Schneider Electric 66124, 66123 user manual Modbus register map, Detailled status table

Page 76

10.3 Modbus register map

10.3.1 Detailled status table

 

 

 

 

 

 

 

 

 

 

Word

 

 

Bit

 

Status Familly

 

Status description

 

 

Status to 0

 

 

Status to 1

 

 

 

 

 

for

 

 

 

 

 

 

 

hex

 

 

0 - F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BMS design

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load powered

 

No

 

yes

40

 

0

 

Status

 

(protected or not protected)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load on inverter

 

No

 

yes

40

 

1

 

Status

 

(UPS on AC normal or on Battery and Q5N closed)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS general alarm – UPS HMI Led Red (Nota 8)

 

No

 

yes

40

 

2

 

Major Fault

 

 

 

 

 

 

 

 

 

 

 

 

UPS on Battery (Nota 5)

 

No

 

yes

40

 

4

 

Status

 

 

 

 

 

 

 

 

 

 

 

 

Low Battery Warning (Nota 5)

 

No

 

yes

40

 

5

 

Major Warning

 

 

 

 

 

 

 

 

 

 

 

 

End of Battery Runtime (Nota 5)

 

No

 

yes

40

 

6

 

Major Fault

 

 

 

 

 

 

 

 

 

 

 

 

Load on bypass

 

No

 

yes

40

 

7

 

Status

 

 

 

 

 

 

 

 

 

 

 

 

Communication fault

 

absent

 

present

40

 

9

 

Major Fault

 

 

 

 

 

 

 

 

 

 

 

 

UPS overload

 

No

 

yes

40

 

 

A

Major Warning

 

 

 

 

 

 

 

 

 

 

 

 

Emergency stop

 

absent

 

present

40

 

 

B

Major Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery to be checked

 

No

 

yes

40

 

 

D

Minor Fault

 

or External battery monitoring fault (Nota 5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Device ventilation fault (Nota 6)

 

No

 

yes

40

 

 

E

Major Fault

 

 

 

 

 

 

 

 

 

 

 

UPS type (Nota 4)

 

0, 5, 6 : undefine,

41

 

1

 

Setting

 

 

 

 

1 : Unitary,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41

 

2

 

Setting

 

 

 

 

2 : Modulare,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41

 

3

 

Setting

 

 

 

 

3 : parallel:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 : SSC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual bypass switch (Q3BP)

 

Open

 

Closed

41

 

6

 

Status

 

 

 

 

 

 

 

 

 

 

 

 

Rectifier major failure (Nota 5)

 

No

 

Yes

41

 

9

 

Major Fault

 

 

 

 

 

 

 

 

 

 

 

 

Load not protected in unitary

 

No

 

Yes

41

 

 

A

Major Fault

 

Load not protected in parallel (external Q5N)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS in Power Saving Mode (Nota 9)

 

No

 

Yes

41

 

 

B

Status

 

 

 

 

 

 

 

 

 

 

 

 

UPS HMI Orange Led - (Nota 8)

 

No

 

Yes

41

 

 

C

Major Warning

 

 

 

 

 

 

 

 

 

 

 

 

Battery present (Nota 5)

 

absent

 

present

42

 

0

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

Battery test in progress (Nota 5)

 

No

 

yes

42

 

8

 

Status

 

 

 

 

 

 

 

 

 

 

 

 

Battery over temperature (Nota 5)

 

No fault

 

Fault

42

 

 

A

Major Fault

 

 

 

 

 

 

 

 

 

 

 

 

Battery circuit breaker (QF1) (Nota 5)

 

Open

 

Closed

42

 

 

F

Status

 

 

 

 

 

 

 

 

 

 

 

 

AC Normal switch (Q1)

 

Open

 

Closed

44

 

3

 

Status

 

 

 

 

 

 

 

 

 

 

 

 

AC Normal voltage out of tolerance (Nota 5)

 

No

 

yes

44

 

8

 

Major Warning

 

 

 

 

 

 

 

 

 

 

 

 

Rectifier (PFC) fuse fault (Nota 5)

 

No

 

yes

44

 

9

 

Major Fault

 

 

 

 

 

 

 

 

 

 

 

 

AC Normal frequency out of tolerance (Nota 5)

 

No

 

yes

44

 

 

B

Major Warning

 

 

 

 

 

 

 

 

 

 

 

 

Redundancy lost for parallel

 

No

 

yes

45

 

7

 

Major Warning

 

 

 

 

 

 

 

 

 

 

 

 

