Schneider Electric 66124, 66123 user manual UPS status zone Essential information

Page 28

6.2.1.4 "UPS status" zone: Essential information

"Active sources": (available on parallel or modular UPS) X UPS + Y redundant + Z PSM:

X indicates the minimal number of UPS necessary to power the load,

Y indicates the number of UPS in redundancy.

Z indicate the number of UPS in PSM (Power Saving Mode)

An alarm can be generated if the number of UPS in redundancy is less than a configurable threshold. See UPS modules section.

"Power source": indicates whether the power comes from the AC normal input or from the UPS battery

"Output load level": indicates the power percentage used at UPS output "Output" indicates if the UPS output is powered

The various icons showing the status of the UPS outputs are:

Output powered

Output not powereded

Battery Information :

"Battery load level": battery charge level in percent

The information is completed with the two following labels:

Charging” : if the utility power is present and the battery charge is in progress

Discharging”: if the UPS operates on battery.

Fault”: if the battery is faulty.

"Remaining backup time": Estimation of the battery's maximum backup time remaining before UPS shutdown

"Battery status": Result of the last automatic battery test carried out by the UPS Possible values are:

OK: the test was completed correctly

NOK: the battery needs to be checked

Deactivated: the automatic battery test is not validated on the UPS

Network Management Card & Modbus/Jbus

34022321XT indice :AE

Page 28/98

Network Management Teleservice Card

 

 

APC by Schneider Electric

www.apc.com

Image 28
Contents Page Contents Notification Installation MGE MIBMGE Galaxy 7000 Network Management card presentation Connecting the UPS to the Ethernet network Protection of the computers / serversSupervision of the UPSs over the network Teleservice for Nmtc Direct sending of E-mailSending text messages SMS Environment Sensor optionTechnical data Hardware characteristicsConfiguration EMC CompatibilityAdministration NetworkEnvironment sensor MIB Management Information BaseModbus/Jbus for Inmc Default parameters BOOTP/DHCPMgeups 1UPS/NMTC+ 9 UPS/INMCUnpacking and check on contents Installation Network Management Card & Modbus/Jbus InmcIndications Installation in the UPS Sensor installation optionLED ACTInstallation Network Management Teleservice Card Nmtc Installation in the UPS Line Phone Port Configure IP parameters ConfigurationNmtc Inmc Your network is equipped with a Dhcp server Test after configuration Your network is not equipped with a Dhcp serverSupervision and administration by browser Optimising the performance of your browserUPS UPS propertiesUPS zone general information on the UPS Page Page Page Power Saving Mode representation Efficiency Booster Mode UPS measurements UPS status zone Essential information Viewing the alarms Viewing the About your UPS window On-line help Shutdown parameters Shutdonw criteria are describe below Measurements Event log Click on Event Log in the menuSystem log Click on System log. in the menuNotification Email NotificationPage Mail Message Settings SenderConfiguration Network settings Page System Notified Applications Page Central shutdown configuration TLS Access controlTLSRSAWITH512MD5 Page Date and time Firmware upload Characteristics Environment Status Environment Settings Page 4 Log Server protection Set-up of the shutdown parametersShutdown criteria managed by the Network Management Card Shutdown when backup time is less than Shutdown durationTeleservice procedure TeleserviceGeneral overview Page Configuration via RS232 Choice 1 Restart / ResetChoice 1 Read Network settings Choice 2 Network ConfigurationChoice 2 Modify Network settings Choice 3 Set Ethernet speed Choice 3 Lost password / Set Login Password to DefaultMGE UPS Systems Network Management Card Choice 4 Return to Default Configuration Installation Modbus/Jbus installation & use10.1.1 RS232 link configuration and connection 10.1.2 RS485 link configuration and connection 10.1.2.1 RS485 connectionPage 10.1.2.2 RS485 link configuration for 2 wires connexion Page 10.1.2.3 RS485 link configuration for 4 wires connexion Page Configuration of the JBUS/MODBUS communication parameters Choice 1 Display Jbus settings Choice 2 Modify Jbus settingsChoice 3 Display Jbus diagnostics Choice 4 Reset Jbus diagnosticsChoice 5 Return to Jbus Default Configuration Choice 6 Display Jbus framesAdditional Web pages Modbus register map Detailled status tableINMC/NMTC SSCMeasurement table Environnement Sensor .3.3.1 Sensor Status table Sensor Measurements tableSensor customisation table RO Examples of Modbus register map Global overviewUPS on AC Normal input Main UPS statusUPS on Battery Word + Bit Main UPS statusLow Battery Warning UPS on Bypass due to End of battery runtime UPS on Bypass due to manual order UPS on Manual Bypass UPS running Power Saving Mode Communication lost Modbus Status Address Value Word + Bit Main UPS statusTable of alarms and UPS events Tables of alarms and eventsAppendices UPS OK Table of system alarms Snmp objects MGE MIBPage Page Table des Traps MIB TrapGlossary IsxcMIB Management Information Base Network Management ProxyReboot NMS Network Management Station SnmpNSM Network Shutdown Module RFC