Schneider Electric 66124, 66123 Shutdown when backup time is less than, Shutdown duration

Page 58

7.2.2Initiating the shutdown procedure when the battery autonomy ratio is lower than: (If remaining time ratio under)

When the card detects that the remaining time ratio (percentage) is less than the configured level, the shutdown sequence is started. By default, this value is set at 20%.

This ratio is equal in % to :

Current autonomy time / Autonomy time announced at the beginning of the UPS on battery sequence

Note:

The UPS already manages an equivalent parameter for the end of backup pre-alarm.

The card does not accept values less than that programmed in the UPS.

Check the UPS documentation.

7.2.3 Shutdown when backup time is less than

When the Network Management Card detects that the percentage of backup time remaining is less than the value set, the shutdown sequence is started.

7.2.4 Shutdown duration

Duration (in seconds) required for the system protected by the Shutdown Modules to shut down.

The Network Shutdown Modules transmit their own "Shutdown duration" to the Network Management Card.

Based on these values (maximum Shutdown duration of all subscribed customer systems) that the card will send to the delayed shutdown order to the UPS.

Network Management Card & Modbus/Jbus

34022321XT indice :AE

Page 58/98

Network Management Teleservice Card

 

 

APC by Schneider Electric

www.apc.com

Image 58
Contents Page Contents Notification Installation MGE MIBMGE Galaxy 7000 Network Management card presentation Connecting the UPS to the Ethernet network Protection of the computers / serversSupervision of the UPSs over the network Sending text messages SMS Teleservice for NmtcDirect sending of E-mail Environment Sensor optionConfiguration Technical dataHardware characteristics EMC CompatibilityEnvironment sensor AdministrationNetwork MIB Management Information BaseModbus/Jbus for Inmc Mgeups Default parametersBOOTP/DHCP 1UPS/NMTC+ 9 UPS/INMCUnpacking and check on contents Installation Network Management Card & Modbus/Jbus InmcIndications LED Installation in the UPSSensor installation option ACTInstallation Network Management Teleservice Card Nmtc Installation in the UPS Line Phone Port Configure IP parameters ConfigurationNmtc Inmc Your network is equipped with a Dhcp server Test after configuration Your network is not equipped with a Dhcp serverUPS Supervision and administration by browserOptimising the performance of your browser UPS propertiesUPS zone general information on the UPS Page Page Page Power Saving Mode representation Efficiency Booster Mode UPS measurements UPS status zone Essential information Viewing the alarms Viewing the About your UPS window On-line help Shutdown parameters Shutdonw criteria are describe below Measurements Event log Click on Event Log in the menuSystem log Click on System log. in the menuNotification Email NotificationPage Mail Message Settings SenderConfiguration Network settings Page System Notified Applications Page Central shutdown configuration TLS Access controlTLSRSAWITH512MD5 Page Date and time Firmware upload Characteristics Environment Status Environment Settings Page 4 Log Server protection Set-up of the shutdown parametersShutdown criteria managed by the Network Management Card Shutdown when backup time is less than Shutdown durationTeleservice procedure TeleserviceGeneral overview Page Configuration via RS232 Choice 1 Restart / ResetChoice 1 Read Network settings Choice 2 Network ConfigurationChoice 2 Modify Network settings Choice 3 Set Ethernet speed Choice 3 Lost password / Set Login Password to DefaultMGE UPS Systems Network Management Card Choice 4 Return to Default Configuration Installation Modbus/Jbus installation & use10.1.1 RS232 link configuration and connection 10.1.2 RS485 link configuration and connection 10.1.2.1 RS485 connectionPage 10.1.2.2 RS485 link configuration for 2 wires connexion Page 10.1.2.3 RS485 link configuration for 4 wires connexion Page Configuration of the JBUS/MODBUS communication parameters Choice 3 Display Jbus diagnostics Choice 1 Display Jbus settingsChoice 2 Modify Jbus settings Choice 4 Reset Jbus diagnosticsChoice 5 Return to Jbus Default Configuration Choice 6 Display Jbus framesAdditional Web pages Modbus register map Detailled status tableINMC/NMTC SSCMeasurement table Environnement Sensor .3.3.1 Sensor Status table Sensor Measurements tableSensor customisation table RO Examples of Modbus register map Global overviewUPS on AC Normal input Main UPS statusUPS on Battery Word + Bit Main UPS statusLow Battery Warning UPS on Bypass due to End of battery runtime UPS on Bypass due to manual order UPS on Manual Bypass UPS running Power Saving Mode Communication lost Modbus Status Address Value Word + Bit Main UPS statusTable of alarms and UPS events Tables of alarms and eventsAppendices UPS OK Table of system alarms Snmp objects MGE MIBPage Page Table des Traps MIB TrapMIB Management Information Base GlossaryIsxc Network Management ProxyNSM Network Shutdown Module RebootNMS Network Management Station Snmp RFC