7 Server protection

7.1Set-up of the shutdown parameters

The Network Shutdown Module, on protected server boot, subscribes itself automatically to notified applications list and sends its essential data:

IP Address or hostname of the server on which it is installed: So that the card can inform it of power events.

Time required to shutdown the server (Shutdown Duration, configurable in the "Set-up" menu of each NSM): The card takes into account the longest shutdown time of all the Network Shutdown Modules subscribed (This is the Shutdown duration of the Shutdown parameters) page to manage UPS shutdowns without affecting any of Shutdown Modules connected.

During normal operation, the Network Shutdown Module periodically checks its connection with the card.

In case of a major power event, the card sends information to the Network Shutdown Module which reacts according to the situation. (shutdown order, programmed actions, messages to the administrator and to users via the network)

When the server shuts down, the Network Shutdown Module unsubscribes itself from the notified applications.

Network Management Card & Modbus/Jbus

34022321XT indice :AE

Page 56/98

Network Management Teleservice Card

 

 

APC by Schneider Electric

www.apc.com

Image 56
Contents Page Contents Notification Installation MGE MIBMGE Galaxy 7000 Network Management card presentation Connecting the UPS to the Ethernet network Protection of the computers / serversSupervision of the UPSs over the network Teleservice for Nmtc Direct sending of E-mailSending text messages SMS Environment Sensor optionTechnical data Hardware characteristicsConfiguration EMC CompatibilityAdministration NetworkEnvironment sensor MIB Management Information BaseModbus/Jbus for Inmc Default parameters BOOTP/DHCPMgeups 1UPS/NMTC+ 9 UPS/INMCIndications Installation Network Management Card & Modbus/Jbus InmcUnpacking and check on contents Installation in the UPS Sensor installation optionLED ACTInstallation Network Management Teleservice Card Nmtc Installation in the UPS Line Phone Port Nmtc Inmc ConfigurationConfigure IP parameters Your network is equipped with a Dhcp server Test after configuration Your network is not equipped with a Dhcp serverSupervision and administration by browser Optimising the performance of your browserUPS UPS propertiesUPS zone general information on the UPS Page Page Page Power Saving Mode representation Efficiency Booster Mode UPS measurements UPS status zone Essential information Viewing the alarms Viewing the About your UPS window On-line help Shutdown parameters Shutdonw criteria are describe below Measurements Event log Click on Event Log in the menuSystem log Click on System log. in the menuNotification Email NotificationPage Mail Message Settings SenderConfiguration Network settings Page System Notified Applications Page Central shutdown configuration TLSRSAWITH512MD5 Access controlTLS Page Date and time Firmware upload Characteristics Environment Status Environment Settings Page 4 Log Server protection Set-up of the shutdown parametersShutdown criteria managed by the Network Management Card Shutdown when backup time is less than Shutdown durationGeneral overview TeleserviceTeleservice procedure Page Configuration via RS232 Choice 1 Restart / ResetChoice 2 Modify Network settings Choice 2 Network ConfigurationChoice 1 Read Network settings MGE UPS Systems Network Management Card Choice 3 Lost password / Set Login Password to DefaultChoice 3 Set Ethernet speed Choice 4 Return to Default Configuration 10.1.1 RS232 link configuration and connection Modbus/Jbus installation & useInstallation 10.1.2 RS485 link configuration and connection 10.1.2.1 RS485 connectionPage 10.1.2.2 RS485 link configuration for 2 wires connexion Page 10.1.2.3 RS485 link configuration for 4 wires connexion Page Configuration of the JBUS/MODBUS communication parameters Choice 1 Display Jbus settings Choice 2 Modify Jbus settingsChoice 3 Display Jbus diagnostics Choice 4 Reset Jbus diagnosticsChoice 5 Return to Jbus Default Configuration Choice 6 Display Jbus framesAdditional Web pages Modbus register map Detailled status tableINMC/NMTC SSCMeasurement table Environnement Sensor .3.3.1 Sensor Status table Sensor Measurements tableSensor customisation table RO Examples of Modbus register map Global overviewUPS on AC Normal input Main UPS statusUPS on Battery Word + Bit Main UPS statusLow Battery Warning UPS on Bypass due to End of battery runtime UPS on Bypass due to manual order UPS on Manual Bypass UPS running Power Saving Mode Communication lost Modbus Status Address Value Word + Bit Main UPS statusAppendices Tables of alarms and eventsTable of alarms and UPS events UPS OK Table of system alarms Snmp objects MGE MIBPage Page Table des Traps MIB TrapGlossary IsxcMIB Management Information Base Network Management ProxyReboot NMS Network Management Station SnmpNSM Network Shutdown Module RFC