Schneider Electric 66123, 66124 user manual UPS on Bypass due to End of battery runtime

Page 85

10.3.4.5 UPS on Bypass due to End of battery runtime

 

 

 

 

Modbus

 

 

 

 

Status

 

 

Address

Value

 

 

 

 

 

 

(word +

 

 

 

 

 

 

 

bit)

 

 

 

 

Main UPS status

 

 

 

 

 

 

 

Load Powered

 

400

1

 

 

 

Load on inverter

 

401

0

 

 

 

UPS on battery

 

404

0

 

 

 

Load on AC Bypass

 

407

1

 

 

 

UPS in maintenance position

 

461

0

 

 

 

Battery Charging

 

493

0

 

 

 

UPS in Power Saving Mode

 

 

41B

0

 

 

 

Nota: Available with NMC fw 808 and G7000 package AM

 

 

 

 

 

 

 

 

 

 

 

 

Breaker status

 

 

 

 

 

 

 

Q5N circuit breaker

 

 

47B

1

 

 

 

Q1 circuit breaker

 

443

1

 

 

 

Q4S circuit breaker

 

 

46E

1

 

 

 

QF1 circuit breaker

 

 

42F

1

 

 

 

Q3BP circuit breaker

 

416

0

 

 

 

UPS Fault

 

 

 

 

 

 

 

UPS general alarm - Red Led from UPS HMI

 

402

1

 

 

 

Nota: Available with NMC fw 808 and G7000 package AN

 

 

 

 

 

 

 

Load not protected

 

 

41A

1

 

 

 

UPS Internal Communication Fault

 

409

0

 

 

 

Rectifier fault

 

419

0

 

 

 

Rectifier (PFC) fuse fault

 

449

0

 

 

 

Battery temperature fault

 

 

42A

0

 

 

 

End of battery runtime

 

406

1

 

 

 

Emergency Power Off

 

 

40B

0

 

 

 

Fan Faillure

 

 

40E

0

 

 

 

UPS Warning

 

 

 

 

 

 

 

Orange Led from UPS HMI

 

 

41C

1

 

 

 

Nota: Available with NMC fw 808 and G7000 package AN

 

 

 

 

 

 

 

Overload

 

 

40A

0

 

 

 

Low battery WARNING

 

405

1

 

 

 

Inverter Overload

 

 

4C2

0

 

 

 

Static switch overload

 

465

0

 

 

 

AC Normal Frequency Out Of Tolerance

 

 

44B

1

 

 

 

AC Normal Voltage Out Of Tolerance

 

448

1

 

 

 

AC bypass Out of tolerance

 

467

0

 

 

Network Management Card & Modbus/Jbus

34022321XT indice :AE

Page 85/98

Network Management Teleservice Card

 

 

APC by Schneider Electric

www.apc.com

Image 85
Contents Page Contents Notification MGE MIB InstallationMGE Galaxy 7000 Network Management card presentation Protection of the computers / servers Connecting the UPS to the Ethernet networkSupervision of the UPSs over the network Direct sending of E-mail Teleservice for NmtcSending text messages SMS Environment Sensor optionHardware characteristics Technical dataConfiguration EMC CompatibilityNetwork AdministrationEnvironment sensor MIB Management Information BaseModbus/Jbus for Inmc BOOTP/DHCP Default parametersMgeups 1UPS/NMTC+ 9 UPS/INMCUnpacking and check on contents Installation Network Management Card & Modbus/Jbus InmcIndications Sensor installation option Installation in the UPSLED ACTInstallation Network Management Teleservice Card Nmtc Installation in the UPS Line Phone Port Configure IP parameters ConfigurationNmtc Inmc Your network is equipped with a Dhcp server Your network is not equipped with a Dhcp server Test after configurationOptimising the performance of your browser Supervision and administration by browserUPS UPS propertiesUPS zone general information on the UPS Page Page Page Power Saving Mode representation Efficiency Booster Mode UPS measurements UPS status zone Essential information Viewing the alarms Viewing the About your UPS window On-line help Shutdown parameters Shutdonw criteria are describe below Measurements Click on Event Log in the menu Event logClick on System log. in the menu System logEmail Notification NotificationPage Sender Mail Message SettingsConfiguration Network settings Page System Notified Applications Page Central shutdown configuration TLS Access controlTLSRSAWITH512MD5 Page Date and time Firmware upload Characteristics Environment Status Environment Settings Page 4 Log Set-up of the shutdown parameters Server protectionShutdown criteria managed by the Network Management Card Shutdown duration Shutdown when backup time is less thanTeleservice procedure TeleserviceGeneral overview Page Choice 1 Restart / Reset Configuration via RS232Choice 1 Read Network settings Choice 2 Network ConfigurationChoice 2 Modify Network settings Choice 3 Set Ethernet speed Choice 3 Lost password / Set Login Password to DefaultMGE UPS Systems Network Management Card Choice 4 Return to Default Configuration Installation Modbus/Jbus installation & use10.1.1 RS232 link configuration and connection 10.1.2.1 RS485 connection 10.1.2 RS485 link configuration and connectionPage 10.1.2.2 RS485 link configuration for 2 wires connexion Page 10.1.2.3 RS485 link configuration for 4 wires connexion Page Configuration of the JBUS/MODBUS communication parameters Choice 2 Modify Jbus settings Choice 1 Display Jbus settingsChoice 3 Display Jbus diagnostics Choice 4 Reset Jbus diagnosticsChoice 6 Display Jbus frames Choice 5 Return to Jbus Default ConfigurationAdditional Web pages Detailled status table Modbus register mapSSC INMC/NMTCMeasurement table Sensor Measurements table Environnement Sensor .3.3.1 Sensor Status tableSensor customisation table RO Global overview Examples of Modbus register mapMain UPS status UPS on AC Normal inputWord + Bit Main UPS status UPS on BatteryLow Battery Warning UPS on Bypass due to End of battery runtime UPS on Bypass due to manual order UPS on Manual Bypass UPS running Power Saving Mode Modbus Status Address Value Word + Bit Main UPS status Communication lostTable of alarms and UPS events Tables of alarms and eventsAppendices UPS OK Table of system alarms MGE MIB Snmp objectsPage Page MIB Trap Table des TrapsIsxc GlossaryMIB Management Information Base Network Management ProxyNMS Network Management Station Snmp RebootNSM Network Shutdown Module RFC