11.2.2 Table des TRAPS : (1.3.6.1.4.1.705.1.11)
SNMP traps are sent when alarms appears and desappears.
Level : 1:informational , 2:major, 3:critical
MIB TRAP | Trap # | niveau |
|
|
|
Trap 1 | Level 3 | |
|
|
|
Trap 2 | Level 1 | |
|
|
|
Trap 5 | Level 3 | |
|
|
|
Trap 6 | Level 1 | |
|
|
|
Trap 7 | Level 3 | |
|
|
|
Trap 8 | Level 1 | |
|
|
|
Trap 11 | Level 2 | |
|
|
|
Trap 12 | Level 1 | |
|
|
|
Trap 13 | Level 2 | |
|
|
|
Trap 14 | Level 1 | |
|
|
|
Trap 17 | Level 2 | |
|
|
|
Trap 18 | Level 1 | |
|
|
|
Trap 21 | Level 3 | |
|
|
|
Trap 22 | Level 1 | |
|
|
|
Trap 23 | Level 3 | |
|
|
|
Trap 24 | Level 1 | |
|
|
|
Trap 31 | Level 3 | |
|
|
|
Trap 37 | Level 3 | |
|
|
|
Trap 38 | Level 1 | |
|
|
|
Trap 65 | Level 2 | |
|
|
|
Trap 66 | Level 2 | |
|
|
|
Trap 67 | Level 2 | |
|
|
|
Trap 68 | Level 2 | |
|
|
|
Nota1: This Information is not present with a Static Switch Cabinet unit.
If the Environment Sensor is detected , the following information are managed.: |
| |
|
|
|
- upsEnvironmentComFailure | Trap 53 | Level 2 |
|
|
|
- upsEnvironmentComOK | Trap 54 | Level 2 |
|
|
|
- upsEnvironmentTemperatureLow | Trap 55 | Level 2 |
|
|
|
- upsEnvironmentTemperatureHigh | Trap 56 | Level 2 |
|
|
|
- upsEnvironmentTemperatureOK | Trap 57 | Level 2 |
|
|
|
- upsEnvironmentHumidityLow | Trap 58 | Level 2 |
|
|
|
- upsEnvironmentHumidityHigh | Trap 59 | Level 2 |
|
|
|
- upsEnvironmentHumidityOK | Trap 60 | Level 2 |
|
|
|
- upsEnvironmentInput1Closed | Trap 61 | Level 2 |
|
|
|
- upsEnvironmentInput1Open | Trap 62 | Level 2 |
|
|
|
- upsEnvironmentInput2Open | Trap 64 | Level 2 |
|
|
|
- upsEnvironmentInput2Closed | Trap 63 | Level 2 |
|
|
|
The level is used to select traps to be sent to the supervisor. This adjustment is available from the “Notified applications” page |
| |
Network Management Card & Modbus/Jbus | 34022321XT indice :AE | Page 96/98 |
Network Management Teleservice Card
APC by Schneider Electric
www.apc.com