Schneider Electric 66123, 66124 user manual System

Page 43

6.4.2 System

Click on "System" in the menu.

This menu enables the customisation of the information on the UPS properties pages.

UPS Contact: This text field is limited to 49 characters. Enter the name of the person responsible for UPS administration at IT network level and/or electrical maintenance. This field does not appear on any other Web page. By default, its value is "Computer Room Manager".

UPS Location: Enter a description (limited to 49 characters) of the location of the UPS in your installation (e.g. Computer room E1-C066). This text is displayed in the home page. By default, its value is "Computer Room".

Default Language: Enables initialisation of the browser language at card connection.

Choice of one of the available languages: English, French, German, Spanish, Italian changes the language of the html interface pages (reboot the browser after modification).

History log interval: [from 5 to 99999 sec., 60 by default]. Measurement save period.

Environment log interval: [from 60 to 99999 sec., 300 by default]. Temperature and humidity measurement save period.

Reset Communication button: performs a remote reboot of the card without modifying the configuration. This action is compulsory for consideration of any changes made on the "Network Settings" page. Security of this operation is ensured by requesting Login and Password. Factory Reset button: enables restoration of the default configuration of all the card’s parameters. TCP/IP parameters: IP address, subnet mask, gateway and BootP/DHCP value are maintained if the "Keep TCP/IP parameters" option is selected. Security of this operation is ensured by requesting Login and Password. The default login and password are: MGEUPS

Export settings to file: Enables exportation ("Download" button) and saving of card configuration information.

Import settings from file: Enables selection of a configuration file ("Browse" button) and uploading ("Upload" button) of card configuration information.

Network Management Card & Modbus/Jbus

34022321XT indice :AE

Page 43/98

Network Management Teleservice Card

 

 

APC by Schneider Electric

www.apc.com

Image 43
Contents Page Contents Notification MGE MIB InstallationMGE Galaxy 7000 Network Management card presentation Protection of the computers / servers Connecting the UPS to the Ethernet networkSupervision of the UPSs over the network Environment Sensor option Teleservice for NmtcDirect sending of E-mail Sending text messages SMSEMC Compatibility Technical dataHardware characteristics ConfigurationMIB Management Information Base AdministrationNetwork Environment sensorModbus/Jbus for Inmc 1UPS/NMTC+ 9 UPS/INMC Default parametersBOOTP/DHCP MgeupsUnpacking and check on contents Installation Network Management Card & Modbus/Jbus InmcIndications ACT Installation in the UPSSensor installation option LEDInstallation Network Management Teleservice Card Nmtc Installation in the UPS Line Phone Port Configure IP parameters ConfigurationNmtc Inmc Your network is equipped with a Dhcp server Your network is not equipped with a Dhcp server Test after configurationUPS properties Supervision and administration by browserOptimising the performance of your browser UPSUPS zone general information on the UPS Page Page Page Power Saving Mode representation Efficiency Booster Mode UPS measurements UPS status zone Essential information Viewing the alarms Viewing the About your UPS window On-line help Shutdown parameters Shutdonw criteria are describe below Measurements Click on Event Log in the menu Event logClick on System log. in the menu System logEmail Notification NotificationPage Sender Mail Message Settings Configuration Network settings Page System Notified Applications Page Central shutdown configuration TLS Access controlTLSRSAWITH512MD5 Page Date and time Firmware upload Characteristics Environment Status Environment Settings Page 4 Log Set-up of the shutdown parameters Server protectionShutdown criteria managed by the Network Management Card Shutdown duration Shutdown when backup time is less thanTeleservice procedure TeleserviceGeneral overview Page Choice 1 Restart / Reset Configuration via RS232Choice 1 Read Network settings Choice 2 Network ConfigurationChoice 2 Modify Network settings Choice 3 Set Ethernet speed Choice 3 Lost password / Set Login Password to DefaultMGE UPS Systems Network Management Card Choice 4 Return to Default Configuration Installation Modbus/Jbus installation & use10.1.1 RS232 link configuration and connection 10.1.2.1 RS485 connection 10.1.2 RS485 link configuration and connectionPage 10.1.2.2 RS485 link configuration for 2 wires connexion Page 10.1.2.3 RS485 link configuration for 4 wires connexion Page Configuration of the JBUS/MODBUS communication parameters Choice 4 Reset Jbus diagnostics Choice 1 Display Jbus settingsChoice 2 Modify Jbus settings Choice 3 Display Jbus diagnosticsChoice 6 Display Jbus frames Choice 5 Return to Jbus Default ConfigurationAdditional Web pages Detailled status table Modbus register mapSSC INMC/NMTCMeasurement table Sensor Measurements table Environnement Sensor .3.3.1 Sensor Status tableSensor customisation table RO Global overview Examples of Modbus register mapMain UPS status UPS on AC Normal inputWord + Bit Main UPS status UPS on BatteryLow Battery Warning UPS on Bypass due to End of battery runtime UPS on Bypass due to manual order UPS on Manual Bypass UPS running Power Saving Mode Modbus Status Address Value Word + Bit Main UPS status Communication lostTable of alarms and UPS events Tables of alarms and eventsAppendices UPS OK Table of system alarms MGE MIB Snmp objectsPage Page MIB Trap Table des TrapsNetwork Management Proxy GlossaryIsxc MIB Management Information BaseRFC RebootNMS Network Management Station Snmp NSM Network Shutdown Module