6.2.1.4 "UPS status" zone: Essential information
"Active sources": (available on parallel or modular UPS) X UPS + Y redundant + Z PSM:
X indicates the minimal number of UPS necessary to power the load,
Y indicates the number of UPS in redundancy.
Z indicate the number of UPS in PSM (Power Saving Mode)
An alarm can be generated if the number of UPS in redundancy is less than a configurable threshold. See UPS modules section.
"Power source": indicates whether the power comes from the AC normal input or from the UPS battery
"Output load level": indicates the power percentage used at UPS output "Output" indicates if the UPS output is powered
The various icons showing the status of the UPS outputs are:
Output powered
Output not powereded
Battery Information :
"Battery load level": battery charge level in percent
The information is completed with the two following labels:
“Charging” : if the utility power is present and the battery charge is in progress
“Discharging”: if the UPS operates on battery.
“Fault”: if the battery is faulty.
"Remaining backup time": Estimation of the battery's maximum backup time remaining before UPS shutdown
"Battery status": Result of the last automatic battery test carried out by the UPS Possible values are:
–OK: the test was completed correctly
–NOK: the battery needs to be checked
–Deactivated: the automatic battery test is not validated on the UPS