Schneider Electric 66123, 66124 Shutdown criteria managed by the Network Management Card

Page 57

7.2Shutdown criteria managed by the Network Management Card

During an extended power failure, three criteria may cause the server shutdown procedure to be initiated. If several criteria are selected, (See

page Shutdown parameters), the first criterion encountered will launch the shutdown procedure.

Utility failure

Start of the shutdown sequence

UPS may go

on bypass,

 

 

 

 

 

 

load is no more

 

Shutdown after :

 

protected

Battery

 

 

 

 

 

autonomy

 

 

 

ratio

Delay before

 

 

 

 

 

 

shutdown

 

 

100%

 

 

 

 

Remaining autonomy

 

 

 

If remaining time under

Shutdown if

Shutdown duration

 

remainig time

 

 

 

ratio under

 

 

 

0%

 

 

t

 

 

 

 

Card parameters

UPS parameters

7.2.1Backup time before initiating the shutdown procedure (Shutdown After - Shutdown Timer)

When the UPS switches to battery, the Network Management Card starts the Shutdown Timer countdown and launches the system shutdown procedure at the end of the countdown.

This value must be chosen so that users have time to complete their tasks and disconnect, without exceeding battery backup time.

Note 1:

The Network Shutdown Module can also manage its own Shutdown Timer (configurable in the Shutdown Module"set-up" menu of each Network Shutdown Module) launched when the UPS switches to battery.

Note that if this criterion is selected to initiate system shutdown, automatic system reboot when power is restored is not guaranteed (e.g. power restoration if only this system was shut down).

Network Management Card & Modbus/Jbus

34022321XT indice :AE

Page 57/98

Network Management Teleservice Card

 

 

APC by Schneider Electric

www.apc.com

Image 57
Contents Page Contents Notification MGE MIB InstallationMGE Galaxy 7000 Network Management card presentation Protection of the computers / servers Connecting the UPS to the Ethernet networkSupervision of the UPSs over the network Direct sending of E-mail Teleservice for NmtcSending text messages SMS Environment Sensor optionHardware characteristics Technical dataConfiguration EMC CompatibilityNetwork AdministrationEnvironment sensor MIB Management Information BaseModbus/Jbus for Inmc BOOTP/DHCP Default parametersMgeups 1UPS/NMTC+ 9 UPS/INMCInstallation Network Management Card & Modbus/Jbus Inmc Unpacking and check on contentsIndications Sensor installation option Installation in the UPSLED ACTInstallation Network Management Teleservice Card Nmtc Installation in the UPS Line Phone Port Configuration Configure IP parametersNmtc Inmc Your network is equipped with a Dhcp server Your network is not equipped with a Dhcp server Test after configurationOptimising the performance of your browser Supervision and administration by browserUPS UPS propertiesUPS zone general information on the UPS Page Page Page Power Saving Mode representation Efficiency Booster Mode UPS measurements UPS status zone Essential information Viewing the alarms Viewing the About your UPS window On-line help Shutdown parameters Shutdonw criteria are describe below Measurements Click on Event Log in the menu Event logClick on System log. in the menu System logEmail Notification NotificationPage Sender Mail Message SettingsConfiguration Network settings Page System Notified Applications Page Central shutdown configuration Access control TLSTLSRSAWITH512MD5 Page Date and time Firmware upload Characteristics Environment Status Environment Settings Page 4 Log Set-up of the shutdown parameters Server protectionShutdown criteria managed by the Network Management Card Shutdown duration Shutdown when backup time is less thanTeleservice Teleservice procedureGeneral overview Page Choice 1 Restart / Reset Configuration via RS232Choice 2 Network Configuration Choice 1 Read Network settingsChoice 2 Modify Network settings Choice 3 Lost password / Set Login Password to Default Choice 3 Set Ethernet speedMGE UPS Systems Network Management Card Choice 4 Return to Default Configuration Modbus/Jbus installation & use Installation10.1.1 RS232 link configuration and connection 10.1.2.1 RS485 connection 10.1.2 RS485 link configuration and connectionPage 10.1.2.2 RS485 link configuration for 2 wires connexion Page 10.1.2.3 RS485 link configuration for 4 wires connexion Page Configuration of the JBUS/MODBUS communication parameters Choice 2 Modify Jbus settings Choice 1 Display Jbus settingsChoice 3 Display Jbus diagnostics Choice 4 Reset Jbus diagnosticsChoice 6 Display Jbus frames Choice 5 Return to Jbus Default ConfigurationAdditional Web pages Detailled status table Modbus register mapSSC INMC/NMTCMeasurement table Sensor Measurements table Environnement Sensor .3.3.1 Sensor Status tableSensor customisation table RO Global overview Examples of Modbus register mapMain UPS status UPS on AC Normal inputWord + Bit Main UPS status UPS on BatteryLow Battery Warning UPS on Bypass due to End of battery runtime UPS on Bypass due to manual order UPS on Manual Bypass UPS running Power Saving Mode Modbus Status Address Value Word + Bit Main UPS status Communication lostTables of alarms and events Table of alarms and UPS eventsAppendices UPS OK Table of system alarms MGE MIB Snmp objectsPage Page MIB Trap Table des TrapsIsxc GlossaryMIB Management Information Base Network Management ProxyNMS Network Management Station Snmp RebootNSM Network Shutdown Module RFC