
7.2Shutdown criteria managed by the Network Management Card
During an extended power failure, three criteria may cause the server shutdown procedure to be initiated. If several criteria are selected, (See
page Shutdown parameters), the first criterion encountered will launch the shutdown procedure.
Utility failure | Start of the shutdown sequence | UPS may go | ||
on bypass, | ||||
|
|
| ||
|
|
| load is no more | |
| Shutdown after : |
| protected | |
Battery |
|
| ||
|
|
| ||
autonomy |
|
|
| |
ratio | Delay before |
|
| |
|
|
| ||
| shutdown |
|
| |
100% |
|
|
| |
| Remaining autonomy |
|
| |
| If remaining time under | |||
Shutdown if | Shutdown duration |
| ||
remainig time |
|
|
| |
ratio under |
|
|
| |
0% |
|
| t | |
|
|
| ||
| Card parameters | UPS parameters |
7.2.1Backup time before initiating the shutdown procedure (Shutdown After - Shutdown Timer)
When the UPS switches to battery, the Network Management Card starts the Shutdown Timer countdown and launches the system shutdown procedure at the end of the countdown.
This value must be chosen so that users have time to complete their tasks and disconnect, without exceeding battery backup time.
Note 1:
The Network Shutdown Module can also manage its own Shutdown Timer (configurable in the Shutdown
Note that if this criterion is selected to initiate system shutdown, automatic system reboot when power is restored is not guaranteed (e.g. power restoration if only this system was shut down).
Network Management Card & Modbus/Jbus | 34022321XT indice :AE | Page 57/98 |
Network Management Teleservice Card |
|
|
APC by Schneider Electric
www.apc.com