Schneider Electric 66124, 66123 Configuration of the JBUS/MODBUS communication parameters

Page 72

10.1.3 Configuration of the JBUS/MODBUS communication parameters

Connect the card to a computer equipped with a Hyper terminal type emulator. The serial link must be set at 9600 baud, 8 bits, no parity, 1 stop bit, and without flow control.

Check that UPS power is on.

Enter the MGEUPS or mgeups password (non modifiable).

The next menu appears:

-----------------------------------------------------------------------------

MGE UPS SYSTEMS

NETWORK MANAGEMENT CARD

-----------------------------------------------------------------------------

1 : Reset

2 : Network configuration

3 : Set Login Password to Default

4 : Return to Default Configuration

5 : Jbus configuration

6 : Sensor configuration

0 : Exit

-----------------------------------------------------------------------------

Type 5 and return to display the JBUS configuration menu.

The next menu appears:

-----------------------------------------------------------------------------

Jbus settings

-----------------------------------------------------------------------------

1 : Display Jbus settings

2 : Modify Jbus settings

3 : Display Jbus diagnostics

4 : Reset Jbus diagnostics

5 : Return to Jbus Default Configuration

6 : Display Jbus frames

0 : Exit

-----------------------------------------------------------------------------

Network Management Card & Modbus/Jbus

34022321XT indice :AE

Page 72/98

Network Management Teleservice Card

 

 

APC by Schneider Electric

www.apc.com

Image 72
Contents Page Contents Notification Installation MGE MIBMGE Galaxy 7000 Network Management card presentation Connecting the UPS to the Ethernet network Protection of the computers / serversSupervision of the UPSs over the network Teleservice for Nmtc Direct sending of E-mailSending text messages SMS Environment Sensor optionTechnical data Hardware characteristicsConfiguration EMC CompatibilityAdministration NetworkEnvironment sensor MIB Management Information BaseModbus/Jbus for Inmc Default parameters BOOTP/DHCPMgeups 1UPS/NMTC+ 9 UPS/INMCInstallation Network Management Card & Modbus/Jbus Inmc Unpacking and check on contentsIndications Installation in the UPS Sensor installation optionLED ACTInstallation Network Management Teleservice Card Nmtc Installation in the UPS Line Phone Port Configuration Configure IP parametersNmtc Inmc Your network is equipped with a Dhcp server Test after configuration Your network is not equipped with a Dhcp serverSupervision and administration by browser Optimising the performance of your browserUPS UPS propertiesUPS zone general information on the UPS Page Page Page Power Saving Mode representation Efficiency Booster Mode UPS measurements UPS status zone Essential information Viewing the alarms Viewing the About your UPS window On-line help Shutdown parameters Shutdonw criteria are describe below Measurements Event log Click on Event Log in the menuSystem log Click on System log. in the menuNotification Email NotificationPage Mail Message Settings SenderConfiguration Network settings Page System Notified Applications Page Central shutdown configuration Access control TLSTLSRSAWITH512MD5 Page Date and time Firmware upload Characteristics Environment Status Environment Settings Page 4 Log Server protection Set-up of the shutdown parametersShutdown criteria managed by the Network Management Card Shutdown when backup time is less than Shutdown durationTeleservice Teleservice procedureGeneral overview Page Configuration via RS232 Choice 1 Restart / ResetChoice 2 Network Configuration Choice 1 Read Network settingsChoice 2 Modify Network settings Choice 3 Lost password / Set Login Password to Default Choice 3 Set Ethernet speedMGE UPS Systems Network Management Card Choice 4 Return to Default Configuration Modbus/Jbus installation & use Installation10.1.1 RS232 link configuration and connection 10.1.2 RS485 link configuration and connection 10.1.2.1 RS485 connectionPage 10.1.2.2 RS485 link configuration for 2 wires connexion Page 10.1.2.3 RS485 link configuration for 4 wires connexion Page Configuration of the JBUS/MODBUS communication parameters Choice 1 Display Jbus settings Choice 2 Modify Jbus settingsChoice 3 Display Jbus diagnostics Choice 4 Reset Jbus diagnosticsChoice 5 Return to Jbus Default Configuration Choice 6 Display Jbus framesAdditional Web pages Modbus register map Detailled status tableINMC/NMTC SSCMeasurement table Environnement Sensor .3.3.1 Sensor Status table Sensor Measurements tableSensor customisation table RO Examples of Modbus register map Global overviewUPS on AC Normal input Main UPS statusUPS on Battery Word + Bit Main UPS statusLow Battery Warning UPS on Bypass due to End of battery runtime UPS on Bypass due to manual order UPS on Manual Bypass UPS running Power Saving Mode Communication lost Modbus Status Address Value Word + Bit Main UPS statusTables of alarms and events Table of alarms and UPS eventsAppendices UPS OK Table of system alarms Snmp objects MGE MIBPage Page Table des Traps MIB TrapGlossary IsxcMIB Management Information Base Network Management ProxyReboot NMS Network Management Station SnmpNSM Network Shutdown Module RFC