K2S fault (Nota 7)

 

No

 

yes

45

 

9

 

Minor Fault

 

 

 

 

 

 

 

 

 

 

 

 

K2S state (Nota 7)

 

No

 

yes

45

 

 

A

Status

 

 

 

 

 

 

 

 

 

 

 

 

Overlaptransfert fault on SSC

 

No

 

yes

45

 

 

B

Minor Warning

 

 

 

 

 

 

 

 

 

 

 

 

UPS on Maintenance position

 

No

 

yes

46

 

1

 

Status

 

 

 

 

 

 

 

 

 

 

 

 

AC bypass overload (Nota 7)

 

No

 

yes

46

 

5

 

Major Warning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Network Management Card & Modbus/Jbus

34022321XT indice :AE

Page 76/98

Network Management Teleservice Card

 

 

APC by Schneider Electric

 

 

www.apc.com

 

 

Image 76
Contents Page Contents Notification Installation MGE MIBMGE Galaxy 7000 Network Management card presentation Connecting the UPS to the Ethernet network Protection of the computers / serversSupervision of the UPSs over the network Teleservice for Nmtc Direct sending of E-mailSending text messages SMS Environment Sensor optionTechnical data Hardware characteristicsConfiguration EMC CompatibilityAdministration NetworkEnvironment sensor MIB Management Information BaseModbus/Jbus for Inmc Default parameters BOOTP/DHCPMgeups 1UPS/NMTC+ 9 UPS/INMCUnpacking and check on contents Installation Network Management Card & Modbus/Jbus InmcIndications Installation in the UPS Sensor installation optionLED ACTInstallation Network Management Teleservice Card Nmtc Installation in the UPS Line Phone Port Configure IP parameters ConfigurationNmtc Inmc Your network is equipped with a Dhcp server Test after configuration Your network is not equipped with a Dhcp serverSupervision and administration by browser Optimising the performance of your browserUPS UPS propertiesUPS zone general information on the UPS Page Page Page Power Saving Mode representation Efficiency Booster Mode UPS measurements UPS status zone Essential information Viewing the alarms Viewing the About your UPS window On-line help Shutdown parameters Shutdonw criteria are describe below Measurements Event log Click on Event Log in the menuSystem log Click on System log. in the menuNotification Email NotificationPage Mail Message Settings SenderConfiguration Network settings Page System Notified Applications Page Central shutdown configuration TLS Access controlTLSRSAWITH512MD5 Page Date and time Firmware upload Characteristics Environment Status Environment Settings Page 4 Log Server protection Set-up of the shutdown parametersShutdown criteria managed by the Network Management Card Shutdown when backup time is less than Shutdown durationTeleservice procedure TeleserviceGeneral overview Page Configuration via RS232 Choice 1 Restart / ResetChoice 1 Read Network settings Choice 2 Network ConfigurationChoice 2 Modify Network settings Choice 3 Set Ethernet speed Choice 3 Lost password / Set Login Password to DefaultMGE UPS Systems Network Management Card Choice 4 Return to Default Configuration Installation Modbus/Jbus installation & use10.1.1 RS232 link configuration and connection 10.1.2 RS485 link configuration and connection 10.1.2.1 RS485 connectionPage 10.1.2.2 RS485 link configuration for 2 wires connexion Page 10.1.2.3 RS485 link configuration for 4 wires connexion Page Configuration of the JBUS/MODBUS communication parameters Choice 1 Display Jbus settings Choice 2 Modify Jbus settingsChoice 3 Display Jbus diagnostics Choice 4 Reset Jbus diagnosticsChoice 5 Return to Jbus Default Configuration Choice 6 Display Jbus framesAdditional Web pages Modbus register map Detailled status tableINMC/NMTC SSCMeasurement table Environnement Sensor .3.3.1 Sensor Status table Sensor Measurements tableSensor customisation table RO Examples of Modbus register map Global overviewUPS on AC Normal input Main UPS statusUPS on Battery Word + Bit Main UPS statusLow Battery Warning UPS on Bypass due to End of battery runtime UPS on Bypass due to manual order UPS on Manual Bypass UPS running Power Saving Mode Communication lost Modbus Status Address Value Word + Bit Main UPS statusTable of alarms and UPS events Tables of alarms and eventsAppendices UPS OK Table of system alarms Snmp objects MGE MIBPage Page Table des Traps MIB TrapGlossary IsxcMIB Management Information Base Network Management ProxyReboot NMS Network Management Station SnmpNSM Network Shutdown Module RFC