Schneider Electric 66123, 66124 user manual UPS on Manual Bypass

Page 87

10.3.4.7 UPS on Manual Bypass

 

 

 

 

Modbus

 

 

 

 

Status

 

 

Address

Value

 

 

 

 

 

 

(word +

 

 

 

 

 

 

 

bit)

 

 

 

 

Main UPS status

 

 

 

 

 

 

 

Load Powered

 

400

1

 

 

 

Load on inverter

 

401

0

 

 

 

UPS on battery

 

404

0

 

 

 

Load on AC Bypass

 

407

0

 

 

 

UPS in maintenance position

 

461

1

 

 

 

Battery Charging

 

493

1

 

 

 

UPS in Power Saving Mode

 

 

41B

0

 

 

 

Nota: Available with NMC fw 808 and G7000 package AM

 

 

 

 

 

 

 

 

 

 

 

 

Breaker status

 

 

 

 

 

 

 

Q5N circuit breaker

 

 

47B

0

 

 

 

Q1 circuit breaker

 

443

1

 

 

 

Q4S circuit breaker

 

 

46E

1

 

 

 

QF1 circuit breaker

 

 

42F

1

 

 

 

Q3BP circuit breaker

 

416

1

 

Q3BP closed + Q5N open

 

UPS Fault

 

 

 

 

 

 

 

UPS general alarm - Red Led from UPS HMI

 

402

1

 

 

 

Nota: Available with NMC fw 808 and G7000 package AN

 

 

 

 

 

 

 

Load not protected

 

 

41A

1

 

 

 

UPS Internal Communication Fault

 

409

0

 

 

 

Rectifier fault

 

419

0

 

 

 

Rectifier (PFC) fuse fault

 

449

0

 

 

 

Battery temperature fault

 

 

42A

0

 

 

 

End of battery runtime

 

406

0

 

 

 

Emergency Power Off

 

 

40B

0

 

 

 

Fan Faillure

 

 

40E

0

 

 

 

UPS Warning

 

 

 

 

 

 

 

Orange Led from UPS HMI

 

 

41C

0

 

 

 

Nota: Available with NMC fw 808 and G7000 package AN

 

 

 

 

 

 

 

Overload

 

 

40A

0

 

 

 

Low Battery Warning

 

405

0

 

 

 

Inverter Overload

 

 

4C2

0

 

 

 

Static switch overload

 

465

0

 

 

 

AC Normal Frequency Out Of Tolerance

 

 

44B

0

 

 

 

AC Normal Voltage Out Of Tolerance

 

448

0

 

 

 

AC bypass Out of tolerance

 

467

0

 

 

Network Management Card & Modbus/Jbus

34022321XT indice :AE

Page 87/98

Network Management Teleservice Card

 

 

APC by Schneider Electric

www.apc.com

Image 87
Contents Page Contents Notification MGE MIB InstallationMGE Galaxy 7000 Network Management card presentation Protection of the computers / servers Connecting the UPS to the Ethernet networkSupervision of the UPSs over the network Environment Sensor option Teleservice for NmtcDirect sending of E-mail Sending text messages SMSEMC Compatibility Technical dataHardware characteristics ConfigurationMIB Management Information Base AdministrationNetwork Environment sensorModbus/Jbus for Inmc 1UPS/NMTC+ 9 UPS/INMC Default parametersBOOTP/DHCP MgeupsInstallation Network Management Card & Modbus/Jbus Inmc Unpacking and check on contentsIndications ACT Installation in the UPSSensor installation option LEDInstallation Network Management Teleservice Card Nmtc Installation in the UPS Line Phone Port Configuration Configure IP parametersNmtc Inmc Your network is equipped with a Dhcp server Your network is not equipped with a Dhcp server Test after configurationUPS properties Supervision and administration by browserOptimising the performance of your browser UPSUPS zone general information on the UPS Page Page Page Power Saving Mode representation Efficiency Booster Mode UPS measurements UPS status zone Essential information Viewing the alarms Viewing the About your UPS window On-line help Shutdown parameters Shutdonw criteria are describe below Measurements Click on Event Log in the menu Event logClick on System log. in the menu System logEmail Notification NotificationPage Sender Mail Message SettingsConfiguration Network settings Page System Notified Applications Page Central shutdown configuration Access control TLSTLSRSAWITH512MD5 Page Date and time Firmware upload Characteristics Environment Status Environment Settings Page 4 Log Set-up of the shutdown parameters Server protectionShutdown criteria managed by the Network Management Card Shutdown duration Shutdown when backup time is less thanTeleservice Teleservice procedureGeneral overview Page Choice 1 Restart / Reset Configuration via RS232Choice 2 Network Configuration Choice 1 Read Network settingsChoice 2 Modify Network settings Choice 3 Lost password / Set Login Password to Default Choice 3 Set Ethernet speedMGE UPS Systems Network Management Card Choice 4 Return to Default Configuration Modbus/Jbus installation & use Installation10.1.1 RS232 link configuration and connection 10.1.2.1 RS485 connection 10.1.2 RS485 link configuration and connectionPage 10.1.2.2 RS485 link configuration for 2 wires connexion Page 10.1.2.3 RS485 link configuration for 4 wires connexion Page Configuration of the JBUS/MODBUS communication parameters Choice 4 Reset Jbus diagnostics Choice 1 Display Jbus settingsChoice 2 Modify Jbus settings Choice 3 Display Jbus diagnosticsChoice 6 Display Jbus frames Choice 5 Return to Jbus Default ConfigurationAdditional Web pages Detailled status table Modbus register mapSSC INMC/NMTCMeasurement table Sensor Measurements table Environnement Sensor .3.3.1 Sensor Status tableSensor customisation table RO Global overview Examples of Modbus register mapMain UPS status UPS on AC Normal inputWord + Bit Main UPS status UPS on Battery Low Battery Warning UPS on Bypass due to End of battery runtime UPS on Bypass due to manual order UPS on Manual Bypass UPS running Power Saving Mode Modbus Status Address Value Word + Bit Main UPS status Communication lostTables of alarms and events Table of alarms and UPS eventsAppendices UPS OK Table of system alarms MGE MIB Snmp objectsPage Page MIB Trap Table des TrapsNetwork Management Proxy GlossaryIsxc MIB Management Information BaseRFC RebootNMS Network Management Station Snmp NSM Network Shutdown Module