Schneider Electric 66124, 66123 user manual UPS on Bypass due to manual order

Page 86

10.3.4.6 UPS on Bypass due to manual order

 

 

 

 

Modbus

 

 

 

 

Status

 

 

Address

Value

 

 

 

 

 

 

(word +

 

 

 

 

 

 

 

bit)

 

 

 

 

Main UPS status

 

 

 

 

 

 

 

Load Powered

 

400

1

 

 

 

Load on inverter

 

401

0

 

 

 

UPS on battery

 

404

0

 

 

 

Load on AC Bypass

 

407

1

 

 

 

UPS in maintenance position

 

461

0

 

 

 

Battery Charging

 

493

1

 

 

 

UPS in Power Saving Mode

 

 

41B

0

 

 

 

Nota: Available with NMC fw 808 and G7000 package AM

 

 

 

 

 

 

 

 

 

 

 

 

Breaker status

 

 

 

 

 

 

 

Q5N circuit breaker

 

 

47B

1

 

 

 

Q1 circuit breaker

 

443

1

 

 

 

Q4S circuit breaker

 

 

46E

1

 

 

 

QF1 circuit breaker

 

 

42F

1

 

 

 

Q3BP circuit breaker

 

416

0

 

 

 

UPS Fault

 

 

 

 

 

 

 

UPS general alarm - Red Led from UPS HMI

 

402

1

 

 

 

Nota: Available with NMC fw 808 and G7000 package AN

 

 

 

 

 

 

 

Load not protected

 

 

41A

1

 

 

 

UPS Internal Communication Fault

 

409

0

 

 

 

Rectifier fault

 

419

0

 

 

 

Rectifier (PFC) fuse fault

 

449

0

 

 

 

Battery temperature fault

 

 

42A

0

 

 

 

End of battery runtime

 

406

0

 

 

 

Emergency Power Off

 

 

40B

0

 

 

 

Fan Faillure

 

 

40E

0

 

 

 

UPS Warning

 

 

 

 

 

 

 

Orange Led from UPS HMI

 

 

41C

0

 

 

 

Nota: Available with NMC fw 808 and G7000 package AN

 

 

 

 

 

 

 

Overload

 

 

40A

0

 

 

 

Low Battery Warning

 

405

0

 

 

 

Inverter Overload

 

 

4C2

0

 

 

 

Static switch overload

 

465

0

 

 

 

AC Normal Frequency Out Of Tolerance

 

 

44B

0

 

 

 

AC Normal Voltage Out Of Tolerance

 

448

0

 

 

 

AC bypass Out of tolerance

 

467

0

 

 

Network Management Card & Modbus/Jbus

34022321XT indice :AE

Page 86/98

Network Management Teleservice Card

 

 

APC by Schneider Electric

www.apc.com

Image 86
Contents Page Contents Notification Installation MGE MIBMGE Galaxy 7000 Network Management card presentation Connecting the UPS to the Ethernet network Protection of the computers / serversSupervision of the UPSs over the network Sending text messages SMS Teleservice for NmtcDirect sending of E-mail Environment Sensor optionConfiguration Technical dataHardware characteristics EMC CompatibilityEnvironment sensor AdministrationNetwork MIB Management Information BaseModbus/Jbus for Inmc Mgeups Default parametersBOOTP/DHCP 1UPS/NMTC+ 9 UPS/INMCIndications Installation Network Management Card & Modbus/Jbus InmcUnpacking and check on contents LED Installation in the UPSSensor installation option ACTInstallation Network Management Teleservice Card Nmtc Installation in the UPS Line Phone Port Nmtc Inmc ConfigurationConfigure IP parameters Your network is equipped with a Dhcp server Test after configuration Your network is not equipped with a Dhcp serverUPS Supervision and administration by browserOptimising the performance of your browser UPS propertiesUPS zone general information on the UPS Page Page Page Power Saving Mode representation Efficiency Booster Mode UPS measurements UPS status zone Essential information Viewing the alarms Viewing the About your UPS window On-line help Shutdown parameters Shutdonw criteria are describe below Measurements Event log Click on Event Log in the menuSystem log Click on System log. in the menuNotification Email NotificationPage Mail Message Settings SenderConfiguration Network settings Page System Notified Applications Page Central shutdown configuration TLSRSAWITH512MD5 Access controlTLS Page Date and time Firmware upload Characteristics Environment Status Environment Settings Page 4 Log Server protection Set-up of the shutdown parametersShutdown criteria managed by the Network Management Card Shutdown when backup time is less than Shutdown durationGeneral overview TeleserviceTeleservice procedure Page Configuration via RS232 Choice 1 Restart / ResetChoice 2 Modify Network settings Choice 2 Network ConfigurationChoice 1 Read Network settings MGE UPS Systems Network Management Card Choice 3 Lost password / Set Login Password to DefaultChoice 3 Set Ethernet speed Choice 4 Return to Default Configuration 10.1.1 RS232 link configuration and connection Modbus/Jbus installation & useInstallation 10.1.2 RS485 link configuration and connection 10.1.2.1 RS485 connectionPage 10.1.2.2 RS485 link configuration for 2 wires connexion Page 10.1.2.3 RS485 link configuration for 4 wires connexion Page Configuration of the JBUS/MODBUS communication parameters Choice 3 Display Jbus diagnostics Choice 1 Display Jbus settingsChoice 2 Modify Jbus settings Choice 4 Reset Jbus diagnosticsChoice 5 Return to Jbus Default Configuration Choice 6 Display Jbus framesAdditional Web pages Modbus register map Detailled status tableINMC/NMTC SSCMeasurement table Environnement Sensor .3.3.1 Sensor Status table Sensor Measurements tableSensor customisation table RO Examples of Modbus register map Global overviewUPS on AC Normal input Main UPS statusUPS on Battery Word + Bit Main UPS statusLow Battery Warning UPS on Bypass due to End of battery runtime UPS on Bypass due to manual order UPS on Manual Bypass UPS running Power Saving Mode Communication lost Modbus Status Address Value Word + Bit Main UPS statusAppendices Tables of alarms and eventsTable of alarms and UPS events UPS OK Table of system alarms Snmp objects MGE MIBPage Page Table des Traps MIB TrapMIB Management Information Base GlossaryIsxc Network Management ProxyNSM Network Shutdown Module RebootNMS Network Management Station Snmp RFC