5 Configuration

5.1Configure IP parameters

Once the card has started:

Connect one end of the cable (3402226700) to the Service port.

If the environment sensor was previously connected, the card must be restarted in order to access the configuration menu. Connect the other end of the cable to the COM port (IOIOI) of a PC.

Launch a HyperTerminal™ type emulator with the foll owing configuration:

NMTC

INMC

Speed: 38400

Speed: 9600

Data bits: 8

Data bits: 8 toto

Parity: none

Parity: none

Stop bits: 1

Stop bits: 1

Flow control: none

Flow control: none

"Locally reproduce the characters entered" option: deactivated.

Enter MGEUPS or mgeups. The main menu is displayed:

Network Management Card & Modbus/Jbus

34022321XT indice :AE

Page 18/98

Network Management Teleservice Card

 

 

APC by Schneider Electric

www.apc.com

Image 18
Contents Page Contents Notification Installation MGE MIBMGE Galaxy 7000 Network Management card presentation Connecting the UPS to the Ethernet network Protection of the computers / serversSupervision of the UPSs over the network Sending text messages SMS Teleservice for NmtcDirect sending of E-mail Environment Sensor optionConfiguration Technical dataHardware characteristics EMC CompatibilityEnvironment sensor AdministrationNetwork MIB Management Information BaseModbus/Jbus for Inmc Mgeups Default parametersBOOTP/DHCP 1UPS/NMTC+ 9 UPS/INMCInstallation Network Management Card & Modbus/Jbus Inmc Unpacking and check on contentsIndications LED Installation in the UPSSensor installation option ACTInstallation Network Management Teleservice Card Nmtc Installation in the UPS Line Phone Port Configuration Configure IP parametersNmtc Inmc Your network is equipped with a Dhcp server Test after configuration Your network is not equipped with a Dhcp serverUPS Supervision and administration by browserOptimising the performance of your browser UPS propertiesUPS zone general information on the UPS Page Page Page Power Saving Mode representation Efficiency Booster Mode UPS measurements UPS status zone Essential information Viewing the alarms Viewing the About your UPS window On-line help Shutdown parameters Shutdonw criteria are describe below Measurements Event log Click on Event Log in the menuSystem log Click on System log. in the menuNotification Email NotificationPage Mail Message Settings SenderConfiguration Network settings Page System Notified Applications Page Central shutdown configuration Access control TLSTLSRSAWITH512MD5 Page Date and time Firmware upload Characteristics Environment Status Environment Settings Page 4 Log Server protection Set-up of the shutdown parametersShutdown criteria managed by the Network Management Card Shutdown when backup time is less than Shutdown durationTeleservice Teleservice procedureGeneral overview Page Configuration via RS232 Choice 1 Restart / ResetChoice 2 Network Configuration Choice 1 Read Network settingsChoice 2 Modify Network settings Choice 3 Lost password / Set Login Password to Default Choice 3 Set Ethernet speedMGE UPS Systems Network Management Card Choice 4 Return to Default Configuration Modbus/Jbus installation & use Installation10.1.1 RS232 link configuration and connection 10.1.2 RS485 link configuration and connection 10.1.2.1 RS485 connectionPage 10.1.2.2 RS485 link configuration for 2 wires connexion Page 10.1.2.3 RS485 link configuration for 4 wires connexion Page Configuration of the JBUS/MODBUS communication parameters Choice 3 Display Jbus diagnostics Choice 1 Display Jbus settingsChoice 2 Modify Jbus settings Choice 4 Reset Jbus diagnosticsChoice 5 Return to Jbus Default Configuration Choice 6 Display Jbus framesAdditional Web pages Modbus register map Detailled status tableINMC/NMTC SSCMeasurement table Environnement Sensor .3.3.1 Sensor Status table Sensor Measurements tableSensor customisation table RO Examples of Modbus register map Global overviewUPS on AC Normal input Main UPS statusUPS on Battery Word + Bit Main UPS statusLow Battery Warning UPS on Bypass due to End of battery runtime UPS on Bypass due to manual order UPS on Manual Bypass UPS running Power Saving Mode Communication lost Modbus Status Address Value Word + Bit Main UPS statusTables of alarms and events Table of alarms and UPS eventsAppendices UPS OK Table of system alarms Snmp objects MGE MIBPage Page Table des Traps MIB TrapMIB Management Information Base GlossaryIsxc Network Management ProxyNSM Network Shutdown Module RebootNMS Network Management Station Snmp RFC