ExampleSample Island Sample Island AssemblyAssembly Fieldbus networkModel Module Type Island Bus Address I/O modules have the following island bus addressesDevices on an Interbus network Network Configuration ConsiderationsFor use with an Advantys STB island ConnectionConsiderations Before YouBegin SyConStep Action Comment Using SyCon to Configure an STB Island on InterbusWith SyCon Stage DescriptionWorkspace To add the NIM to the network configurationConfiguring Add the NIMInstructions Create an EDSSaving Using CMD to Configure an STB Island on Interbus Island slave to your configuration using CMDCMD Downloading AddAdding Island SlaveApplication Example Glossary BOS ARPCRC CanCOB ComsEIA DhcpDIN EDSFedp EMCEMI EOSGSD FsdpIEC type 1 input BaseScanning IECInput response Industrial I/OInput filtering Input polarityNema Energized and open when the coil is energizedEnergized and closed when the coil is energized ContactNMT NIMPDM PDOPLC Profibus DP Process I/OProducer Consumer modelSDO RTDSAP ScadaSnmp SmmpsStdp TCPTFE Voltage group UDPVaristor Suppress transient voltage surgesIndex Interbus Heartbeat message, 34 housing ID codeIndex